General Technical Data
Climatic conditions
Ambient operating temperature T
B
–25 to +55 °C
Storage temperature
–25 to +70 °C
Relative humidity
10 to 95%, no condensation
Climatic conditions (EN 61131-2)
Air pressure in operation
860 to 1060 hPa
___________________________________________________________________________
Mechanical strength
Sinusoidal vibration (EN 60068-2-6)
Frequency range
5 to 150 Hz
Amplitude
3.5 mm (5 to < 9 Hz)
Acceleration
1 g (9 to 150 Hz)
Number of cycles
10 per axis (on 3 axes)
Broad-band random vibration (EN 60068-2-64)
Frequency range
5 to 500 Hz
Acceleration 4.9
g
Semi-sinusoidal shock (EN 60068-2-27)
Acceleration / Duration
15 g / 11 ms
___________________________________________________________________________
Electrical safety
Protect. type housing / terminals (EN 60529)
IP 40 / IP 20
Finger-proof
to DIN EN 50274
Clearance/creepage (EN 61131 -2)
Overvoltage category
III
Contamination level
2 inside, 3 outside
Test voltage
DC 24 V
350 V
AC 300 V
2000 V
___________________________________________________________________________
Electromagnetic compatibility
Burst EN
61000-4-4
Supply 2
kV
I/O 1
kV
Functional earth (shield)
1 kV
Surge
EN 61000-4-5, diff. mode / com. mode
Supply
1.0 kV / 2.0 kV
I/O
1.0 kV / 2.0 kV
Functional earth (shield)
– / 1.0 kV
Communication (field bus)
– / 1.0 kV
High-frequency electromagnetic fields acc. to EN
61000-4-3
10 V/m
Conducted induced disturbances
acc. to EN 61000-4-6
10 V
Electrostatic discharge
acc. to EN 61000-4-2
4 kV (contact discharge)
8 kV (air discharge)
Interference emissions
acc. to DIN EN 55011:2003 class A
40 dB (V/m) (20 - 230 MHz)
47 dB (V/m) (230 -1000 MHz)
___________________________________________________________________________
System safety (not for bus coupling modules)
Safety integrity level
SIL 3 (IEC/EN 61508/EN 62061)
The system must be switched off and restarted at least once a year and the safety
functions must be tested!
Approvals
SIL 3 (EN 61508/EN 62061) and PLe/category 4 (EN ISO 13849-1) (not for bus coupling modules)
TÜV
cULus
Unless otherwise stated,
the general technical
data applies to all base,
expansion and bus
coupler modules.