White Rodgers 1F95W-71 Скачать руководство пользователя страница 6

6

SYSTEM CONFIGURATION

ANY TIME OPTION SWITCHES #1 OR #2 ARE
CHANGED, THE 9 VOLT ENERGIZER

®

 BATTERY MUST

BE REMOVED FOR A MINIMUM OF 2 MINUTES.

Set Option Switches

1.

For furnaces not requiring a G terminal to energize
fan (systems with fan/limit switch or automatic fan on/
off operation):

2.

For systems with electric furnace, and where blower
is energized through fan relay (no sequence to ener-
gize blower):

3.

For systems with an economizer for first stage cooling:

ENGAGE TWO UPPER GUIDES;

PIVOT DOWN

Figure 7. Attaching thermostat to subbase

Attach Thermostat To Subbase

WE RECOMMEND THAT YOU SET OPTION SWITCHES
TO DESIRED POSITION BEFORE ATTACHING ON
SUBBASE 
(see OPERATION). WE ALSO RECOM-
MEND THAT YOU PROGRAM THE THERMOSTAT
WITH BATTERY INSTALLED BEFORE ATTACHING
ON SUBBASE 
(see OPERATION GUIDE for program-
ming instructions).

USE 

SYSTEM

HEAT - OFF - COOL - AUTO

 TO TURN THERMOSTAT OFF BEFORE

ATTACHING THERMOSTAT TO WALL. FAILURE TO
TURN THERMOSTAT OFF MAY CAUSE EQUIPMENT
DAMAGE DUE TO RAPID COMPRESSOR CYCLING.

To attach thermostat to subbase, line up the plastic snap
guides at the top of the thermostat and the 4 connector
pins on the thermostat with the connectors near the top
right section of the subbase (when viewed from the front).

Gently pivot the thermostat down until the 8-pin connec-
tors and the plastic snaps lock into place (see fig. 7). Be
gentle when attaching thermostat
. If the thermostat
does not seem to be attaching to the subbase easily,
make sure that the connector pins and plastic snaps are
properly aligned, and that excess wire is pushed into the
wall. Damage to the thermostat may occur if force is
used.

OPERATION

NOTE

Figure 8. Back of thermostat

Option switches

9-pin connector

4-pin connector

Battery

Set option switches #1 and #2, install the battery, and
program the thermostat before changing option switch #3
or #4.

4.

To enable total keypad lockout (ALL buttons will be
disabled and will not operate until configuration is
changed):

Switch #3 in ON position disables all buttons.

ON

1

2

3

4

Switch #1 ON
Switch #2 (see step 3)
Switch #3 (see step 4)
Switch #4 (see step 5)

ON

1

2

3

4

Switch #1 OFF
Switch #2 (see step 3)
Switch #3 (see step 4)
Switch #4 (see step 5)

ON

1

2

3

4

Switch #1 (see steps 1 & 2)
Switch #2 ON
Switch #3 (see step 4)
Switch #4 (see step 5)

NOTE

ON

1

2

3

4

Switch #1 (see steps 1-2)
Switch #2 (see step3)
Switch #3
Switch #4 (see step 5)

ON

Содержание 1F95W-71

Страница 1: ...acement Installation Remove Old Thermostat Attach Subbase to Wall Attach Thermostat to Subbase Operation 6 System Configuration Set Option Switches Check Thermostat Operation Fan Operation Heating Sys...

Страница 2: ...building temperature Observe the following general rules when selecting a location 1 Locate thermostat about 5 ft above the floor 2 Install thermostat on a partitioning wall not on an outside wall 3 N...

Страница 3: ...THE WALL 7 Install new thermostat using the following proce dures Attach Subbase To Wall 1 Remove the packing material from the thermostat Place the fingers of one hand on the center top and bottom po...

Страница 4: ...RSONALINJURY AND OR EQUIPMENT DAMAGE COULD RESULT NOTE TABLE 2 WIRE IDENTIFICATION LABELS 1 G G 1 9 Y1 Y1 9 2 C C 2 3 L L 3 4 R R 4 5 O O 5 6 B B 6 7 E1 E1 7 8 E2 E2 8 10 Y2 Y2 10 11 W1 W1 11 12 W2 W2...

Страница 5: ...HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made Damage to equipment will occur when power is restored IF SAFETY CIRCUITS ARE IN ONLY ONE...

Страница 6: ...the top of the thermostat and the 4 connector pins on the thermostat with the connectors near the top right section of the subbase when viewed from the front Gently pivot the thermostat down until the...

Страница 7: ...interruption or failure if the battery is not installed When power is restored the thermostat will automatically maintain a temperature of 64 F or a cooling temperatureof82 F factorypreprogrammed asne...

Страница 8: ...If you need further information about this product please write to White Rodgers Division Emerson Electric Co 9797 Reavis Road St Louis MO 63123 5398 Attention Technical Service Department...

Отзывы: