4

The heat pump or condensing unit should be hoisted with 2 lifting 
slings. Attach the slings to rigging shackles that have been 
hooked through holes in the lifting brackets.

Place 2 spreaders on top of the heat pump or condensing unit to 
protect it from damage from the pressure exerted by the slings. 
Make sure that all equipment is rated to handle at least 750 lbs 
and that the slings will not allow the heat pump or condensing 
unit to shift. See “Typical Sling Configuration.”

Typical Sling Configuration

Convert to Downflow

This heat pump or condensing unit is factory-built for horizontal 
airflow applications and may also be field-converted for 
downflow use.

To convert to downflow use:

1. Remove the filter access panel.

2. Remove the two downflow duct cover plates (one screw and 

tab for each) found in the return and supply air 
compartments.

3. Using eight #10 x 

³⁄₄

" screws (field supplied), install the 

previously removed duct covers on the horizontal return and 
supply air openings. Use the pilot holes provided.

4. Reinstall the filter access panel. 

 

Connect Condensate Drain

The condensate drain outlet is a 

³⁄₄

" threaded PVC fitting located 

at the bottom on the side of the heat pump or condensing unit. A 

³⁄₄

" drain line with trap must be installed on all applications to 

avoid accumulation of condensate under or around the heat 
pump or condensing unit.

Install Condensate Trap

1. Construct the condensate trap from PVC tubing as shown in 

“Condensate Trap Construction.”

NOTES:

The condensate trap allows a standing column of water of 
at least 2" (50 mm).

The top of the drain trap inlet must be at least least 1" 
(25 mm) above the top of the drain trap outlet.

The trap should be installed as close to the heat pump or 
condensing unit as possible, while still providing proper 
drainage.

For service access, do not block heat exchanger access 
panel or the filter access panel with the drain line.

2. Thread the drain assembly into the 

³⁄₄

" PVC fitting.

NOTE: Do not glue the threaded fitting so it can be removed 
during servicing of unit.

3. Run the drain line to an open drain or other suitable disposal 

point.

Condensate Trap Construction

A. Spreaders
B. Cables

C. Lifting bracket (accessory lift kit) 

D. Sheet metal 

screw 

E. Pallet 

A. Horizontal return and supply air openings
B. Filter access panel 

C. Downflow duct cover plates 

D

E

A

B

C

C

A

B

A.

³⁄₄

" PVC fitting (threaded) drain 

condensate connection

B.

³⁄₄

" drain pipes, field provided

C. Drain trap outlet
D. Drain trap inlet

A

B

1" Min.

12" Max.

2" Min.

3" Min.

C

D

Содержание W2PC3

Страница 1: ...eed Motor 10 SYSTEM MAINTENANCE 11 TROUBLESHOOTING 12 ASSISTANCE OR SERVICE 16 Accessories 16 48373F007 Whirlpool Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Whirlpool Models W2PH3 W2PC3 W4PH4 W4PC4 You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential h...

Страница 2: ...it must be installed on a solid level mounting pad that will not settle or shift Isolate the pad from the building structure to avoid possible transmission of sound or vibration from the heat pump or condensing unit into the conditioned space The heat pump or condensing unit foundation should be raised to a minimum of 3 above finish grade In areas which have prolonged periods of temperature below ...

Страница 3: ...ge claims should be filed with the carrier immediately Claims of shortages should be filed with the seller within 5 days NOTE If any damages are discovered and reported to the carrier do not install the heat pump or condensing unit as your claim may be denied PlaceHeatPumporCondensingUnitin Final Location IMPORTANT Place the heat pump or condensing unit in the final location and position it in the...

Страница 4: ...d at the bottom on the side of the heat pump or condensing unit A drain line with trap must be installed on all applications to avoid accumulation of condensate under or around the heat pump or condensing unit Install Condensate Trap 1 Construct the condensate trap from PVC tubing as shown in Condensate Trap Construction NOTES The condensate trap allows a standing column of water of at least 2 50 ...

Страница 5: ...ed Surface Area for Disposable Filters chart and are based on a face velocity of 325 ft 99 1 m per min for disposable filters and 525 ft 160 m per min for cleanable filters InstallAccessoryHeater 1 Disconnect power 2 Remove the heater compartment access panel 3 Remove the heater blockoff by removing the 4 screws holding it in place 4 Insert the heater kit into the control panel and fasten in the s...

Страница 6: ... prevent moisture from entering the heat pump or condensing unit Low voltage wiring must be separated from line voltage wiring Line Voltage Connections 1 Disconnect power 2 Remove the blower access panel 3 Remove the heater compartment access panel 4 Route the field supply wires through the line voltage conduit opening to the electrical connection area providing sufficient length to connect to the...

