   CZ-4 ZONING SYSTEM FEATURES

 

 

 
 

         

 

 

 
                   Table of Contents 
           

Installation                            2 

           Operation                             2-3 
           Set-Up for Various 
           HVAC Equipment                 3 

           

Leaving Air Sensor               3-4 

           Timers                                   4   
           ZoneAdder                            4 
           Checkout                               4 
           Wiring                                   4-5 
           Troubleshooting                    5 
           Wiring Diagram                     6  

 
INSTALLATION 

The  CZ-4  is a four (4) zone control panel that controls up to four 
zones of heating and cooling.  The CZ-4  panel is the central control 
panel that all zone dampers, zone thermostats, HVAC Equipment, 
power transformer, Leaving Air  Sensor and   ZoneAdder

  panels are 

wired.   
 
When installing the CZ-4 panel it is important to pick a central location 
where it is most convenient to bring all the wires.  Most often this is at  
the furnace or air handler.  It is often the most convenient location 
and closest to power, the HVAC unit controls and the zone dampers 
when typically located at or near the plenum.  
 

 
The CZ-4 case and cover are made of sturdy ABS plastic and can be 
mounted to any flat surface.  It is recommended that the panel be 
mounted to a wall or return plenum and NOT on the furnace or 
plenum where it will be in contact with the hot temperatures.  The 
panel can be located in an attic space or in an enclosed cabinet of a 
rooftop unit,  in order for the panel to be out of direct exposure to the 
elements.   
 
The cover easily removes from the case by pulling firmly and 
separating the cover from the case exposing the circuit board.  There 
are 4 key-hole mounting points in each corner of the case.  The case 
has openings in the rear of the case as well as the side for all wiring.  
Wiring can come from the back as well as the side in order to make a 
neat installation.   

 

OPERATION 

The CZ-4 can control various types of HVAC Equipment all from the 
same panel.  The CZ-4  features allow the use of single stage 
thermostats to control up to three  stage heating and two  stages 
cooling and simple heat pump thermostats to control heat  pumps.  
The  CZ-4  has various features that make installation and checkout 
very simple for all of the board’s functionality.   
 
The  CZ-4’s basic function is zone control.  On a call for heating or 
cooling, the panel will accept the first call from any zone.  Upon 
accepting this call the CZ-4  will open the damper(s) to the zone(s) 
calling, close the damper(s) to those zones not calling, activate the 
needed HVAC controls for heating or cooling, whichever is being 
called and not accept any calls for the opposite mode.   

Zone Terminal Connections 
for Zone Thermostats 
& Zone Dampers 

24VAC 
Transformer 
Terminals 

Automatic 
Resetting Fuse 

Zone Calling 
Indicators 

Mode DIP 
Switches 

HVAC 
Equipment 
Connections 

Leaving Air Sensor 
(CLAS) Terminals 

ZONE ADDER 
(CAZ-2 panel) 
RJ11 Connection 

 Adjustable 
Heating Limit 

Mounting 
Keyholes 
Two at Top 
also. 

Adjustable Second 
Stage Timer 

Power Indicator 
LED 

Boot Button 

System Mode 
Indicator LED 

Purge Override 
Button 

No Sensor Jumper 

Содержание CZ-4

Страница 1: ...FORM 2045 2 1306 2013 White Rodgers by Permission 37 6864B Model CZ 4 Installation and Operating Instructions ...

Страница 2: ...e by pulling firmly and separating the cover from the case exposing the circuit board There are 4 key hole mounting points in each corner of the case The case has openings in the rear of the case as well as the side for all wiring Wiring can come from the back as well as the side in order to make a neat installation OPERATION The CZ 4 can control various types of HVAC Equipment all from the same p...

Страница 3: ...3 O TO W Switch is placed to ON when using Heat Pump thermostats that use an O terminal to activate the reversing valve in COOLING The O on the thermostat is wired to W on the zone terminal in order to determine if the call is for heating or cooling All zone thermostats must operate and be wired the same way 4 B TO W Switch is used when using Heat Pump thermostats that use a B terminal to activate...

Страница 4: ...time the unit has already been supplying the first mode in order to determine how long it will hold off the opposite call If an opposite call is made shortly after the first call the opposite call may be held off for as much as 20 minutes If the first call or subsequent calls for the first call mode has had that mode operating for up to 20 minutes already and an opposite call comes in after 20 min...

Страница 5: ... all cases eliminate the problem If not the following procedure can help isolate the problem Zone s Not Calling Each zone has a Green LED next to the zone relay when it is calling and that calling is being recognized by the CZ 4 If a zone is supposed to be calling and the Zone LED is not on check for 24VAC across the thermostat terminal C and the Y if a Cool call W if a Heat Call or G if a Fan cal...

Страница 6: ... G Y R W O B C CLOSE OPEN COM ZONE CONNECTIONS THERMOSTAT DAMPER Single Stage Thermostat ON OFF HEAT PUMP EQUIP FAN ON IN HEAT STAT O TO W STAT B TO W FAN IN PURGE EMERGENCY HEAT STAGE TIME ZONE CTRL 3 1 2 3 4 5 6 7 8 W2 W1 Y1 Y2 O G E B R First Stage Cooling Relay 24V Transformer Second Stage Cooling Relay First Stage Heat Relay Fan Relay EQUIPMENT HEATING COOLING EQUIPMENT Second Stage Heat Rela...

Отзывы: