INSTALLER/CONFIGURATION MENU
CONFIGURATION MENU
Non-
Displayed
Press
or
7
Program-
Press
(Factory
to select from
Day
mable
Button
Default)
listed options
Comments
1
1
(GAS)
ELE
GAS setting: furnace controls blower.
ELE setting: thermostat controls blower.
2
2
Days (7)
5, 0
Selects programming option.
3
* NA
PS (4)
2
Selects programming periods per day.
4
3
Cool, Off,
Cool, Off, Heat,
Selects system switch configuration for heat and cool with
Heat, Auto
Off, Heat, Cool, Off
Auto changeover, Heat & Cool, Heat Only or Cool Only.
5
* NA
E (On)
OFF
Selects Energy Management Recovery on or off.
6
4
Cr Heat (FA)
SL
Selects Heat cycle rate Fast (FA) or Slow (SL).
7
5
Cr Cool (FA)
SL
Selects Cool cycle rate Fast (FA) or Slow (SL).
8
6
CL (OFF)
On
Selects Compressor lockout ON or OFF.
9
7
dL (On)
OFF
Selects display light on or off.
10
8
0
1, 2, 3, 4 HI
Selects temperature display adjustment 1, 2, 3 or 4 degrees
(Room temp)
1, 2, 3, 4 LO
high or low.
11
9
°F
°C
Selects Fahrenheit or Celsius temperature display.
12
10
b (On)
OFF
Selects beeper on or off.
13
11
Heat (99)
62-99
Selects highest Heat setpoint temperature.
Can select 62° to 99°F.
14
12
Cool (45)
45-82
Selects lowest Cool setpoint temperature.
Can select 45° to 82°F.
15
13
Keypad
L, P
Selects keypad lockout full or partial to be set.
lockout (L)
Temperature Limit
Activates temperature limit ranges.
16
14
Keypad
On
Selects keypad lockout on or off.
lockout (OFF)
000
000 to 999
Selects keypad lockout combination number if lockout is on.
000 is not a valid selection.
17
15
000 Change
On
Select change filter alert time period.
Filter (OFF)
200 hours
25 to 1975 hours
When set ON, selects time in 25 hour increments.
18
16
Change
On
Selects change humidifier pad alert time period
Humidifier
(OFF)
100 hours
25 to 1975 hours
When set ON, selects time in 25 hour increments.
To enter the menu: Press the
Menu
button. Press and hold for 5 seconds the
Installer Config
button this displays menu item
#1 in the table below. Press
to advance to the next menu item or
to return to a previous menu item. Press
or
to
change a menu item.
1) GAS or Electric (ELE) fan operation. If the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if the heating system energizes the fan on a
call for heat. Note: Resetting the thermostat switches the
option to ELE.
2) This control can be configured for 7 independent day or
5/1/1 programming or non-programmable mode. The
display indicates "
7 Days
" as default. The programs per
week can be toggled to "
5 Days
" or "
0 Days
" by pressing
the
or
keys. A selection of 0 Days for non-program-
mable will eliminate the need for EMR, and that step
in the menu will be skipped.
3)
Programmable Periods
– This control can be configured
for 4 or 2 programmable periods per day. The display
indicates "
4 PS
" in the display as default. The program-
mable periods can be toggled by pressing the
or
keys.
4)
System Switch Configuration
– This thermostat is
configured for Heat and Cool with Auto changeover
(SYSTEM switch with Cool Off Heat Auto) default. It can
also be configured for Heat and Cool (Cool Off Heat),
Heat only (Off Heat), and Cool only (Cool Off).
5)
Energy Management Recovery
– (this step is skipped if
configured to be non-programmable).
Energy Management Recovery (E) On causes the
thermostat to start heating or cooling early to make the
building temperature reach the program setpoint at the
time you specify. Heating will start 5 minutes early for
every 1° of temperature required to reach setpoint.
Example
: E On is selected and your heating is pro-
grammed to 65° at night and 70° at 7 AM. If the building
temperature is 65°, the difference between 65° and 70° is
5°. Allowing 5 minutes per degree, the thermostat set-
point will change to 70° at 6:35 AM. Cooling allows
more time per degree, because it takes longer to reach
temperature.