40
Vacuum pumping
Leakage detection
Use vacuum pump
1. Remove the valve caps
on the liquid valve and
gas valve and the nut of
refrigerant charging vent.
2. C o n n e c t t h e c h a r g i n g
hose of piezometer to
the refrigerant charging
vent of gas valve and
then connect the other
c h a r g i n g h o s e t o t h e
vacuum pump.
3. Open the piezometer com-
pletely and operate for
10-15min to check if the
pressure of piezometer
remains in -0.1MPa.
4. Close the vacuum pump and
maintain this status for 1-2min
to check if the pressure of piezometer remains in -0.1MPa. If the pressure
decreases, there may be leakage.
5. Remove the piezometer, open the valve core of liquid valve and gas valve
completely with inner hexagon spanner.
6. Tighten the screw caps of valves and refrigerant charging vent.
7. Reinstall the handle.
Note:
- In case of removing value cap indoor unit, remove a nut with small
diameter firstly. Otherwise, seal cap with bigger diameter will fly out.
1. With leakage detector:
Check if there is leakage with leakage detector.
2. With soap water:
If leakage detector is not available, please use soap water for leakage
detection. Apply soap water at the suspected position and keep the soap
water for more than 3 mins. If there are air bubbles coming out of this
position, there's a leakage.
Содержание ACH09000R
Страница 20: ...17 K QQ ć K D K Z D D ʝ DQG ʞ K D ...
Страница 23: ...20 K 45oC to c dry ...
Страница 28: ...25 DEQRUPDO RU VWUDQJH VPHOO ...
Страница 29: ...26 Installation dimension diagram Indoor Unit Outdoor Unit ...
Страница 35: ... J J Q ACV09000R ACH09000R ACV12000R ACH12000R 32 ...
Страница 40: ...37 Q chassis outdoor drain joint drain vent Drain hose foot holes foot holes ...
Страница 45: ...42 P 39 AF YX_ KAF AQ AFF KAF K 0 1 0 0 ...
Страница 93: ...டઅဳ ؿ ສ 90 ᔾ ᄈ ؿ ႇОቸ ݯ 5 D டઅဳ قؿ ဳ ϝ ࣩ ဳ ϝ О J P Оธ J P ዀຝ ݚ 15 15 30 60 250 350 20 50 120 120 250 350 ...
Страница 96: ... ෮iΣɻʼ خ τ Є א ᘩֶɺ ޚ ଲɾ୮cȹล ߜʼ ݯ خ ๅe 66129924622 ...