English
5
SAE J1628 RECOMMENDED PROCEDURES
For the purpose of Automotive A/C Testing with respect to the SAE J1627 standard, the following leak testing
procedure applies:
1. Operate
the
ELD-H
in high sensitivity mode.
2. Leak test with the engine not in operation.
3. The air conditioning system shall be charged with sufficient refrigerant to have a gauge pressure of at
least 340 kPa when not in operation. At temperatures below 15
°
C, leaks may not be measurable, since
this pressure may not be reached.
4. Take care not to contaminate the detector probe tip. If the part is particularly dirty, it should be wiped off
with a dry shop towel or blown off with shop air. No cleaners or solvents shall be used, since many
electronic detectors are sensitive to their ingredients.
5. Visually trace the entire refrigerant system, and look for signs of air-conditioning lubricant leakage,
damage, and corrosion on all lines, hoses, and components. Each questionable area shall be carefully
checked with the detector probe, as well as all fittings, hose to line couplings, refrigerant controls, service
ports with caps in place, brazed or welded areas, and areas around attachment points and hold-downs on
lines and components.
6. Always follow the refrigerant system around in a continuous path so that no areas of potential leaks are
missed. If a leak is found, always continue to test the remainder of the system.
7. At each area checked, the probe shall be moved around the location, at a rate no more than 25-50 mm/s
and no more than 5 mm from the surface completely around the position. Slower and closer movement of
the probe often helps locate the exact position of the leak.
8. An apparent leak shall be verified at least once by blowing shop air into the area of the suspected leak, if
necessary, and repeating the check of the area. In cases of very large leaks, blowing out the area with
shop air often helps locate the exact position of the leak.
9. Leak testing of the evaporator core while in the air conditioning module shall be accomplished by turning
the air conditioning blower on high for a period of 15 sec. minimum, shutting it off, then waiting for the
refrigerant to accumulate in the case for time specified by paragraph 10, then inserting the leak detector
probe into the blower resistor block or condensate drain hold if no water is present, or into the closest
opening in the heating/ventilation/air conditioning case to the evaporator, such as the heater duct or a vent
duct. If the detector alarms, a leak apparently has been found.
10. The accumulation time shall be 10 minutes.
11. Following any service to the refrigerant system of the vehicle, and any other service which disturbs the
refrigerant system, a leak test of the repair and of the service ports of the refrigerant system shall be done.
Содержание ELD-H
Страница 1: ...ELD H Refrigerant Gas Leak Detector User s Guide...
Страница 20: ...19 NOTES...
Страница 21: ...20 NOTES...
Страница 22: ...21 NOTES...
Страница 24: ......