TECHNICAL  SUPPORT 

Telephone: 0161 331 5700 

E-mail: [email protected]

 

http://www.whitecroftlighting.com/

 

INSTALLATION 

Please note that this leaflet shows the installation process for both the small and 
medium housing products. Any differentiation in the process will be highlighted. 

 

SMALL HOUSING 

 

MEDIUM HOUSING 

 

1. Mount the unit to the wall using the diagram fig.1. Ensure that a suitable air gap between the 
highest point of the luminaire and any features above is maintained. See fig. 2. Use suitable 
mounting hardware. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

SMALL HOUSING 

 

MEDIUM HOUSING 

 

2. To set the angle of the luminaire loosen the grub screw and then use a spanner to loosen 
the nut. The luminaire will then freely pivot on the bracket. Once you have set the luminaire to 
the desired angle tighten the nut with a spanner then tighten the grub screw to the torque 
ratings as shown in fig.3. You may wish to set the angle before or after wiring the luminaire in 
place. Note that you should not angle the luminaire greater than 100° off horizontal (fig.4). 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

SMALL HOUSING 

 

MEDIUM HOUSING 

 

3. To access the luminaire internals remove the 4 
hex bolts from the upper section. The lower section 
will come loose. Ensure you have hold of the lower 
section as the two halves become disconnected as 
fig 5.   
Remove the internal terminal block cover if 
required. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

 

 

 
 
 
 

SMALL HOUSING 

 

MEDIUM HOUSING 

 

4. Wire the mains to the luminaire as per the images in fig.6. Feed through the mains 
cable via the IP gland ensuring correct installation as to not compromise the integrity of 
the product. Use a cable suitable for exterior use. The gland will accept wire with a 
diameter between 9 and 12mm. This product is not suitable for through wiring. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

5. To connect a DALI pair 
to the internal LED driver 
you will need to first 
break an extra hole into 
the luminaire housing 
before using a suitable IP 
gland and wire to the 
terminal blocks as 
specified in image 4. 
 
6. Carefully reattach the 
terminal block cover and 
lower section (tighten 
screws evenly) and 
reinstate the mains 
supply. 

 
 

Fig1 

Fig2 

Fig3 

Fig4 

Fig5 

Fig6 