background image

2

Mounting

Hole

Mounting

Hole

Place Level

across Mounting Tabs

(for appearance only)

Place Level

across Mounting Tabs

(for appearance only)

RC

C

G

W

RH

CLASS II

TRANSFORMER

COOLING

HOT

24VAC

NEUTRAL

LINE IN

Y

L

O

B

Optional (Heat Pump)

Malfunction Indicator

Low

Voltage
System

Power

Optional

Common

Connection

Fan

Relay

Heat

Relay

LINE IN

HOT

24VAC

NEUTRAL

CLASS II

TRANSFORMER

HEATING

Changeover

Valve Cooling

Changeover

Valve Heating

Compressor

Contactor

System

Malfunction

Switch

Remove

Jumper

2 "AA" Batteries

WIRING CONNECTIONS

Refer to equipment manufacturers' instructions for specific
system wiring information. After wiring, see CONFIGURA-
TION section for proper thermostat configuration.

Wiring diagrams shown are for typical systems and describe
the thermostat terminal functions.

WARNING

!

Thermostat installation and all components of the
control system shall conform to Class II circuits per
the NEC code.

INSTALLATION

Battery Location

2 "AA" alkaline batteries are included in the thermostat at
the factory with a battery tag to prevent power drainage.
Remove the battery tag to engage the batteries.
To replace batteries, set system to 

OFF

, remove thermostat

from wall and install the batteries in the rear along the top of
the thermostat (see Figure 1).

Figure 1 – Thermostat base and rear view of thermostat

Remove Old Thermostat

A standard heat/cool thermostat consists of  three basic parts:
1. The cover, which may be either a snap-on or hinge type.
2. The base, which is removed by loosening all captive screws.
3. The switching subbase, which is removed by unscrewing

the mounting screws that hold it on the wall or adapter
plate. 

Before removing wires from old thermostat,

label each wire with the terminal designation from
which it was attached

. Disconnect the wires from the old

thermostat one at a time. 

Do not let wires fall back into

the wall

.

Installing New Thermostat

1. Pull the thermostat body off  the thermostat base. Forcing

or prying on the thermostat will cause damage to the unit.

2. Place base over hole in wall and mark mounting hole

locations on wall using base as a template.

3. Move base out of  the way. Drill mounting holes. If  you

are using existing mounting holes and the holes drilled
are too large and do not allow you to tighten base snug-
ly, use plastic screw anchors to secure the base.

4. Fasten base snugly to wall using mounting holes shown

in Figure 1 and two mounting screws. Leveling is for
appearance only  and will not affect thermostat operation.

5. Connect wires to terminal block on base using

appropriate wiring schematic (see Figures 2 & 3).

Figure 2 –

Two Transformer System

Figure 3 – Single Transformer System

Terminal Designation

Description

W  . . . . . . . . . Heat Relay

G  . . . . . . . . . Fan Relay

RH  . . . . . . . . . Power for Heating
RC  . . . . . . . . . Power for Cooling

C  . . . . . . . . . Common wire from secondary side of  cooling

system transformer or heat only system transformer

2

Terminal Designation

Description

L  . . . . . . . . . . Heat pump malfunction indicator for

systems with malfunction connection

O  . . . . . . . . . Changeover valve for heat pump energized

constantly in cooling

B  . . . . . . . . . Changeover valve for heat pump energized

constantly in heating

Y  . . . . . . . . . Compressor Relay

Optional 24VAC

Common

Connection

RC

C

G

W

RH

CLASS II

TRANSFORMER

24 Volt

Hot

24 Volt

Common

LINE IN

Y

L

O

B

Optional (Heat Pump)

Malfunction Indicator

Fan

Relay

Heat

Relay

System

Malfunction

Switch

Single transformer heat and cool
systems require a jumper from
RC to RH for heat only systems.
Attach power to RH. For cool only
attach power to RC.

*

Low

Voltage
System

Power

Changeover

Energized in Cooling

Changeover

Energized in Heating

Compressor

Relay

*

6. Push excess wire into wall and plug hole with a fire re-

sistant material (such as fiberglass insulation) to prevent
drafts from affecting thermostat operation.

7. Carefully line the thermostat up with the base and snap

into place.

TERMINAL DESIGNATION DESCRIPTIONS

NOTE

: If continuous backlight or hardwired power

input are desired but do not function in both HEAT
and COOL modes, cut the heating transformer 24V
wires and tape off. Connect the neutral circuit
disconnected from the heating transformer to the
neutral circuit of the cooling transformer. Disconnect
the wire to the RH terminal and install a jumper
between 

RH 

and 

RC

. Depending on the system

requirements, replace the cooling transformer with a
75VA class II transformer if needed.

NOTE

: Heat Pump without Aux: If using 

for MALF indicator, 

C

must be connected. Terminals 

and 

must be jumpered and CR

HEAT must be selected to SL in Configuration Menu item 6.

Содержание 1F97-1271

Страница 1: ...cal Rating Single Stage Battery Power mV to 30 VAC NEC Class II 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 99...

Страница 2: ...holes If you are using existing mounting holes and the holes drilled are too large and do not allow you to tighten base snug ly use plastic screw anchors to secure the base 4 Fasten base snugly to wal...

Страница 3: ...grammed filter time period as a reminder to change or clean your humidifier pad 2 Indicates period of day being programmed 3 RUN SCHEDULE run program button 4 SET TIME button or HOLD temperature butto...

Страница 4: ...d hold for 5 seconds the Installer Config button this displays menu item 1 in the table below Press to advance to the next menu item or to return to a previous menu item Press or to change a menu item...

Страница 5: ...range selected 14 Cool Temperature Limit Range This feature adjusts the lowest setpoint temperature for cool The default setting is 45 F It can be changed between 46 F and 82 F by pressing the or key...

Страница 6: ...change to the other mode Set Current Time and Day 1 Press Menu and then Set Time button once The display will show the hour only 2 Press and hold either the or key until you reach the correct hour an...

Страница 7: ...ogramming see configura tion section Factory settings are listed on Monday Saturday and Sunday If you are re programming a 5 1 1 day schedule pencil in your own times and temperatures directly below t...

Страница 8: ...tly contact the furnace manufacturer or local HVAC service person for assistance Diagnostic Set SYSTEM Switch to HEAT and raise the setpoint above room temperature Within a few seconds the thermostat...

Отзывы: