background image

12

Proper Piping Practice

NOTE: The unit gas supply entrance is factory sealed with plugs. 
Keep plugs in place until gas supply is ready to be installed. Once 
ready, replace the plugs with the supplied grommets and install 
gas supply line.

Check Gas Piping

IMPORTANT:

The unit and its gas connections must be leak tested before 
placing in operation.

Do not use a match or open flame to test for leaks.

Do not exceed specified pressures for testing.

Disconnect this unit and its shutoff valve from the gas supply 
during any pressure testing of the system at test pressures in 
excess of 

¹⁄₂

 psig (3.48 kPa).

Close the manual shutoff valve during any pressure testing of 
the gas supply piping system at test pressures equal to or 
less than 

¹⁄₂

 psig (3.48 kPa).

There will be air in the gas supply line after testing for leaks on a 
new installation. Therefore, the air must be bled from the line by 
loosening the ground joint union until pure gas is expelled. 
Tighten the ground joint union and wait for 5 minutes until all gas 
has been dissipated in the air. Be certain there is no open flame in 
the vicinity during air bleeding procedure. The unit is placed in 
operation by closing the main electrical disconnect switch for the 
unit.

Install Propane Gas

NOTE: Propane gas conversion kits must be installed to convert 
units to propane gas.

A gas detecting warning system is the only reliable way to detect 
a propane gas leak. Rust can reduce the level of odorant in 
propane gas. Do not rely on your sense of smell. Contact a local 
propane gas supplier about installing a gas detecting warning 
system. 

All propane gas equipment must conform to the safety standards 
of the National Board of Fire Underwriters, NBFU Manual 58. 

For satisfactory operation, propane gas supply pressure must be 
within 9.7" W.C. to 10.3" W.C. at the furnace manifold with all gas 
appliances in operation.

Maintaining proper gas pressure depends on 3 main factors: 

Vaporization rate, depending on the temperature of the liquid 
and the wetted surface area of the container or containers.

Proper pressure regulation. Two-stage regulation is 
recommended for both cost and efficiency. 

Pressure drop in the lines between the regulators, and 
between 2

nd

 stage regulator and the appliance. Pipe size 

required will depend on the length of the pipe run and the 
total load of all appliances.

A. Manual shutoff valve
B. Drip leg

C. Ground joint union (installed upstream of 

gas control valve)

D. Grommet

D

C

B

A

Goodman 90

To prevent property damage or personal injury due to fire,
the following instructions must be performed regarding
gas connections and pressure testing:
-The unit and its gas connections must be leak tested 
before placing in operation. Because of the danger of 
explosion or fire, never use a match or open flame to test 
for leaks. Never exceed specified pressures for testing. 
Higher pressure may damage gas control valve and cause 
overfiring which may result in premature heat exchange 
failure.

-The unit and its gas shutoff valve must be disconnected 

from the gas supply during any pressure testing of that 
system at test pressures in excess of 

¹⁄₂

 psig (3.48 kPa).

-This unit must be isolated from the gas supply system 

by closing its manual shutoff valve during any pressure 
testing of the gas supply piping system at test pressures 
equal to or less than 

¹⁄₂

 psig (3.48 kPa).

CAUTION

Goodman 91

To avoid property damage or personal injury, be sure 
there is NO OPEN FLAME in the vicinity during air 
bleeding. 

WARNING

Goodman 92

To avoid property damage, personal injury or death due 
to fire or explosion caused by a propane gas leak, install 
a gas detecting warning device. Since rust can reduce the 
level of odorant in propane gas, a gas detecting warning 
device is the only reliable way to detect a propane gas 
leak. Contact a local propane gas supplier about installing 
a gas detecting warning device.

WARNING

Содержание Gold WGGE45

Страница 1: ... 14 Gas Manifold Pressure Measurement and Adjustment 15 Blower Speed Adjustments 17 Blower Performance Data 17 Unit Shutdown 19 Cooling Start Up 19 SEQUENCE OF OPERATION 20 Heating System 20 Cooling System 20 Fan Only 21 Cooling Start Up 21 MAINTENANCE 22 TROUBLESHOOTING 23 Unit Fails to Operate Properly 23 Ignition Control Error Codes 23 Abnormal Operation Heating 24 Abnormal Operation Cooling 25...

Страница 2: ... outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace A gas fired furnace for installation in a residential garage must be installed as specified in the Location Requirements section of these instructions The furnace shall be installed so the electrical components are protected ...

Страница 3: ...damage personal injury or death Goodman 37 WARNING To prevent the risk of property damage personal injury or death do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit Goodman 7 Installation and repair of this unit should be performed ONLY by individuals meeting the requirements of an Entry Level Technician as specified by the Air Con...

Страница 4: ...ources of such compounds include swimming pool chemicals and chlorine bleaches paint stripper adhesives paints varnishes sealers waxes which are not yet dried and solvents used during construction and remodeling Various commercial and industrial processes may also be sources of chlorine fluorine compounds To avoid possible illness or death of the building occupants do not locate outside air intake...

Страница 5: ...de A 47 119 4 cm B 51 129 5 cm C 18 46 8 cm D Medium 9 24 2 cm large 14 35 6 cm E 7 20 2 cm F 16 40 6 cm G 1 3 5 cm H 5 14 cm I Medium 32 81 3 cm large 40 101 6 cm J 2 7 cm K Air return L Medium 16 40 6 cm large 18 45 7 cm M Air supply N 3 7 6 cm O Evaporator control panel access panel P 16 40 9 cm Q 19 48 6 cm R 4 12 1 cm S Gas supply entrance T Condensate drain connection 1 9 cm NPT female U Hea...

Страница 6: ...rdance with the Minimum Required Surface Area for Disposable Filters chart All return air must pass through a filter before entering the unit An electronic air cleaner filter rack or other accessible filter arrangement must be installed in the return air ductwork Minimum recommended filter areas are listed in the Minimum Required Surface Area for Disposable Filters chart and are based on a face ve...

Страница 7: ...Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or certified copy thereof showing trade and other discounts or reductions d Copy of the inspection report issued by the carrier representative at the time damage is reported to the carrier The carrier is responsible for making a prompt inspection of the damage and for a thor...

Страница 8: ...ng the 3 screws provided attach the combustion air intake hood with the opening facing down to the heat exchanger access door Hood Attachment ConnectCondensateDrain The condensate drain outlet is a threaded PVC fitting located at the bottom on the side of the unit A drain line with trap must be installed on all applications to avoid accumulation of condensate under or around the unit Condensate Dr...

Страница 9: ... labeled Stage Delay from NONE to 5 MIN or 10 MIN This selection will cause the control to run on low stage for the selected time 5 or 10 minutes and then shift to high stage This option controls both cooling and heating modes If the jumper is not moved only low stage cool and low stage heat will operate IMPORTANT Electrical wiring disconnect means and over current protection are to be supplied by...

Страница 10: ...e the black wire lead from the 240 volt terminal on the transformer to the 208 volt terminal center tap on the transformer See the wiring connection diagrams in Troubleshooting 4 Replace the burner access panel MakeGasConnections NOTE This unit is factory set to operate on Natural gas at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas i...

Страница 11: ...Proper Piping Practice illustration for the general layout at the unit The following rules apply 1 Use black iron pipe and fittings for the supply piping The use of a flex connector and or copper piping is permitted as long as it is in agreement with local codes 2 Use pipe joint compound on male threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint un...

Страница 12: ...ll gas appliances in operation Maintaining proper gas pressure depends on 3 main factors Vaporization rate depending on the temperature of the liquid and the wetted surface area of the container or containers Proper pressure regulation Two stage regulation is recommended for both cost and efficiency Pressure drop in the lines between the regulators and between 2nd stage regulator and the appliance...

Страница 13: ...s at 15 psig settings multiply by 1 13 To convert to capacities at 5 psig settings multiply by 0 879 A 1st stage regulator B 5 to 15 psig 20 psig maximum C 2nd stage regulator D Continuous 11 W C A D C B Propane Gas Piping Chart I Pipe or Tubing Length ft m Tubing Size O D Type L Nominal Pipe Size Schedule 40 30 9 2 309 700 1 303 2 205 3 394 1 843 3 854 40 12 2 265 599 1 115 1 887 2 904 1 577 3 29...

Страница 14: ... this manual reset control Rollout Protection on Burner Bracket Propane Gas Piping Chart II Tubing Size O D Type L Nominal Pipe Size Schedule 40 Pipe or Tubing Length ft m 1 1 1 10 3 49 110 206 348 539 291 608 1 146 2 353 3 525 20 6 1 34 76 141 239 368 200 418 788 1 617 2 423 30 9 2 27 61 114 192 296 161 336 632 1 299 1 946 40 12 2 23 52 97 164 253 137 284 541 1 111 1 665 50 15 2 20 46 86 146 224 ...

Страница 15: ...and there is no gas odor move the gas control valve switch to the On position 9 Replace the heat exchanger door on the side of the unit 10 Open the manual gas shutoff valve external to the unit 11 Turn on the electrical power supply to the unit 12 Set the thermostat to the desired setting Gas Control Valve White Rodgers 35G54 Gas Manifold Pressure Measurement and Adjustment Gas Supply And Manifold...

Страница 16: ...ealer for the appropriate conversion Gas Input Check Natural Gas Only To measure the gas input use a gas meter and proceed as follows 1 Turn off the gas supply to all other appliances except the unit 2 With the unit operating time the smallest dial on the meter for 1 complete revolution If this is a 2 cu ft dial divide the seconds by 2 if it is a 1 cu ft dial use the seconds as is This gives the s...

Страница 17: ... table provided in the Product Data Book applicable to your model for details BlowerPerformanceData Heating Cooling Speed Tap Definition Lead Color Speed Tap Definition Lead Color T1 Low Speed Heat White T3 Low Speed Cool Purple T2 High Speed Heat Brown T4 High Speed Cool Yellow T5 High Speed Cool High Static WGGE4524A070M Rise Range 35º to 65º Unit Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 T1 1st St...

Страница 18: ... 1 325 1 268 1 198 Watts 431 445 456 463 475 489 495 502 Amps 1 64 1 69 1 71 1 76 1 80 1 84 1 88 1 90 WGGE4549A115M Rise Range 45º to 75º Unit Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 T1 1st Stage Heating Speed CFM 1 140 1 090 1 038 980 914 852 806 741 Watts 178 188 199 212 220 231 242 248 Amps 1 52 1 57 1 67 1 76 1 79 1 90 1 97 2 01 Rise 56 59 62 65 70 75 X X T2 2nd Stage Heating Speed CFM 1 417 1 ...

Страница 19: ...F superheat at the compressor is required at conditions 95ºF 35ºC outdoor ambient dry bulb temperature 80ºF 27ºC dry bulb 67ºF 19ºC wet bulb indoor ambient temperature approximately 50 humidity This superheat varies when conditions vary from the conditions described After superheat is adjusted it is recommended that subcooling be checked at the condenser coil liquid line out In most operating cond...

Страница 20: ...n NOTE If a single stage thermostat is used the control will step to low stage after the main burners light and remain at low stage for 5 or 10 minutes depending on the jumper position If the call for heat remains after the transition delay time expires the control will transition from low stage to high stage 6 The 30 second Heat Fan On delay time begins after the main burners light 7 The unit del...

Страница 21: ...pplication check the unit refrigerant subcooling at the condenser The refrigerant subcooling is a function of outdoor ambient temperature and return air temperature of the conditioned space It is the installing contractors responsibility to ensure that the proper refrigerant subcooling at the condenser is adjusted for each application For example 10ºF refrigerant subcooling level is adequate for a...

Страница 22: ...e Sensor Qualified Servicer Only A drop in the flame current can be caused by a nearly invisible coating on the flame sensor This coating created by the fuel or combustion air supply can be removed by gently cleaning the flame sensor with steel wool NOTE After cleaning the microamp signal should be stable and in the range of 4 to 6 microamps DC Flame Sensor Flue Passages Qualified Servicer Only At...

Страница 23: ...unit on at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They should extend directly outward from the burner ports without curling downward floating or lifting off of the ports TROUBLESHOOTING UnitFailstoOperateProperly Review Sequence of Operation and visua...

Страница 24: ...quent attempts the control will recycle for 4 consecutive ignition attempts 5 attempts total before locking out The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts The integrated control will automatically reset after 1 hour or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over 5 seconds If diagno...

Страница 25: ...changer Failed induced draft blower Insufficient combustion air NOTE The rollout limit switch is a manual reset limit switch located on the burner bracket The cause of the flame rollout must be determined and corrected before resetting the limit Flame Detected with Gas Control Valve Closed 5 Flashes Red LED 2 Flashes Amber LED If a flame is detected with the gas control valve de energized the comb...

Страница 26: ...noid not present on all models BK BK T1 T2 L2 L1 CC For 208 volt transformer operation move the black wire from Terminal 3 to Terminal 2 on the transformer For 208 volt transformer operation move the black wire from Terminal 3 to Terminal 2 on the transformer TR 24V 208 240 C 1 2 3 BU GND Power Supply 208 230 1 60 Use copper conductors only For economizer remove plug from economizer harness Connec...

Страница 27: ... Control Valve Integrated Ignition Control Ignitor Limit Switch Pressure Switch Run Capacitor for Compressor and Fan Rollout Switch Solenoid 2nd Stage Cool Transformer Vent Motor Component Legend BK BU BR G OR PR R W Y Black Blue Brown Green Orange Purple Red White Yellow Symbol Color Ignition Control Diagnostic Indicator Chart Red Light Signal Refer to Abnormal Operation Heating and Abnormal Oper...

Страница 28: ...irlpool Home Cooling and Heating dealer Placeholder 90 120 150 180 Circulator Blower High Off Seconds Gas Control Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 Low High Off Low Off On High Off Low High Off Low Placeholder Circulator Blower High Off Seconds Compressor Outdoor Fan Thermostat Low High Off Low High Off Low High Off Low WPIO 325C 2009 All rights reserved Registered T...

Отзывы: