17

2. The temperature rise must be within the range specified on 

the rating plate.

NOTE: Air temperature rise is the temperature difference 
between supply and return air.

With a properly designed system, the proper amount of 
temperature rise will normally be obtained when the unit is 
operated at the rated input with the recommended blower speed.

If the correct amount of temperature rise is not obtained, it may 
be necessary to change the blower speed. A higher blower speed 
will lower the temperature rise. A slower blower speed will 
increase the temperature rise.

NOTE: Blower speed must be set to give the correct air 
temperature rise through the unit as marked on the rating plate.

External Static Pressure Check

The total external static pressure must be checked on this unit to 
determine if the airflow is proper.

Blower Speed Adjustments

Refer to the wiring diagram in “Troubleshooting” to verify the 
speed tap settings.

Depending upon the model, blower speeds are changed at the 
indoor blower. The ignition control board has 4 blower speeds: 
Low Heat, High Heat, Low Cool and High Cool.

NOTE: Fan Only energizes at Low Heat speed. 

The WGGE45 models are equipped with X-13 motors. X-13 
motors are constant torque motors with very low power 
consumption. This motor is energized by 24VAC. Adjust the CFM 
for the unit by changing the 24VAC leads to the speed terminal 
block on the motor.

NOTE: Heating airflow must be adjusted to provide the 
temperature rise shown on the rating plate. A higher speed tap 
may not provide more airflow. Blower speeds are programmed to 
deliver adequate airflow at rated external static pressure (ESP). 
Refer to airflow table provided in the Product Data Book 
applicable to your model for details.

Blower Performance Data

Heating

Cooling

Speed 
Tap

Definition

Lead 
Color

Speed 
Tap

Definition

Lead 
Color

T1

Low Speed 
Heat

White

T3

Low Speed 
Cool

Purple

T2

High Speed 
Heat

Brown

T4

High Speed 
Cool

Yellow

T5

High Speed 
Cool 
High-Static

WGGE4524A070M—Rise Range: 35º to 65º

Unit Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

T1—1

st

-

Stage 
Heating 
Speed

CFM 742

677

631

575

526

-

-

-

Watts 84

89

97

101

111

-

-

-

Amps 0.75 0.82

0.90 0.92 1.01 -

-

-

Rise

52

57

62

X

X

-

-

-

T2—2

nd

-

Stage 
Heating 
Speed

CFM 907

857

814

761

727

678

-

-

Watts 134

140

149

154

165

169

-

-

Amps 1.18

1.24

1.32 1.33 1.41 1.47

-

-

Rise

57

61

64

X

X

X

-

-

T3—
Cooling 
Speed

CFM 857

816

760

721

670

629

-

-

Watts 116

126

131

140

145

155

-

-

Amps 1.04

1.16

1.18 1.25 1.31 1.39

-

-

T4—
Cooling 
Speed

CFM 907

857

814

761

727

678

-

-

Watts 134

140

149

154

165

169

-

-

Amps 1.18

1.24

1.32 1.33 1.41 1.47

-

-

T5—
Cooling 
Speed

CFM 1,040 988

949

903

871

824

-

-

Watts 185

198

208

213

222

228

-

-

Amps 1.33

1.40

1.42 1.49 1.55 1.58

-

-

WGGE4530A090M—Rise Range: 45º to 75º

Unit Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

T1—1

st

-

Stage 
Heating 
Speed

CFM 1,065 1,003 961

913

855

814

749

713

Watts 168

174

185

195

202

212

218

227

Amps 1.42 1.48

1.55 1.62 1.69 1.76

1.82 1.87

Rise

49

52

54

57

60

63

69

72

T2—2

nd

-

Stage 
Heating 
Speed

CFM 1,255 1,217 1,165 1,113 1,073 1,018 991

-

Watts 257

269

274

285

296

302

313

-

Amps 2.10

2.19

2.21 2.30 2.36 2.41

2.48 -

Rise

55

57

59

62

64

68

70

-

T3—
Cooling 
Speed

CFM 1,148 1,092 1,044 994

929

811

763

715

Watts 170

176

184

194

210

222

224

236

Amps 1.55

1.66

1.72 1.77 1.89 1.99

2.03 2.07

T4—
Cooling 
Speed

CFM 1,148 1,092 1,044 994

929

811

763

715

Watts 170

176

184

194

210

222

224

236

Amps 1.55

1.66

1.72 1.77 1.89 1.99

2.03 2.07

T5—
Cooling 
Speed

CFM 1,333 1,293 1,237 1,193 1,158 1,101 -

-

Watts 304

314

321

333

341

345

-

-

Amps 2.41

2.48

2.54 2.71 2.77 2.78

-

-

Содержание Gold WGGE45

Страница 1: ... 14 Gas Manifold Pressure Measurement and Adjustment 15 Blower Speed Adjustments 17 Blower Performance Data 17 Unit Shutdown 19 Cooling Start Up 19 SEQUENCE OF OPERATION 20 Heating System 20 Cooling System 20 Fan Only 21 Cooling Start Up 21 MAINTENANCE 22 TROUBLESHOOTING 23 Unit Fails to Operate Properly 23 Ignition Control Error Codes 23 Abnormal Operation Heating 24 Abnormal Operation Cooling 25...

Страница 2: ... outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace A gas fired furnace for installation in a residential garage must be installed as specified in the Location Requirements section of these instructions The furnace shall be installed so the electrical components are protected ...

Страница 3: ...damage personal injury or death Goodman 37 WARNING To prevent the risk of property damage personal injury or death do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit Goodman 7 Installation and repair of this unit should be performed ONLY by individuals meeting the requirements of an Entry Level Technician as specified by the Air Con...

Страница 4: ...ources of such compounds include swimming pool chemicals and chlorine bleaches paint stripper adhesives paints varnishes sealers waxes which are not yet dried and solvents used during construction and remodeling Various commercial and industrial processes may also be sources of chlorine fluorine compounds To avoid possible illness or death of the building occupants do not locate outside air intake...

Страница 5: ...de A 47 119 4 cm B 51 129 5 cm C 18 46 8 cm D Medium 9 24 2 cm large 14 35 6 cm E 7 20 2 cm F 16 40 6 cm G 1 3 5 cm H 5 14 cm I Medium 32 81 3 cm large 40 101 6 cm J 2 7 cm K Air return L Medium 16 40 6 cm large 18 45 7 cm M Air supply N 3 7 6 cm O Evaporator control panel access panel P 16 40 9 cm Q 19 48 6 cm R 4 12 1 cm S Gas supply entrance T Condensate drain connection 1 9 cm NPT female U Hea...

Страница 6: ...rdance with the Minimum Required Surface Area for Disposable Filters chart All return air must pass through a filter before entering the unit An electronic air cleaner filter rack or other accessible filter arrangement must be installed in the return air ductwork Minimum recommended filter areas are listed in the Minimum Required Surface Area for Disposable Filters chart and are based on a face ve...

Страница 7: ...Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or certified copy thereof showing trade and other discounts or reductions d Copy of the inspection report issued by the carrier representative at the time damage is reported to the carrier The carrier is responsible for making a prompt inspection of the damage and for a thor...

Страница 8: ...ng the 3 screws provided attach the combustion air intake hood with the opening facing down to the heat exchanger access door Hood Attachment ConnectCondensateDrain The condensate drain outlet is a threaded PVC fitting located at the bottom on the side of the unit A drain line with trap must be installed on all applications to avoid accumulation of condensate under or around the unit Condensate Dr...

Страница 9: ... labeled Stage Delay from NONE to 5 MIN or 10 MIN This selection will cause the control to run on low stage for the selected time 5 or 10 minutes and then shift to high stage This option controls both cooling and heating modes If the jumper is not moved only low stage cool and low stage heat will operate IMPORTANT Electrical wiring disconnect means and over current protection are to be supplied by...

Страница 10: ...e the black wire lead from the 240 volt terminal on the transformer to the 208 volt terminal center tap on the transformer See the wiring connection diagrams in Troubleshooting 4 Replace the burner access panel MakeGasConnections NOTE This unit is factory set to operate on Natural gas at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas i...

Страница 11: ...Proper Piping Practice illustration for the general layout at the unit The following rules apply 1 Use black iron pipe and fittings for the supply piping The use of a flex connector and or copper piping is permitted as long as it is in agreement with local codes 2 Use pipe joint compound on male threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint un...

Страница 12: ...ll gas appliances in operation Maintaining proper gas pressure depends on 3 main factors Vaporization rate depending on the temperature of the liquid and the wetted surface area of the container or containers Proper pressure regulation Two stage regulation is recommended for both cost and efficiency Pressure drop in the lines between the regulators and between 2nd stage regulator and the appliance...

Страница 13: ...s at 15 psig settings multiply by 1 13 To convert to capacities at 5 psig settings multiply by 0 879 A 1st stage regulator B 5 to 15 psig 20 psig maximum C 2nd stage regulator D Continuous 11 W C A D C B Propane Gas Piping Chart I Pipe or Tubing Length ft m Tubing Size O D Type L Nominal Pipe Size Schedule 40 30 9 2 309 700 1 303 2 205 3 394 1 843 3 854 40 12 2 265 599 1 115 1 887 2 904 1 577 3 29...

Страница 14: ... this manual reset control Rollout Protection on Burner Bracket Propane Gas Piping Chart II Tubing Size O D Type L Nominal Pipe Size Schedule 40 Pipe or Tubing Length ft m 1 1 1 10 3 49 110 206 348 539 291 608 1 146 2 353 3 525 20 6 1 34 76 141 239 368 200 418 788 1 617 2 423 30 9 2 27 61 114 192 296 161 336 632 1 299 1 946 40 12 2 23 52 97 164 253 137 284 541 1 111 1 665 50 15 2 20 46 86 146 224 ...

Страница 15: ...and there is no gas odor move the gas control valve switch to the On position 9 Replace the heat exchanger door on the side of the unit 10 Open the manual gas shutoff valve external to the unit 11 Turn on the electrical power supply to the unit 12 Set the thermostat to the desired setting Gas Control Valve White Rodgers 35G54 Gas Manifold Pressure Measurement and Adjustment Gas Supply And Manifold...

