background image

7

SYSTEM LOCKOUT AND

DIAGNOSTIC FEATURES

SYSTEM LOCKOUT FEATURES

When system lockout occurs, the gas valve is de-ener-
gized, the circulator blower is energized at heat speed,
and, if flame is sensed, the inducer blower is energized.
The diagnostic indicator light will flash or glow continu-
ously to indicate system status. (System lockout will
never override the precautionary features.)

To reset the control after system lockout, do one of the
following:

1.

Interrupt the call for heat or cool at the thermostat for
at least one second but less than 20 seconds (if flame
is sensed with the gas valve de-energized, interrupt-
ing the call for heat at the thermostat will not reset the
control).

2.

Interrupt the 24 VAC power at the control for at least
one second. You may also need to reset the flame
rollout sensor switch.

3.

After one hour in lockout, the control will automatically
reset itself.

DIAGNOSTIC FEATURES

The 50A55 control continuously monitors its own opera-
tion and the operation of the system. If a failure occurs, the
LED will indicate a failure code as shown below. If the
failure is internal to the control, the light will stay on
continuously. In this case, the entire control should
be replaced, as the control is not field-repairable
.

If the sensed failure is in the system (external to the
control), the LED will flash in the following flash-pause
sequences to indicate failure status (each flash will last
approximately 0.25 seconds, and each pause will last
approximately 2 seconds).

1 flash, then pause

System lockout

2 flashes, then pause

Pressure switch stuck closed

3 flashes, then pause

Pressure switch stuck open

4 flashes, then pause

Open limit switch

5 flashes, then pause

Open rollout switch

6 flashes, then pause

115 Volt AC power reversed/
improper ground

7 flashes, then pause

Low flame sense signal

Continuous flashing

Flame has been sensed when

(no pause)

no flame should be present (no
call for heat)

The LED will also flash once at power-up.

COOL MODE

In a typical system, a call for cool is initiated by closing the
thermostat contacts. This energizes the 50A55 control
and the compressor. The cool delay-to-fan-on period
begins. After the delay period ends, the optional elec-
tronic air cleaner is energized, and the circulator fan is
energized at cool speed. After the thermostat is satisfied,
the compressor is de-energized and the cool mode delay-
to-fan-off period begins. After the delay-to-fan-off period
ends, the circulator fan and electronic air cleaner (op-
tional) are de-energized.

MANUAL FAN ON MODE

If the thermostat fan switch is moved to the ON position,
the circulator fan (cool speed) and optional electronic air
cleaner are energized. When the fan switch is returned to
the AUTO position, the circulator fan and electronic air
cleaner (optional) are de-energized.

TWINNING INTERFACE

If the control has six screw terminals, one of which is
designated TWIN, the control is equipped with a single
wire twinning interface. If twinning is used, either control
will process a call for heat, cool or fan as described above.
However, after the heat-, cool-, or fan-on delay time
expires, both units will energize the circulator blowers at
the same time. Likewise, after the heat-, cool-, or fan-off
delay time expires, both units will de-energize the circula-
tor blowers at the same time. This allows for proper air flow
to be obtained. To assure proper control operation, both
controls must share a common transformer ground (TR).

To enable twinning, do the following.

1.

Power supplied to both furnaces must be from the
same phase of the incoming 120 VAC power.

2.

Connect the TWIN screw terminals on the 50A55-143
of the furnaces to be twinned to each other using a
single wire (14-22 AWG.).

Содержание 50A55-143

Страница 1: ...pted ignition control that employs a microprocessor to continually monitor analyze and control the proper operation of the gas burner inducer and fan Signals interpreted during continual surveillance...

Страница 2: ...ty non condensing MOUNTING Surface mount multipoise Timing Specs 60 Hz maximum Flame Establishing Time 0 8 sec Flame Failure Response Time 2 0 sec At 50 Hz all timing specifications should be increase...

Страница 3: ...holes for mounting control To ensure proper mounting hole locations there is a mount ing hole template on page 8 of this instruction sheet Detach the page with the template from the instruction sheet...

Страница 4: ...H LIMIT N C PRESSURE SWITCH N O FLAME SENSOR PROBE COMPRESSOR CONTACTOR ELECTRONIC AIR CLEANER HUMIDIFIER INDUCER CIRCULATOR BLOWER 50A55 24 VAC 120 VAC 24 VAC CLASS II TRANSFORMER HOT LINE NEUTRAL LI...

Страница 5: ...alent low voltage thermostat Y terminal or equivalent 2nd wire from Y terminal goes to 24 VAC HOT side of compressor contactor coil one wire twinning terminal 24 VAC COMMON side of compressor contacto...

Страница 6: ...s valve is de energized After proof of flame loss the heat delay to fan off period begins and the inducer blower remains energized to purge the system for 5 seconds When the purge is complete the indu...

Страница 7: ...reversed improper ground 7 flashes then pause Low flame sense signal Continuous flashing Flame has been sensed when no pause no flame should be present no call for heat The LED will also flash once at...

Страница 8: ...MOUNTING HOLE TEMPLATE FOR MOUNTING HOLE LOCATIONS 4 172 007 2 plcs 6 402 010 2 plcs Refer to page 3 of the installation instructions for proper installation...

Отзывы: