INSTALLATION 

 

EN / M-GV4 Piccolo for marine applications / May 2017 

5

 

2.5 

VENTILATION  

 

2.5.1 

General 

The  Genverter  normally  draws  air  from  the  engine 
compartment or machine room.  An engine compartment with 
natural  ventilation  must  have  vent  openings  of  adequate  size 
and  location  to  enable  the  Genverter  to  operate  without 
overheating.  To  allow  an  ample  supply  of  air  within  the 
temperature limits of the generating set an opening of at least 
100 cm2 is required.  
A  "sealed"  engine  compartment  must  have  a  good  extraction 
ventilator to maintain reasonable ambient  temperatures. High 
temperature  of  intake  air  reduces  engine  performance  and 
increases engine coolant temperatures. Air temperatures above 
40°C  reduce  the  engine  power  by  2%  for  each  5°C  of  rise. 
Further  the  electronic    inverter  is  rated  for  40°C.  At  higher 
temperatures  the  electric  output  will  be  lower.  To  minimise 
these effects the engine room temperature must  not be more 
than 15ºC above the outside ambient air temperature.  
Apply  a  combination  of  ventilators,  blowers  and  air  intake 
ducting  to  meet  the  temperature  limit.  The  air  inlet  ducts 
should  run  to  the  bottom  of  the  engine  compartment  to  clear 
fumes  from  the  bilge  and  to  circulate  fresh  air.  Air  outlets 
should be at the top of the engine compartment to remove the 
hottest air.  An  engine compartment  blower should be used as 
an extraction ventilator to remove air from the engine room.  
In  cases  where  it  is  impossible  to  meet  the  above  mentioned 
temperature  limit  by  using  engine  compartment  ventilation, 
connections  are  to  be  made  for  an  air  inlet  directly  to  the 
Genverter enclosure. 
Air inlets should be louvered, where appropriate, to protect the 
engine  room  and  to  protect  the  generating  set  from    water 
spray.  
 

2.6 

CONNECTIONS 

2.6.1 

Overview 

The Genverter GV4 Piccolo comes supplied with all supply and 
output lines (i.e. cooling water connections, exhaust, fuel lines 
etc.) already connected to the engine and inverter. The supply 
lines are fed through the capsule’s front base.  
The connections are marked as shown in Figure 2 (next page).  
All  electrical  connections,  cable  types  and  sizes  must  comply 
with  the  appropriate  national  regulations.  Supplied  cables  are 
rated for ambient temperatures up to 70°C. 
If  the  cables  are  required  to  meet  higher  temperature 
requirements, they must be run through conduits.  
 

ATTENTION! 
Before  working  (installation)  on  the  system  read 
the section safety instructions. 

 

2.7 

FUEL SUPPLY  

2.7.1 

Fuel tank  

Fuel  tanks  should  be  made  of  appropriate  material  such  as 
(stainless) steel or plastic. Steel tanks should not be galvanised 
or painted inside. Condensation can occur in metal tanks when 
temperature  changes.  Therefore,  water  accumulates  at  the 
bottom  of  the  tank  and  provisions  should  be  made  for  the 
drainage of this water.  
The tank will need a filling connection, a return connection and 
an  air  ventilation  connection  which  will  require  protection 
against water entry.  
Some official regulations do not allow connection points at the 
base of the fuel tank; connections are to be made at the top of 
the  tank  with  internal  tubing  down  to  a  few  cm  above  the 
bottom  of  the  tank.  Using  the  existing  fuel  tank  of  the  car-
engine the fitting should be carried out with extra care. Both a 
supply line and a return line should be installed and go into the 
tank from the top. Interference of the two systems (car engine 
and Genverter engine) should be avoided. 
 

2.7.2 

Fuel lift pump  

Apart  from  the  machine  fuel  pump,  the  generating  set  is 
supplied with a separate fuel lift pump; therefore the tank can 
be  installed  at  a  lower  level  than  the  generating  set  (see 
Figure 3). The maximum suction height is 1 m.  
If  the  pump  has  to  lift  the  fuel  higher  than  one  meter  an 
external fuel lift pump must be installed  (Art. No. 50201062).  
When  using  a  second  electric  fuel  supply  pump,  it  is 
recommended  to  mount  a  loose  supplied  pump  close  to  the 
tank and mount it in an angle or vertical to prevent air bubbles 
to  block  the  system.  The  pump  makes  clicking  noises  and 
therefore  could  be  mounted  on  rubber  mountings.  When  the 
clicking  noises  of  the  pump  are  not  acceptable  another 
noiseless pump is available as an option (Art. No. 50202200). 
 
 

Содержание GV4 Piccolo

Страница 1: ...ALLATION MANUAL High efficiency 4kW Genverter for marine use V1 1 May 2017 WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel 31 512 571550 Fax 31 512 571599 www whisperpower com Art no 40200831 ...

Страница 2: ... 8 2 Inter cooling 8 2 8 3 Raw water supply 8 2 8 4 Installation of through hull fitting 9 2 8 5 Water strainer 9 2 8 6 Siphon breaker air vent 9 2 9 Exhaust system 9 2 9 1 Standard wet exhaust system installation 10 2 9 2 Super silent exhaust system 10 2 10 Dry exhaust system 12 2 10 1 General remarks 12 3 ELECTRICAL INSTALLATION 12 VOLT 14 3 1 Engine control system 14 3 2 Starter battery 14 3 3 ...

Страница 3: ...ed by WhisperPower This manual is valid for the following models Part number Description 49002005 M GV4 Piccolo MARINE Refer to the user s manual for identification of the Genverter set For other models see our website www whisperpower com WARNING During installation and commissioning of the Genverter the Safety Guidelines Measures are applicable at all times See chapter 2 of the user s manual WAR...

Страница 4: ...air inlet of the engine room must be protected against the ingress of water and it is recommended to fit an air inlet strainer for protection against dirt and dust 2 4 INSTRUCTIONS FOR OPTIMAL SOUND AND VIBRATION INSULATION Position the GV4 Piccolo as low as possible in the vessel The Genverter is secured to the base frame inside the canopy by means of a double flexible engine mountings system Thi...

Страница 5: ...e capsule s front base The connections are marked as shown in Figure 2 next page All electrical connections cable types and sizes must comply with the appropriate national regulations Supplied cables are rated for ambient temperatures up to 70 C If the cables are required to meet higher temperature requirements they must be run through conduits ATTENTION Before working installation on the system r...

Страница 6: ...ons of the GV 4 Piccolo Figure 3 Fuel supply fuel tank is below the Genverter Fuel lift pump Fuel out Siphon breaker loop out 5 4 3 2 1 1 2 3 4 5 7 6 8 6 7 8 Engine control and 3 phase power output Battery connections Fuel in Sea water in Siphon breaker loop in Front view Bottom view ...

Страница 7: ...ication of the boat The fuel pipes can be plumbed to the flexible hoses which are on the generating set and have a connection to fit to 8 mm pipe This fuel lines fulfils CE standards and are according to ISO 7840 A2 It is important to avoid bends in the pipes as they could trap air bubbles The return pipe should never be connected to the suction pipe The return line should be of 8 mm diameter and ...

Страница 8: ...s see Figure 6 A properly installed cooling system is critical to keep engine temperatures within an acceptable range Ensure that the installation complies with the following installation instructions 2 8 3 Raw water supply For raw water supply the following installation materials are required a skin fitting a sea cock a water strainer hoses and clamps In order to keep the suction resistance in th...

Страница 9: ...vent Ideally the air vent should be mounted above the yacht keel centre line i e to minimize the influence of swaying on the water intake Fast motorboats will lay deeper when sailing at large speed non planing and have additional pressure on the water inlet This should be avoided to prevent water from entering into the engine If the air vent is clogged the water hoses will not be vented when the G...

Страница 10: ...er line refer to Figure 6 ref 5 The goose neck must be vertical and situated preferable along the ship s keel centre line It is recommended to install an extra muffler see Figure 9 ref 2 close to the through hull fitting Because of the small gas flow of the small engine it is very important to keep strictly to the instructions above some mufflers and water locks cause too high back pressure It is ...

Страница 11: ...o the hull outlet will help further to reduce noise emission If the M GV4 Piccolo and the exhaust system have been installed correctly neighbouring boats will not be disturbed by outlet noise With the super silent exhaust system GV 4 noises are almost inaudible For optimal noise reduction the sea water outlet from the exhaust water separator centre outlet on the unit should be installed below the ...

Страница 12: ...stainless steel flexible bellow hose to allow for expansion and to prevent vibrations to be transferred Rubbers are supplied to mount the mufflers flexible The insulation jacket for the flexible bellow and the resonance muffler are also very effective in damping vibrations Still it could be that additional measures has to be taken like an extra clamp in a vibrating section of pipe insulation blank...

Страница 13: ...ning the location of the Genverter set one has to consider how to get away with the exhaust In wind still conditions a light smell of exhaust fumes around the boat will not be avoidable To bring the exhaust to the deck or to the top of the deck house gives the best results on noise and smell However when the pipes go through the boat they should be insulated and around the hole in the deck or roof...

Страница 14: ...er cables are required a larger cross sectional area should be considered to compensate for voltage reduction Connect the cables as described in section 4 1 When two batteries are used in series to provide a 24 Volt supply system never take off 12 Volt starting power from one of these batteries This will result in severe damage to both batteries within a short time Disconnect the battery leads if ...

Страница 15: ...commended to apply cables with a larger cross section refer to ISO 13297 annex A 3 8 TRANSFER SWITCH A power source selector switch much be installed between the PMG box and the vehicle s electrical supply system This switch must ensure that all AC consumers can be switched off at once This switch should also be installed to keep the generating set and land grid power systems separate Transfer swi...

Страница 16: ...ry switch circuit breaker is closed 7 Open the fuel valve Check if there are no air leaks in the fuel supply line and check if the lift of the fuel is less than 1 meter Check if there is no air in the water fuel separator 8 Check if the air intake in the canopy is not blocked 9 Check the oil level and colour of the oil 10 To bleed the fuel system Push the Start button on the local control not on t...

Страница 17: ...FUEL KIT Figure 22 Fuel supply kit no qty article no description dimensions 41 2 50221203 Straight coupling 8 mm 42 1 40230090 Fuel strainer water separator M14x1 5 mm 43 2 50221618 Parallel male stud coupling M14 8 mm 44 2 50221644 Reducing male nipple M14 M16 60 gr 45 2 50221615 Hose connection 8 mm 46 2 50221616 Nut coupling M16x1 5 mm 47 1 50221252 Nipple hose pipe 8 mm 48 4 50221522 Hose clam...

Страница 18: ... 50220055 Cool water hose transp spiral 13x19mm 6 1 50230062 Nickel plated brass intake strainer 3 4 7 1 50230067 Mounting bracket small water strainer 1158 TOTAL 40230201 WATER INLET KIT 12 5 mm SYPHON BREAKER KIT 12 5 mm pos qty article no description 1 1 50230017 Siphon breaker valve 12 5mm 1 2 complete including valve assembly 2 6 50221521 Hose clamp stainless 12 20 3 3m 50220057 Cooling water...

Страница 19: ...le no description 22 8 50221504 Hose clamp stainless 32 44 mm 23 2 5m 40220033 Marine exhaust hose 40 mm 1 31 1 50221015 Male hose connection 1 x 40mm 32 1 50230044 Lever operated ball valve FF 1 33 1 50230033 Brass through hull fitting 1 x 70 34 1 40230197 Water gas separator Delta 40 40 40mm 1 TOTAL 40230093 Delta water gas separator kit 40mm OPTIONAL INSTALLATION MATERIALS pos qty article no de...

Страница 20: ...ing f f 1 galvanised 69 3 ST 50221661 U clamp 42mm M10 70 3 ST 50221664 Bracket U clamp 25cm M10 48mm passivated 71 6 ST 50211406 Washer SP M10 72 6 ST 50211447 Washer spring SP M10 73 6 ST 50211466 Nut hexagonal SP M10 75 1 ST 50221471 Elbow 90 degr m f galvanised 1 BATTERY INSTALLATION KIT article no description dimensions 61112002 WBC Handy 20 charger 12V 2A 157 x 33 x 34 mm 40290093 battery te...

Страница 21: ...DIAGRAMS DRAWINGS EN M GV4 Piccolo for marine applications May 2017 21 5 DIAGRAMS DRAWINGS 5 1 ELECTRICAL DIAGRAMS Figure 26 Electrical control diagram ...

Страница 22: ...DIAGRAMS DRAWINGS 22 May 2017 M GV4 Piccolo for marine applications EN Figure 27 Electrical wiring diagram ...

Страница 23: ...DIAGRAMS DRAWINGS EN M GV4 Piccolo for marine applications May 2017 23 5 2 MECHANICAL DRAWINGS Figure 28 GV4 Piccolo mechanical drawings ...

Страница 24: ...Kelvinlaan 82 9207 JB Drachten Netherlands Tel 31 512 571550 Fax 31 512 571599 www whisperpower com info whisperpower com ...

Отзывы: