CHECK THERMOSTAT OPERATION

If at any time during testing, your system does not operate
properly, contact a qualified serviceperson.

Fan Operation

1. Turn on power to the system.

2. Press SYSTEM button until the system is OFF.

3. Move FAN switch to ON. The blower should begin to operate.

4. Move FAN switch to AUTO position. The blower should stop

within a short period of time.

Heating System

1. Press SYSTEM button to turn thermostat to HEAT.

2. Press 

 to adjust thermostat setting to 90

°

 and hold for five

seconds. After you release the button, both stages of the
heating system should begin to operate within five seconds.

3. Press 

 to adjust temperature setting below room tempera-

ture. The auxiliary heating system will stop immediately and
the first stage will stop within three to four minutes.

Cooling System

To prevent compressor and/or property damage, if the
outdoor temperature is below 50

°

F, DO NOT operate

the cooling system.

1. Press SYSTEM button to turn thermostat to COOL.

2. Press 

 to adjust thermostat setting to 45

°

 and hold for five

seconds. After you release the button, the blower should
come on immediately on high speed, followed by cold air
circulation. Both stages of the cooling system should begin
to operate (if you have a two-stage cooling system).

NOTE

CAUTION

!

LOCKOUT BYPASS OPTION

FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS FEA-
TURE DUE TO POSSIBILITY OF EQUIPMENT OR
PROPERTY DAMAGE, OR PERSONAL INJURY.

COMPRESSOR SHORT TERM

CYCLE PROTECTION

This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature

while testing thermostat operation, simply press 

and 

 buttons at the same time.

DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESS THE COMPRESSOR OIL HEATERS HAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.

If the fan is running but the compressor is not running and the
word  COOL  is flashing, the compressor lockout feature is
operating (see Lockout Bypass Option to temporarily
override the compressor lockout feature during testing).

3. Press 

 to adjust temperature setting above room tempera-

ture. The cooling system should stop operating.

During normal operation, the second stage of heat or cool may
take 15 to 30 minutes to turn on. The delay varies depending on
the performance of the first stage. Typically the second stage will
come on sooner in more severe weather, while in milder weather
it will take longer. There is no adjustment to this feature, as it is
designed to maximize both comfort and efficiency.

NOTE

Содержание 1F81-71

Страница 1: ...Optional B and O terminals Preprogrammed temperature control LCD continuously displays set point and alternately dis plays time and room temperature Temperature override until next program period Man...

Страница 2: ...stheEnergyManagementRecov ery EMR feature EMR allows the thermostat to energize the heating system up to 30 minutes before the time pro grammed into the thermostat The thermostat will then energize th...

Страница 3: ...fety circuits Fan Relay G TRANSFORMER Compressor Contactor Stage 2 24 VAC 120 VAC Hot Neutral TRANSFORMER TWO COMMONS MUST BE JUMPERED TOGETHER CUT AND TAPE OFF The 24 Volt neutral connection to termi...

Страница 4: ...if you have a two stage cooling system NOTE CAUTION LOCKOUT BYPASS OPTION FOR QUALIFIED SERVICE TECHNICIANS USE ONLY OPERATORSSHOULDNOTUSETHISFEA TURE DUE TO POSSIBILITY OF EQUIPMENT OR PROPERTY DAMA...

Страница 5: ...STORAGE When programming you can enter both your heating and cooling programs at the same time There is no need to reprogram the thermostat at the beginning of each season Figure 6 Thermostat display...

Страница 6: ...also want to look at the sample program table to get an idea of how the thermostat can be programmed Entering Your Program Follow these steps to enter the heating and cooling programs you have select...

Страница 7: ...YOUR PROGRAMMING Follow these steps to check your thermostat programming one final time before beginning thermostat operation 1 Press SYSTEM button until HEAT is displayed 2 Press VIEW PRGM to view t...

Страница 8: ......

Отзывы: