EN
WIKA operating instructions DELTA-plus, DELTA-comb and DELTA-switch
24
14532078.01 12/2021 EN/DE
■
Voltages greater than AC 50 V or DC 75 V:
- Do not connect circuits simultaneously with extra-low voltage circuits or with
safety extra-low voltage (SELV) or protected extra-low voltage (PELV).
- Circuits must offer a device, external to the measuring instrument, that
enables the instrument to be isolated from the electrical supply. This must be
easily accessible and be marked as the isolation device for the instrument.
- Cables for the circuit must fulfil the isolation requirements and conform to, for
example, IEC 60227 or IEC 60245.
■
With flexible connection leads, use isolated end splices.
■
Connection leads must be suited to the ambient temperature range of the
application.
■
Seal the cable entry with the appropriate approved cable glands.
6. Commissioning, operation
Only use cable
with a diameter
of 7 ... 13 mm
Version of cable socket
14078258.01
■
Install the connection cables securely.
74
96
M20 x 1.5
Содержание DPG40