Lamp Replacement (Annually)

The lamp should be replaced annually even if
it appears to be operating normally. UV-C
energy production diminishes over time.

1. Obtain the correct replacement lamp for

your model.

2. Disconnect power to the equipment. 

3. Open the cover of the device. Allow lamp

to cool 10 minutes before touching.

4. Detach the electrical connector from the

lamp bracket and disconnect the lamp.

5. Carefully remove the UV-C lamp and

replace it with the new lamp. Refer to page
6 for instructions. Be sure to clean the
lamp of dust and fingerprints prior to instal-
lation. 

6. Close the cover of the device.

7. Reconnect power.

8. Verify operation.

Do I still need an air filter?

Yes. The Comfort Plus™ UV-C lamp is designed to be
used in addition to a dust filter or electronic air cleaner
and the filtration of dust particles will also aid in keeping
the bulb(s) of the Comfort Plus™ UV-C lamp unit clean.
However, filters are inefficient at dealing with micro-
scopic bacteria, molds, and viruses and are incapable
of preventing mold from growing on a surface. The
Comfort Plus™ UV-C lamp contributes significantly to
the reduction of the small microbial organisms that pass
through filters and into the general air system.

Proper Clean-Up Technique In Case Of Lamp
Breakage

Wear protective gloves, eyewear and mask.

Sweep the broken glass and debris into a plastic
bag, seal the bag, and dispose of properly.
Contact your local waste management office for
proper disposal.

Do not use a vacuum cleaner. Do not
incinerate.

Lamp Disposal

Dispose of your spent UV-C lamps at your
local recycling center. You may also send your
spent lamps in the same container you
received your replacement lamps to:

White-Rodgers UV Lamp Reclamation
1112 Industrial Park Drive
Royse City, TX 75189

MAINTENANCE AND TROUBLESHOOTING

• Check that the lamp connector is securely

attached to lamp.

• Check that the fuse is in good working

order. Replace if necessary.

• Check that proper power is being supplied

to the device and that switch lights when
turned on.

• Lamps should be cleaned every six (6)

months to remove any dust accumulation on
the bulbs that might lessen the effectiveness
of the UV-C light. The Comfort Plus™ UV-C
light bulbs have a service life of 9,000 hours,
or approximately 375 days.

Fuse Replacement

1. Disconnect power cord.

2. Unscrew the knob marked "Fuse" and

remove fuse. 

3. Install new fuse and screw knob back in

place. Use a 3A/250V fast-acting glass fuse.

4. Reconnect power cord.

Mercury Hazard. Do Not Break.

Each UV-C lamp contains a small amount of Mercury.
May cause redness or irritation. Use proper disposal
techniques in case of breakage. 

WARNING

Replacement Parts

Part No.

UV-C Lamp 

UVP-06207

Electronic Ballast (UV100) 

UVP-06212

Electronic Ballast (UV200)

UVP-06213

Power Cord (120V)

UVP-212261-00

Power Cord (240V)

UVP-212107-00

Power Cord Receptacle

UVP-212106-00

Cover Interlock Switch

UVP-212108-00

Lighted On/Off Switch

UVP-750-0026-001

Fuseholder

UVP-212225-00

Fuse

UVP-750-0108-001

Burn Hazard.

During replacement, allow lamps to cool 10 minutes
before removing them. Personal injury may result.

WARNING

Содержание Comfort plus UV100

Страница 1: ...rocess either destroys the micro organism or neutralizes its ability to reproduce Features Reduces or prevents mold growth on HVAC coils allowing them to operate at peak effi ciency Also greatly reduc...

Страница 2: ...52 Specifications subject to change without notice Sizing The UV100 is suitable for slab coil applications 3 tons or less and 1200 CFM or less Or where space permits only a single lamp The UV200 is su...

Страница 3: ...d mount for possible future use Brackets are secured with knurled nuts Note The angle bracket is useful in applications where the duct is narrower than 16 Fig 1 Device may be mounted before or after A...

Страница 4: ...e careful of sharp edges on device and HVAC equipment while installing the device Personal injury may result CAUTION Drill the lamp and viewport hole for UV100 Drill the lamp and viewport holes for UV...

Страница 5: ...hole required on dual lamp model only 3 16 1 4 holes for mounting screws Fiberboard Mounting Strap Template Use this template to construct strap from minimum 26 gauge metal Make strap no wider than 1...

Страница 6: ...Check Operation With the cover replaced attach the power cord to the device and connect to 120V or 240V power Optional 240V power cord P N 212107 00 is required for 240V operation The device power sw...

Страница 7: ...aste management office for proper disposal Do not use a vacuum cleaner Do not incinerate Lamp Disposal Dispose of your spent UV C lamps at your local recycling center You may also send your spent lamp...

Страница 8: ...The Emerson logo is a trademark and service mark of Emerson Electric Co 212744 00 Rev 1A 4 03...

Отзывы: