CHECK THERMOSTAT OPERATION

FAN OPERATION

1.

Turn on power to the system. If the heat source has
a standing pilot, be sure to light it.

2.

Press  

FAN

ON - AUTO

until FAN 

 is displayed. The blower

should begin to operate.

3.

Press 

FAN

ON - AUTO

 until FAN 

 is displayed. The blower

should stop operating within approximately one
minute.

HEATING SYSTEM

When checking thermostat, option switch #4 (for auto-
matic changeover) must be in the OFF position, to allow
temporary setting of heat setpoints above cool settings.
After system checkout, reset option switch #4 to the ON
position  if automatic changeover is desired (see SYS-
TEM CONFIGURATION
).

1.

Press 

SYSTEM

HEAT - OFF - COOL - AUTO

 until HEAT is displayed (it may already

be displayed).

2.

Press 

 to adjust thermostat to 99

°

F. All stages of

the heating system should begin to operate within five
minutes (if the compressor is not operating, it may be
locked out. See LOCKOUT BYPASS OPTION).

COOLING SYSTEM

To prevent compressor and/or property damage,
if power to the compressor has been off or
interrupted for more than 1 hour and the outdoor
temperature is below 50

°

F, DO NOT operate the

system for at least the amount of time the com-
pressor was off! This will allow the compressor
heaters to warm the compressor oils to avoid
damage due to slugging.

1.

Press 

SYSTEM

HEAT - OFF - COOL - AUTO

 until COOL is displayed.

2.

Press 

 to adjust the thermostat to 40

°

F. All

stages of the cooling system should come on within
five minutes (if the compressor is not operating, it may
be locked out. See LOCKOUT BYPASS OPTION).

After heating and cooling system have been checked and
are running properly, determine if automatic changeover
is desired (see SYSTEM CONFIGURATION).

Refer to the OPERATION GUIDE if you need additional
information on thermostat operation.

TROUBLESHOOTING

Refer to the Question & Answer section of the OPERA-
TION GUIDE
 for information on troubleshooting the ther-
mostat.

NOTE

CAUTION

!

LOCKOUT BYPASS OPTION

FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS FEA-
TURE DUE TO POSSIBILITY OF EQUIPMENT OR
PROPERTY DAMAGE, OR PERSONAL INJURY.

DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESS THE COMPRESSOR OIL HEATERS HAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.

COMPRESSOR SHORT TERM CYCLE

PROTECTION

This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature

while testing thermostat operation, simply press 

ADV

PRGM

and 

HOLD
TEMP

 buttons at the same time at initial startup.

CAUTION

!

Содержание 1F91W-71

Страница 1: ...of 64 F or a cooling temperature of 82 F INSTALLATION INSTRUCTIONS WHITE RODGERS Ifindoubtaboutwhetheryourwiringismillivolt line orlow voltage have it inspected by a qualified heating and air conditi...

Страница 2: ...any temperature radiating equip ment 4 Avoid locations close to windows adjoining outside walls or doors that lead outside 5 Avoid locations close to air registers or in the direct path of air from th...

Страница 3: ...packing material from the thermostat Place the fingers of one hand on the center top and bottom portion of the thermostat Grasp the subbase in the other hand on the top and bottom center and gently p...

Страница 4: ...stic expansion plugs to secure subbase 6 Push excess wire into wall and plug hole with a fire resistant material such as fiberglass insulation to prevent drafts from affecting thermostat operation DO...

Страница 5: ...st be observed If the HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made Damage to equipment will occur when power is restored Relay contac...

Страница 6: ...used SYSTEM CONFIGURATION ANY TIME AN OPTION SWITCH IS CHANGED THE 9 VOLT ENERGIZER BATTERY MUST BE REMOVED FOR A MINIMUM OF 2 MINUTES SET OPTION SWITCHES 1 Multi stage Systems up to 3 heat stages and...

Страница 7: ...sor heaters to warm the compressor oils to avoid damage due to slugging 1 Press SYSTEM HEAT OFF COOL AUTO until COOL is displayed 2 Press to adjust the thermostat to 40 F All stages of the cooling sys...

Страница 8: ...If you need further information about this product please write to White Rodgers Division Emerson Electric Co 9797 Reavis Road St Louis MO 63123 5398 Attention Technical Service Department...

Отзывы: