5-5
HIGH AND LOW WATER
LEVEL SWITCHES
Refer to page 4-16 for the procedure for access-
ing the high and low water level switches.
1. Unplug air conditioner or disconnect power.
2. Disconnect the high or low water level
switch connector from the control board.
3. Set the ohmmeter to the R x 1 scale.
4. Touch the ohmmeter test leads to the
plug terminals. The meter should indicate
an open circuit (infinite) with the switch
float down, and continuity (0 Ω) with the
float raised.
OVERLOAD PROTECTOR
Refer to page 4-20 for the procedure for ac-
cessing the overload protector.
1. Unplug air conditioner or disconnect power.
2.
Discharge the compressor motor ca-
pacitor by touching a 20,000 Ω resis-
tor to the capacitor terminals.
3. Disconnect the overload protector wires.
4. Set the ohmmeter to the R x 1 scale.
5. Touch the ohmmeter test leads to the
overload protector terminal and connec-
tor. The meter should indicate continuity
(0 Ω).
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.