Страница 16: ...ealer for the appropriate conversion Gas Input Check Natural Gas Only To measure the gas input use a gas meter and proceed as follows 1 Turn off the gas supply to all other appliances except the unit 2 With the unit operating time the smallest dial on the meter for 1 complete revolution If this is a 2 cu ft dial divide the seconds by 2 if it is a 1 cu ft dial use the seconds as is This gives the s...

Страница 17: ... table provided in the Product Data Book applicable to your model for details BlowerPerformanceData Heating Cooling Speed Tap Definition Lead Color Speed Tap Definition Lead Color T1 Low Speed Heat White T3 Low Speed Cool Purple T2 High Speed Heat Brown T4 High Speed Cool Yellow T5 High Speed Cool High Static WGGE4524A070M Rise Range 35º to 65º Unit Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 T1 1st St...

Страница 18: ... 1 325 1 268 1 198 Watts 431 445 456 463 475 489 495 502 Amps 1 64 1 69 1 71 1 76 1 80 1 84 1 88 1 90 WGGE4549A115M Rise Range 45º to 75º Unit Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 T1 1st Stage Heating Speed CFM 1 140 1 090 1 038 980 914 852 806 741 Watts 178 188 199 212 220 231 242 248 Amps 1 52 1 57 1 67 1 76 1 79 1 90 1 97 2 01 Rise 56 59 62 65 70 75 X X T2 2nd Stage Heating Speed CFM 1 417 1 ...

Страница 19: ...F superheat at the compressor is required at conditions 95ºF 35ºC outdoor ambient dry bulb temperature 80ºF 27ºC dry bulb 67ºF 19ºC wet bulb indoor ambient temperature approximately 50 humidity This superheat varies when conditions vary from the conditions described After superheat is adjusted it is recommended that subcooling be checked at the condenser coil liquid line out In most operating cond...

Страница 20: ...n NOTE If a single stage thermostat is used the control will step to low stage after the main burners light and remain at low stage for 5 or 10 minutes depending on the jumper position If the call for heat remains after the transition delay time expires the control will transition from low stage to high stage 6 The 30 second Heat Fan On delay time begins after the main burners light 7 The unit del...

Страница 21: ...pplication check the unit refrigerant subcooling at the condenser The refrigerant subcooling is a function of outdoor ambient temperature and return air temperature of the conditioned space It is the installing contractors responsibility to ensure that the proper refrigerant subcooling at the condenser is adjusted for each application For example 10ºF refrigerant subcooling level is adequate for a...

Страница 22: ...e Sensor Qualified Servicer Only A drop in the flame current can be caused by a nearly invisible coating on the flame sensor This coating created by the fuel or combustion air supply can be removed by gently cleaning the flame sensor with steel wool NOTE After cleaning the microamp signal should be stable and in the range of 4 to 6 microamps DC Flame Sensor Flue Passages Qualified Servicer Only At...

Страница 23: ...unit on at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They should extend directly outward from the burner ports without curling downward floating or lifting off of the ports TROUBLESHOOTING UnitFailstoOperateProperly Review Sequence of Operation and visua...

Страница 24: ...quent attempts the control will recycle for 4 consecutive ignition attempts 5 attempts total before locking out The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts The integrated control will automatically reset after 1 hour or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over 5 seconds If diagno...

Страница 25: ...changer Failed induced draft blower Insufficient combustion air NOTE The rollout limit switch is a manual reset limit switch located on the burner bracket The cause of the flame rollout must be determined and corrected before resetting the limit Flame Detected with Gas Control Valve Closed 5 Flashes Red LED 2 Flashes Amber LED If a flame is detected with the gas control valve de energized the comb...

Страница 26: ...noid not present on all models BK BK T1 T2 L2 L1 CC For 208 volt transformer operation move the black wire from Terminal 3 to Terminal 2 on the transformer For 208 volt transformer operation move the black wire from Terminal 3 to Terminal 2 on the transformer TR 24V 208 240 C 1 2 3 BU GND Power Supply 208 230 1 60 Use copper conductors only For economizer remove plug from economizer harness Connec...

Страница 27: ... Control Valve Integrated Ignition Control Ignitor Limit Switch Pressure Switch Run Capacitor for Compressor and Fan Rollout Switch Solenoid 2nd Stage Cool Transformer Vent Motor Component Legend BK BU BR G OR PR R W Y Black Blue Brown Green Orange Purple Red White Yellow Symbol Color Ignition Control Diagnostic Indicator Chart Red Light Signal Refer to Abnormal Operation Heating and Abnormal Oper...

Страница 28: ...irlpool Home Cooling and Heating dealer Placeholder 90 120 150 180 Circulator Blower High Off Seconds Gas Control Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 Low High Off Low Off On High Off Low High Off Low Placeholder Circulator Blower High Off Seconds Compressor Outdoor Fan Thermostat Low High Off Low High Off Low High Off Low WPIO 325C 2009 All rights reserved Registered T...

Отзывы: