Operating instructions for safety module mod. NC96 MAT
WIDE Automation
S.r.l._Via Malpasso, 1340 I-47842 San Giovanni in Marignano [RN] Italia_Tel. +39 0541 827239 0541 825021_www.wideautomation.it
Su
b
je
c
t
to
t
e
c
h
n
ic
a
l c
h
a
n
g
e
s
w
ith
o
u
t
n
o
tic
e
,
n
o
r
e
sp
o
n
s
ib
ili
ty
w
ill
b
e
a
s
s
u
m
e
d
f
o
r
e
ve
ry
d
e
ta
il.
©
W
ID
E
AU
T
O
M
AT
IO
N
S.
r.
l.
–
NC9
6
Op
e
ra
tin
g
I
n
s
tr
u
c
tio
n
(
E
N
)
re
v.
2
_
0
8
/1
6
–
Pa
g
.
2
/2
LED indications
FUNCTION
LED
Colour Status
Operating voltage
Power
Green
On
Output 13-14 and 23-24: OPEN
Output 31-32: CLOSED
CH1, CH2 Green
Off
Output 13-14 and 23-24: CLOSED
Output 31-32: OPEN
CH1, CH2 Green
On
Dimensions
TECHNICAL DATA
Parameter
Value
Container Material
PA
Dimensions
114,5 x 99 x 22,5 mm
Weight
160 g
Operating environmental conditions
Temperature: -5 … +55 °C
Relative Humidity: 4% … 100%
Pressure: 86 … 106 kPa
Environmental storage conditions
Temperature: -25 … +70 °C
Relative Humidity: 5% … 95%
Pressure: 86 … 106 kPa
Degree of protection (IEC 60529)
IP20
Degree of contamination
2
Assembly
35mm DIN standard Rail
Connection Type
Screw terminals
Supply Voltage
24V -15%/+10% (AC 50 ÷ 60 Hz)
Internal Fuse on the power supply
630mA fast fuse
Current consumption
@24Vdc: 25mA min, 70mA max; @24Vac: 110 min, 220 Max
Safety Output Switching Voltage
240Vac max
Switching current AC-1 / Electrical Life
3A (AC/DC) (safety outputs) / > 10
5
cycles
Minimum Switching current @10V
10mA
Safety Output Switching Power
720VA max
Front View
External fuse at the Output
4A gG (according IEC EN 60269-1)
Safety Output Terminals
13 -14, 23 – 24
Auxiliary Output Terminals
31 - 32 NC (optocoupled)
Usage Category / Electrical Life
(SAFETY Outputs)
AC-15: 1.4A/240V (inductive load, cosφ=0.3)/10
5
cycles
DC-13: 1A / 24V / 10
5
cycles
Auxiliary NC Output parameters
max: 60 mA @ 24 Vdc
Useful Lifetime
10 years
OFF state response time
20mS
Safety Category and PL
(EN ISO 13849-1:2015)
CAT. 3
PL-d
PL-e
PL-e
nop (number of operation / year)
(load: AC-15: 1,4 A / 250 Vac)
66000
31900
19000
MTTFd (years)
30
62
100
PFHd
2.65x10
-7
8.84x10
-8
4.29x10
-8
TM
20 years
Vibration Resistance
EN ISO 13856-1:2013, EN ISO 13856-2:2013
Mechanical Life (# of cycles)
10
7
EMC Compliance
EN 61326-3-1:2011, EN 55011:2011
In accordance with
EN 60204-1:2006+A1:2009, EN ISO 13849-1:2015,
EN ISO 13856-1:2013, EN ISO 13856-2:2013
Approvals
TÜV IT 0948 15 MAC 0061 B
UL CERTIFICATION REQUIREMENTS
Power Source (input)
Input Terminals
Voltage
Max Current
A1 – A2
24 Vdc/ac
220mA / 70mA
Auxiliary Output (SAFETY)
Output Terminals
Contacts Type
General Use or resistive
Pilot Duty
13 – 14 / 23 – 24
NO
3A/240Vac Res
1.4A/240Vac
1A/24Vdc
Signalling Outputs (SIGNAL)
Output Terminals
Contacts Type
Nom. Ratings
31 – 32
NC
60mA/24Vdc
Environmental Ratings
Max. Surrounding Air Temperature: 55°C
Pollution Degree: 2
Environmental designation
Open type equipment
Installation Notes
Use with min. 60°C copper (CU) conductor only
Terminal tightening torque: 5-7 LbIn (0,56-0,79 Nm)