Страница 7: ...t pump or condensing unit in its final location SEQUENCE OF OPERATION CoolingCycle CoolingOnly Upon cooling demand the thermostat closes circuit R to Y Closing R to Y energizes the package unit for cooling operation and closes the contactor starting the compressor and outdoor fan The thermostat automatically closes R to G circuit which also brings on the indoor fan at the same time Upon satisfying...

Страница 8: ...at run cycle This time period must occur before a defrost cycle is initiated The defrost interval can be adjusted to 30 T1 60 T2 or 90 T3 minutes See Defrost Control Board in the Adjust Defrost System section The defrost timing jumper is factory installed to provide a 60 minute defrost interval If the timing selector jumper is not in place the control defaults to a 90 minute defrost interval The m...

Страница 9: ... Plug to the pins corresponding to 90 4 Replace the heater compartment access panel 5 Reconnect power TroubleshoottheDefrostSystem Diagnostic LEDs The defrost board uses 2 LEDs for diagnostics The LEDs flash a specific sequence according to the condition Defrost Control Board Diagnostic LEDs Mode Green LED DS2 Red LED DS1 No Power to Board Off Off Normal Operation Power to Board Simultaneous Slow ...

Страница 10: ...y a timing circuit in the blower control Timings are not adjustable There is no blower on delay after a call for heating or cooling Blower off delay is 90 seconds after the thermostat is satisfied NOTE No blower speed adjustments are required CirculatingAirBlower VariableSpeedMotor Packaged units equipped with a variable speed circulation air blower motor will deliver a constant airflow within a w...

Страница 11: ... reduction in the normal airflow rate The variable speed motor interface board provides a connection for a humidistat on the HUM terminal When a humidistat is connected the dehumidifier resistor on the interface must be cut The humidistat should be wired to open during high humidity which will reduce blower airflow ADJUST HEAT and COOL Taps and Dehumidify Resistor SYSTEM MAINTENANCE Leaves and oth...

Страница 12: ...UT CMC1 S6 L1 24 V Fuse Y A15 W2 R Y BU W G OR R BU BU Y BU BK BK Defrost Control BU W P 1 P 2 P 4 P 6 P 5 Reversing Valve Defrost Thermostat Defrost Control High Pressure Switch if used Contactor Blower Control Indoor Blower Motor Capacitor Condenser Fan Motor Blower Control Compressor Contactor Compressor Compressor Contactor Thermostat Blower Speed Chart for Heat Pump and Cooling Only Models Un...

Страница 13: ... 60 Dual Capacitor Y W R R C12 L2 T2 T1 L1 Compressor B1 C R S F C H PCO if used NC C B3 BU 24V 240V 208V R Reversing Valve High Pressure Switch S4 NOTE Connection must be jumpered when pressure switch is not used Defrost Control CMC1 Defrost Thermostat S6 P 4 Contactor Low Pressure Switch S79 L1 BU BK BK BK BK Y Y Y Y Y K1 Fan O OUT LO PS DF COMMON Y1 OUT HI PS 24V W1 C L R O Y1 W BU R OR Y W R P...

Страница 14: ...K R P 3 A15 Blower Control C NC NO C L M H B3 C4 Indoor Blower Motor Capacitor Condenser Fan Motor B4 BK BK R Y Compressor Compressor Contactor R BR PR K1 2 P 2 L2 L2 T2 K1 1 Compressor Contactor BK Dual Capacitor C12 R S C C F H T1 P 1 B1 208 230V 1 60 L1 L1 T1 Blower Speed Chart for Heat Pump and Cooling Only Models Unit Factory shipped Settings Cooling Input BLK 24 L Low 30 M Medium 36 H High 4...

Страница 15: ...OOL NORM TEST A B C D A B C D ICM Board A54 HUM R C1 EM W1 O Y2 Y1 G B3 Indoor Blower Motor R BU W OR Y G Transformer BU 24V 240V 208V R T1 Y B4 PR BR BK BK BK BK K1 1 Compressor Contactor Indoor Blower Motor P 1 BK BK L1 208 230V 1 60 Dual Capacitor W R R C12 T2 T1 L1 Compressor B1 C R S F C H PCO if used B3 BK K1 1 Compressor Contactor L2 P 2 Y L2 Y Factory Shipped Settings Unit ADJUSTHEAT COOL ...

Страница 16: ...1 W G G W2 W2 O O Without Economizer Thermostat Outdoor Unit C C R R Y1 Y W W1 W1 G G Y2 W2 W2 O O Thermostat Outdoor Unit With Economizer Economizer Blue White Yellow Orange Green Black Part Number Accessory Model s 48193 001 ALIFT801 1 Lifting Bracket Kit All Electric Heater Kits Cat No Model No Description Used On 10W47 PHK05BP 1 5 kw Electric Heater Kit All 10W48 PHK07BP 1 7 5 kw Electric Heat...

Отзывы: