exhaust
hood or
sweep
elbow

180°

sweep

elbow

wall

wall

roof

main exhaust vent

horizontal vent

2 ft. (61 cm)
min. above

vertical vent

highest point of

building

main collector

vent

Do Not  

install screening or cap over

end of vent.

Gas requirements

OBSERVE ALL GOVERNING CODES
AND ORDINANCES.

Page 4

An

exhaust hood 

should cap the

outside end of the main vent to
prevent exhausted air from returning
to the dryers. If an exhaust hood
cannot be used, the outside end of
the main vent should have a sweep
elbow directed downward. If the
main vent travels vertically through
the roof, rather than through the wall,
install 180° sweep elbow on the end
of vent at least 2 feet (61 cm) above
the highest part of the building. The
opening wall or roof shall have a
diameter 1/2 inch (1.3 cm) larger than
the exhaust vent diameter. The
exhaust vent should be centered in
the opening.

A.

The installation must conform

with local codes, or in the absence of
local codes with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54
installation codes.

B.

The design of this dryer has

been certified by the CSA
International for use at altitudes up to
10,000 feet (3048 m) above sea level
at the B.T.U. rating indicated on the
model/serial plate. Burner input
adjustments are not required when
the dryer is operated up to this
elevation.
When installed above 10,000 feet
(3048 m), a four percent (4%)
reduction of the burner B.T.U. rating
shown on the model/serial plate is
required for each 1,000 foot (305 m)
increase in elevation. For assistance
when converting to other gas types
and/or installing above 10,000 feet
(3048 m) elevation, contact your
local service company.

Four-inch outlet hood is preferred.

However, a 2-1/2-inch (6.4 cm) outlet
exhaust hood may be used. A 
2-1/2-inch (6.4 cm) outlet creates
greater back pressure than other
hood types. For permanent
installation, a stationary exhaust
system is required.

A main exhaust vent 

can be used for

exhausting a group of dryers. Main
exhaust vent should be sized to
remove 200 CFM of air per dryer.
Large-capacity lint screens of proper
design may be used in the main
exhaust vent if checked and cleaned
frequently. The room where the dryers
are located should have make-up air
equal to or greater than the CFM of
all the dryers in the room.

Back-draft Damper Kits,

Part No.

3391910, are available from your
Whirlpool dealer and should be
installed in each dryer's exhaust vent
to prevent exhausted air from
returning into the dryers and to keep
the exhaust in balance within the
main exhaust vent. Unobstructed air
openings are required.

Each exhaust vent 

should enter the

main vent at an angle pointing in the
direction of the airflow. Vents entering
from the opposite side should be
staggered to reduce the exhausted
air from interfering with the other
vents.

The

maximum angle 

of each vent

entering the main vent should be no
more than 30°.

Keep air openings free of dry
cleaning fluid fumes. Fumes create
acids which, when drawn through the
dryer heating units, can damage
dryers and loads being dried.

clean-out cover

should be located

on the main exhaust vent for
periodically cleaning of the exhaust
system.

dryer exhaust vent

dryer exhaust vent

main collector vent

air flow

30° max.

30° max.

dryer exhaust vent

dryer exhaust vent

30° max.

An 

exhaust hood 

should cap the

exhaust vent to prevent exhausted air
from returning into the dryer. The
outlet of the hood must be at least 
12 inches (30.5 cm) from the ground
or anything else that may be in the
path of the exhaust.

WARNING

Explosion Hazard

Use a new AGA or CSA
approved gas supply line.

Install a shut-off valve.

Securely tighten all gas
connections.

If connected to LP, have a
qualified person make sure gas
pressure does not exceed 13"
(33 cm) water column. Examples
of a qualified person include
licensed heating personnel,
authorized gas company
personnel, and authorized
service personnel.

Failure to do so can result in
death, explosion, or fire.

Gas Dryer

Содержание 8316557

Страница 1: ...tallation Instructions with the owner Owner Keep Installation Instructions for future reference Save Installation Instructions for local electrical inspector s use COMMERCIAL ELECTRONIC DRYER GAS Part No 8316557 COMMERCIAL LAUNDRY PRODUCTS www whirlpool com 120 volt 60 Hz ELECTRIC 120 240 volt 60 Hz ...

Страница 2: ...nstalled in an area where it will be exposed to water and or weather It is your responsibility to If installing a GAS dryer FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliances IMPORTANT SAFETY INSTRUCTIONS WARNING To reduce the risk of fire electric shock or injury to persons when using your appliance follow basic preca...

Страница 3: ...tal foil vent Failure to do so can result in death or fire WARNING Metal flexible vent must be fully extended and supported when the dryer is in its final position DO NOT KINK OR CRUSH THE VENT The metal flexible vent must be completely open to allow adequate exhaust air to flow Allow as much room as possible when using elbows or making turns Bend vent gradually to avoid kinking Remove excess flex...

Страница 4: ... is required A main exhaust vent can be used for exhausting a group of dryers Main exhaust vent should be sized to remove 200 CFM of air per dryer Large capacity lint screens of proper design may be used in the main exhaust vent if checked and cleaned frequently The room where the dryers are located should have make up air equal to or greater than the CFM of all the dryers in the room Back draft D...

Страница 5: ...d For L P gas usage 3 8 inch approved copper tubing may be used Pipe joint compounds suitable for use with L P gas should be used F The supply line shall be equipped with a shutoff valve installed within 6 ft 1 8 m of dryer in accordance with the National Fuel Gas Code ANSI Z223 1 latest edition This valve should be located in the same room as the dryer and should be in a location that allows ease...

Страница 6: ...evel adjust the legs of the dryer up or down until the dryer is level 12 Plug power supply cord into grounded outlet 13 Check dryer operation some accumulated time may be on the timer due to factory testing Pull timer set button left Operating time will accumulate per number of depressions and type of timing cam used Push START RESTART button Using a full heat cycle not the air cycle let the dryer...

Страница 7: ...lectrical requirements If codes permit and a separate ground wire is used it is recommended that a qualified electrician determine that the ground path is adequate Important Observe all governing codes and ordinances A four wire or three wire single phase 120 240 volt 60 Hz AC only electrical supply or four wire or three wire 120 208 volt if specified on the model serial rating plate is required o...

Страница 8: ...Four wire recommended method Three wire if four wire is not available 1 Disconnect the power supply 2 Remove hold down screw and terminal block cover Power supply cord Direct wire This dryer is manufactured with the cabinet ground conductor connected to the NEUTRAL center of the wiring harness at the terminal block If local codes do NOT permit this type of connection use Four wire connection instr...

Страница 9: ... the other wires to outer terminal block screws Tighten screws 6 Connect the ground wire bare of the power supply cable to the external ground conductor screw Tighten screw 9 Tighten strain relief screws 10 Insert tab of terminal block cover into slot of dryer rear panel Secure cover with hold down screw 9 Tighten strain relief screws 10 Insert tab of terminal block cover into slot of the dryer re...

Страница 10: ...utral wire 4 Loosen or remove center terminal block screw 7 Tighten strain relief screws 8 Insert tab of terminal block cover into slot of dryer rear panel Secure cover with hold down screw 6 Place the hooked ends of the other power supply cable wires under the outer terminal block screws hook facing right Squeeze hooked ends together Tighten screws 5 Place the hooked end of the neutral wire white...

Страница 11: ... separate ground wire is used it is recommended that a qualified electrician determine that the ground path is adequate 7 To exhaust dryer see Exhaust requirements Pages 3 4 Connect exhaust vent to dryer exhaust outlet and exhaust hood using 4 10 2 cm clamps Use caulking to seal exterior wall opening around exhaust hood 8 Carefully move dryer into final position Place level on top of the dryer fir...

Страница 12: ...6 cm 48 sq 24 sq The dryer must be exhausted outdoors No other fuel burning appliance may be installed in the same closet 14 35 6 cm max 1 2 5 cm 4 10 2 cm dia This dryer may be installed in a recessed area or closet For recessed area and closet installations minimum clearances can be found on the serial tag on the dryer The installation spacing is in inches and is minimum allowable Additional spa...

Отзывы: