WHISPERKOOL SERIES ADVANCED CONTROLLER (CONT.)

Cellar Pre-Chill 

(cont.)

2. The CPC feature can be adjusted to the customer’s specific needs by accessing the 

control panel menu.

Note

: This feature is not available on the remote keypad application.

Set

1. Press the “Set” button once and it will display the set point. After about 5 seconds, the 

display will return to normal operation and display the bottle probe temperature. 

2. Press and hold the “Set” button for 3 to 5 seconds until the set point is displayed and the 

°F symbol starts blinking. Then, press the “Up” or “Down” arrow to change the set point. 

Next, press the “Set” button once and the set point numbers and the temperature on the 

display will blink to confirm the new set point. 

3. Press the “Up” button to display the high temperature data history, or press the “Down” 

button to see the low temperature history. Once the high/low data history is displayed, it 

can be reset by holding the set button (“RST” will blink on the display). It will then erase 

the past recorded data file and start recording from the current time and temperature.

4. Press the “Set” and the “Down” buttons simultaneously for 3 to 5 seconds and you will  

access the customer preference selection menu. The menu allows the customer to tweak 

the control system to their applicable choice.

Customer 

Preference  

Selection 

Menu (CPSM)

To access the CPSM, press the “Set” and “Down” buttons simultaneously for 5-7 seconds. 

This will display “CF”, now press the “Set” and “Down” buttons simultaneously for another 

5-7 seconds. The display will briefly show “Pr2”, signifying you have accessed the CPSM.

The following CPSM options are available for adjustment:

Fon

 — Humidity management: This parameter is normally set at 5, which should provide 

adequate relative humidity for the cellar.

•  An increase in this parameter will increase the humidity (%RH), and a decrease in 

the parameter will decrease humidity. 

•  Adjustments should be made in increments of 5, with a maximum of 15, and a  

minimum of 0. 

•  After any adjustment to Humidity Enhancement, you should wait a minimum of 

three days before making any additional adjustments. This will allow the cellar 

sufficient time to acclimate to the new setting.

Fof

 — Humidity Management Enhancement: This parameter is normally set at 5. This  

parameter usually should not be adjusted, as it provides an off cycle time for the fan 

during the compressor off cycle.

CCS

 — Cellar Pre-Chill Set Point: This parameter is set at 52°F, but can be adjusted to a set 

point between 55°F and 67°F.

bLL/Act

 — Compressor off or on for low (bLL) or high (Act) temperature alarm: These  

parameters are set at “n.” With this parameter set at “n”, the refrigeration system will 

continue to operate normally if there is a high or low temperature alarm. To change this 

parameter, change the setting to “y”, and the compressor/refrigeration system will shut off 

during a high or low temperature alarm.

Содержание 2500 CABINET

Страница 1: ...WK25 031114 USE WITH VINOTHEQUE WINE CABINETS ONLY The Coolest Thing In Wine Storage 2500 CABINET SYSTEM MANUAL ...

Страница 2: ...slated transmitted or reduced to any printed or electronic medium or to any machine readable form for any purpose in whole or in part without the written consent of WhisperKOOL Every effort has been made to ensure that the information in this manual is accurate WhisperKOOL is not responsible for printing or clerical errors WhisperKOOL reserves the right to make corrections or improvements to the i...

Страница 3: ...hermometer System Operation Controller Operation Testing the Refrigeration Unit Cool Down Period Normal Operation and Maintenance Troubleshooting Installation Terms and Conditions Technical Assistance 2 3 4 5 7 10 10 11 12 13 15 WhisperKOOL 1738 E Alpine Ave Stockton CA 95205 1 800 343 9463 www whisperkool com ...

Страница 4: ...WK25 031114 Page 2 1 800 343 9463 WHISPERKOOL 2500 QUICK REFERENCE GUIDE F Rear of Cabinet Bottle Probe Fan ...

Страница 5: ...escape the reservoir Starting the unit before the oil has had a chance to settle again can cause damage to the compressor and negatively affect cooling A dedicated 20 amp circuit is highly recommended for optimum operation Tripped breakers and deficient performance may occur if other devices are pulling power from the same circuit Do not use a Ground Fault Interrupter GFI with this product The coo...

Страница 6: ... space Avoid pulling too much on the probe cord as it may become disconnected which would lead to inaccurate temperature readings The WhisperKOOL system is based on the temperature of the wine It is ideal to place the probed bottle mid way in the racking so that it is not near cold supply air Do not be misled by ambient temperatures that are read from the outside of the cabinet The air temperature...

Страница 7: ...to run for about 1 minute This is a feature of the WhisperKOOL Humidity Management WHM system The WHM is an adjustable feature that allows the customer the convenience of managing the humidity enhancement of their wine cellar It is one of the many customer preference selection features that allow the customer the ability to fine tune the controls Anti Frost Cycle The Anti Frost Cycle is a precauti...

Страница 8: ...ondensing refrigerant creates heat which will need to dissipate away from the unit on the outside Some units have an exhaust fan mounted on top of the cabinet which forces air away from the unit vertically In order to avoid disrupting the ventilation do not place anything on top of the cabinet Do Not Place Anything On Top of the Cabinet WhisperKOOL 2500 Cooling System If your cabinet is not equipp...

Страница 9: ...om the current time and temperature forward Temperatures displayed would reflect bottle probe temperatures from that point in time and beyond 3 The Hi Low feature should be reset at initial start up and after the cellar or cabinet has obtained normal operating temperatures generally 55 F Cellar Pre Chill Activate the Cellar Pre Chill feature by pressing the Up button for 3 to 5 seconds and the CPC...

Страница 10: ...lection Menu CPSM To access the CPSM press the Set and Down buttons simultaneously for 5 7 seconds This will display CF now press the Set and Down buttons simultaneously for another 5 7 seconds The display will briefly show Pr2 signifying you have accessed the CPSM The following CPSM options are available for adjustment Fon Humidity management This parameter is normally set at 5 which should provi...

Страница 11: ...obe temperature During a Probe 1 failure alarm the bottle probe temperature can be monitored by pressing the Up or Down arrows to view the temperature history HES Differential for Energy Reduction This parameter is set at 4 which results in a set point of 58 F during energy reduction A decrease in this setting will decrease the set point and an increase in this feature will increase the set point ...

Страница 12: ...ot working correctly contact Vinothèque s customer service department at 1 800 343 9463 We will work with you to diagnose the problem and promptly resolve it LOADING BOTTLES AND COOL DOWN PERIOD Loading Bottles The cabinet may settle slightly based on the weight of all the bottles It is best to spread the loading of bottles evenly throughout the cabinet starting on the bottom first This will preve...

Страница 13: ...hould be 55 F or desired wine temperature Maintenance WhisperKOOL recommends vacuuming of the condenser fins located in the rear of the cabinet every three months A partially obstructed condenser dramatically reduces the efficiency of the cooling unit Monthly Check filters Check for unusual noise or vibration Quarterly Clean filters o Remove the filter covering the coil o Wash with warm water o Dr...

Страница 14: ... temperature Inadequate ventilation Assure proper space above behind and on the side of the unit Do not set anything on top Door gasket not sealing properly See cabinet owner s manual Not cooling Thermostat setting May be set too warm lower the set temperature Thermostat not operating correctly Test unit with bypass plug Contact Customer Service Low on refrigerant or Freon Unit may need service Co...

Страница 15: ...air or replace at WhisperKOOL s sole option the Product at no charge to the End User and 2 PARTS supply at no charge to the End User new or rebuilt replacement parts for the Product in exchange for the return of defective parts and 3 FREIGHT cover normal ground freight charges for parts and in the event the Product is not repairable in the field cover normal ground freight charges within the conti...

Страница 16: ... End User s responsibility to secure safe haven storage for ANY AND ALL items that are being kept and stored in the End User s wine cellar including any Product WhisperKOOL takes no responsibility for the safety and preservation of the aforementioned items in the event that the environment becomes unsuitable to maintain a proper storage environment 6 SALES AND USE TAX WhisperKOOL only collects Cal...

Страница 17: ...om 6 00 a m to 4 00 p m Pacific Standard Time The appointed customer service representative will be able to assist you with your questions and warranty information more effectively if you provide them with the following The model and serial number of your WhisperKOOL unit Location of the system and installation details such as ventilation construction of your wine cellar and room size Contact Whis...

Страница 18: ...WK25 031114 WhisperKOOL 1738 E Alpine Ave Stockton CA 95205 1 800 343 9463 www whisperkool com ...

Отзывы: