M-SQ PRO 15/18 kVA
Marine Diesel Generator
39
5.2 Engine faults
CAUTION!
Remove 3 Amp. fuse in the control panel while working
on the generator to prevent the engine from starting.
5.2.1 General
Most electrical problems relating to Voltage or Frequency are
due to wrong engine speed.
Note that RPM and Hz are basically the same.
Use the problem solving table to find the cause of a wrong
engine speed. When there is no obvious cause one can adjust the
RPM (see special procedures).
When the engine is not cranking well, starting problems almost
always originate from battery problems or poor battery cable
connections.
When the engine is cranking, well starting problems almost
always originate from lack of fuel or air bubbles in the fuel pipes.
CAUTION!
When the engine does not start instantly, prolonged
cranking can fill up the exhaust system with cooling
water because of the water injected exhaust. When
the water enters the cylinder through the valves this will bring
severe damage to the engine. When the engine does not start
and repeated cranking is necessary shut off the seawater inlet.
Open the valve immediately after the engine has started.
A failure code is displayed when a hardware failure at the
generator is detected.
Failure code
Problem
COMMUNICATION
Communication error between the panel and the generator
LOW START BAT
Starter battery voltage too low
ALTERNATOR
No output battery charging voltage
EXHAUST TEMP
Exhaust temperature is too high
WATER TEMP
Coolant temperature is too high
OIL PRESSURE
Oil pressure failure
LOW VOLTAGE
Generator AC output voltage is too low
HIGH CURRENT
generator is in overload
FREQUENCY
output frequency of the generator is too low
ECU FAILURE
When red light, fig. 25 is blinking
→
see table page 37(SQ-Pro 18 only)
Fig 25 ECU red light