background image

PART NO. 37-1104H

Replaces 37-1104G

1018

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING  OR  OPERATING THIS  CONTROL  COULD  CAUSE  PERSONAL 
INJURY AND/OR PROPERTY DAMAGE.

 

 DESCRIPTION

241-2, 1605-64 & 1609 Series

Refrigeration Temperature Controls

INSTALLATION INSTRUCTIONS

This hydraulic action temperature control is applicable for all 
types of commercial or industrial refrigeration applications. This 
control will close contacts on rise in temperature and open them 
on a fall in temperature.
This control has a two-circuit contact structure which will simul-
taneously close two circuits on a rise of temperature and open 
them on  a fall of temperature.

 

 INSTALLATION

The switch mechanism of this control may be mounted in any 
location,  provided  that  the  temperature  and  humidity  of  the 
air in which it is located do not cause a condensation on the 
switch parts.
The sensitive element, or “bulb”, should be located in the 

aver-

age temperature

 of the controlled area.

Capillary tubing should be led over a path that protects it from 
damage from blows, cuts, etc., and should be installed without 
kinking or twisting. The tubing should be attached to some surface 
at frequent intervals along its length, and should not hang loosely. 

Excess tubing should be coiled and secured at a convenient 
protected location close to the switch mechanism.
The bulb should be handled with reasonable care, as a dent or 
sharp bend may change the calibration and cause the control 
to cycle at a temperature different from the dial setting.
Refrigeration  and  temperature  controls  are  calibrated  and 
tested  under  controlled  manufacturing  conditions.  Published 
specifications do not include normal manufacturing specifica-
tions. Minor differences in performance could be expected as 
conditions change.

 

 PRECAUTIONS

Operator: Save these instructions for future use!

This two-circuit control is intended for use on zoning systems 
where all controls operate a common compressor but operate 
a separate solenoid refrigerant valve in each zone.

WARNING

!

CAUTION

THIS  CONTROL  MUST  BE  INSTALLED  BY  A  QUALIFIED 
INSTALLER.
All wiring must conform to local and national electrical codes 
and ordinances.
This control is a precision instrument, and should be handled 
carefully. Rough handling or distorting components could cause 
the control to malfunction.
This control has been accurately calibrated at the factory. Any 
attempt to re-calibrate this control will void the White-Rodgers 
warranty.
If in doubt about whether your wiring is millivolt, low or line volt-
age, have it inspected by a qualified heating and air conditioning 
contractor or a licensed electrician.
Label all wires prior to disconnection when servicing controls. 
Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manufac-
turers’ recommended installation/service instructions to insure 
proper operation.

www.white-rodgers.com

www.emersonclimate.com

FIRE/SHOCK HAZARD

Disconnect power to system at main fuse 
or circuit breaker box before installation.
Do  not  use  on  circuits  exceeding 
specified voltages.

FREEZE HAZARD

Install low temperature limit device.
System malfunction may cause freeze 
damage.

Содержание 1609 Series

Страница 1: ...nt from the dial setting Refrigeration and temperature controls are calibrated and tested under controlled manufacturing conditions Published specifications do not include normal manufacturing specifi...

Страница 2: ...igh side pressure control Motor starter Solenoid refrigerant valve To Compressor Motor Line L1 L2 Note Make L1 HOT on 120V installation Circuit showing temperature control to open and close refrigeran...

Страница 3: ...publi es n incluent pas les sp cifications de fabrication standard De l gers carts de performance peuvent survenir selon les changements de conditions PR CAUTIONS Op rateur Il faut conserver ces instr...

Страница 4: ...seur mais chaque zone doit avoir une lectrovanne de frigorig ne et une commande de temp rature qui lui sont propres B Fixed indicator cut out point C Differential adjusting screw D Movable indicator c...

Страница 5: ...sdemanufactura Lasespecificacionespublicadasnoincluyenlasespecificaciones normalesdemanufactura Sepuedenesperardiferenciasmeno res en el rendimiento con el cambio de condiciones PRECAUCIONES Operador...

Страница 6: ...asta que el indicador movible D se ale a la temperatura a la cual el compresor tiene que arrancar B Fixed indicator cut out point C Differential adjusting screw D Movable indicator cut in point A Adju...

Страница 7: ...NOTES...

Страница 8: ...hite Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co www white rodgers com www emersonclimate com Homeowner Help Line 1 800 284 292...

Отзывы: