58
9 Supplement
WIKA Operating Instructions - Process pressure transmitter CPT-2x
1
2
0 °C
(32 °F)
-40 °C
(-104 °F)
50 °C
(122 °F)
80 °C
(176 °F)
150 °C
(302 °F)
100 °C
(212 °F)
-40 °C
(-104 °F)
Fig. 34: Temperature derating CPT-2x, version up to +150 °C (+302 °F)
1 Process temperature
2 Ambient temperature
SIP process temperature (SIP = Sterilization in place)
Applies to instruments configurations suitable for vapour, i.e. material measuring cell seal EPDM or
FFKM (Perlast G75S).
Vapour stratification up to 2 h
+150 °C (+302 °F)
Process pressure
Permissible process pressure
see specification "
process pressure
" on the type label
Mechanical stress
10)
Vibration resistance
4 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
Shock resistance
50 g, 2.3 ms according to EN 60068-2-27 (mechanical
shock)
11)
Ambient conditions
Version
Ambient temperature
Storage and transport temperature
Standard version
-40 … +80 °C (-40 … +176 °F) -60 … +80 °C (-76 … +176 °F)
Version IP66/IP68 (1 bar)
-20 … +80 °C (-4 … +176 °F)
-20 … +80 °C (-4 … +176 °F)
Version IP68 (25 bar), with connection
cable PUR
-20 … +80 °C (-4 … +176 °F)
-20 … +80 °C (-4 … +176 °F)
Version IP68 (25 bar), connection ca-
ble PE
-20 … +60 °C (-4 … +140 °F)
-20 … +60 °C (-4 … +140 °F)
Electromechanical data - version IP66/IP67 and IP66/IP68 (0.2 bar)
12)
Options of the cable entry
Ʋ
Cable entry
M20 x 1.5; ½ NPT
Ʋ Cable gland
M20 x 1.5; ½ NPT (cable diameter see below table)
Ʋ Blind plug
M20 x 1.5; ½ NPT
10)
Depending on the instrument version.
11)
2 g with housing version stainless steel double chamber
12)
IP66/IP68 (0.2 bar), only with absolute pressure.