4.  Flaring work.

A) Firmly hold copper pipe in a 

die in the dimension shown in 
the table below.

Connection Adjustment

1.  Align the pipes to be connected.
2.  Unscrew the flare nut with your 

fingers and then with a wrench 
and screw wrench, as shown in 
the following figure.

Caution:

 Excessive twisting may 

break the nut, depending on the 
installation conditions.

Electrical work

1. If there is serious safety problem 

about the power supply, the 
technicians should refuse to install 
the air conditioner and explain to the 
client until the problem is solved.

2. Power voltage should be in the 

range of 90%~110%of rated 
voltage.

3. The creepage protector and main 

power switch with a 1.5 times 
capacity of Max. Current of the unit 
should be installed in power circuit.

4. Ensure the air conditioner is 

grounded well.

5. According to the attached 

Electrical Connection Diagram 
located on the panel of the 
outdoor unit to connect the wire.

6. All wiring must comply with local 

and national electrical codes and 
be installed by qualified and 
skilled electricians.

7. An individual branch circuit and 

single receptacle used only for 
this air conditioner must be 
available. See the following table 
for suggested wire sizes and fuse 
specifications:

Electric safety regulations for the initial Installation

19

Refrigerant piping connection

20

Electrical work

Bar

Cooper
pipe

Handle

Clamp
handle

Yoke

Red arrow mark

Flare

nut

Pipings

Indoor unit
tubing

6,35

9,52

12,70

16

1500 (153 kgf/cm)

2500 (255 kgf/cm)

3500 (357 kgf/cm)

4500 (459 kgf/cm)

1600 (163 kgf/cm)

2600 (265 kgf/cm)

3600 (367 kgf/cm)

4700 (479 kgf/cm)

Máx.

A (mm)

Mín.

1,3

1,6

1,8

2,2

0,7

1,0

1,0

2,0

6,35

9,52

12,70

16

OUTER

DIAMETER (mm)

OUTER

DIAMETER (mm)

TIGHTENING

TORQUE (N/cm)

ADITIONAL TIGHTENING

TORQUE (N/cm)

Содержание E)24C6CHLW

Страница 1: ...INSTRUCTIONS MANUAL SPLIT TYPE ROOM AIR CONDITIONER INVERTER TYPE Models S5 21 22 W_R22_ENGLISH_130705A WAS C E 12P5CHLWP WAS C E 18P5CHLWP...

Страница 2: ...If you need to dispose of this appliance in the future do NOT throw it away with the rest of your domestic garbage Instead please take the appliance to the nearest WEEE collection point where availab...

Страница 3: ...p firearms away It may cause fire 6 Do not operate or stop the unit by switching on or off the power It may cause electric shock or fire due to heat generation 7 Do not operate with wet hands or in da...

Страница 4: ...ean the air conditioner with water Water may enter the unit and degrade the insulation It may cause an electric shock 20 Ventilate the room well when used together with a stove etc An oxygen shortage...

Страница 5: ...beforehand 1 Site with machine oil 2 Sites with a high concentration of salinity such as coastal areas 3 Sites with sulfuric gas such as hot water springs 4 Sites with high frequency equipment such a...

Страница 6: ...than 5 meters 16 feet and for pipes measuring at least 10 meters 33 feet in length 7 The site must provide enough space around the unit as shown in the diagram 8 Children must not be able to access t...

Страница 7: ...ion purposes only 2 Copper lines must be insulated independently 7 8 5 4 2 3 1 Indoor unit Outdoor unit 6 6 More than 12cm More than 12cm Air filter More than 200cm More than 60cm More than 30cm More...

Страница 8: ...install the drain hose as illustrated below 2 When connecting extension drain hose insulate the connecting part of extension drain hose with a shield pipe do not let the drain hose slack Connective p...

Страница 9: ...ntly windy 4 If the installation site is exposed to heavy winds such as in coastal areas place the unit along the widest part of the wall or use protective plates 7 If need suspending installation the...

Страница 10: ...le longer than the measured distance D Cut the cable 1 5m longer than the pipe length 2 Burr removal A Completely remove all burrs from the cut cross section of pipe tube B Put the end of the copper t...

Страница 11: ...air conditioner is grounded well 5 According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire 6 All wiring must comply with local and national...

Страница 12: ...ording to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire 6 All wiring must comply with local and national electrical codes and be installed by...

Страница 13: ...l work Electrical work Wire connector of outdoor unit 1 Remove the electrical control board cover from the outdoor unit by loosening the screw 2 Connect the connective cables to the terminals as ident...

Страница 14: ...Operating current rises 3 Cooling or heating efficiency drops 4 Moisture in the refrigerant circuit may freeze and block capillary tubing 5 Water may lead to corrosion of Air purging with vacuum pump...

Страница 15: ...cuation is complete fully close the handle Lo of the manifold valve and stop the operation of the vacuum pump Make evacuation for 15 minutes or more and check that the compound meter indicates 76cmHg...

Страница 16: ...itioner may attract condensation Please sets the vertical air flow louver to its maximum angle vertically to the floor and set HIGH fan mode Optimum performance will be achieved within these operating...

Страница 17: ...erature sensor inside front panel Panel Infra red signal receiver Drain hose connector and refrigerant gas connector Remote control Connector cable Detection valve Drain hose and refrigerant connectin...

Страница 18: ...vate the programs To replace batteries 1 Slide out the battery compartment cover located in the back part of the remote control 2 Install the two AAA batteries in the compartment indicated in the draw...

Страница 19: ...door temperature setting FAN SPEED This button is used for setting Fan Speed in the sequence that goes from AUTO LOW MED to HIGH then back to Auto ON OFF Push this button to start the unit operation P...

Страница 20: ...ower and the OPERATION indicator lamp on the display panel of the indoor unit starts flashing 1 Use the MODE select button to select AUTO 2 Push the TEMP button to set the desired room temperature The...

Страница 21: ...tion movement would alter automatically SLEEP mode Press the sleep button to activate the sleep mode To deactivate press the button again Cold only mode The indoor unit fan operates at a low velocity...

Страница 22: ...g operation and the signal h will be shown on the DIGITAL DISPLAY area You are now ready to reset the time of the STOP operation 2 Push the TIMER OFF button again to set the time you want to stop the...

Страница 23: ...HEATING performance may be impaired due to too restricted air flow area Do not operate unit with horizontal louver in closed position When the air conditioner is connected to power initial power the h...

Страница 24: ...lean the fresh air filter at least once a month and replace every 4 to 5 months Use a vacuum cleaner then dry 6 Clean the support frame using a vacuum cleaner or water After dry air filter air filter...

Страница 25: ...t is blown out from the indoor unit This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit A peculiar smell comes out from the indoor uni...

Страница 26: ...indicator or other indicator flash 5 times per second and the flashing is not stop by disconnecting and connecting the unit 2 Frequent change of fuses and malfunctions in the switch circuit 3 Water sp...

Страница 27: ...Notes Notes 52 Notes Notes 51...

Отзывы: