17
DIAGNOSTIC INFORMATION
!
WARNING
ELECTRIC SHOCK HAZARD
Disconnect the electrical power before servicing any components.
Failure to do so can result in death or electrical shock.
HIGH
SIDE
85±20
135±20
180±20
PERFORMANCE DATE
*(NORMAL OPERATING CONDITIONS)
AMB
70°
90°
110°
SYSTEM PRESSURE
(PSIG)
WATTS
160±20
165±20
185±20
LOW
SIDE
0
1
2
*Normal operating conditions are viewed when
air and temperature controls are at mid-setting,
freezer section temperature is between 0°- 5°F
and unit is cycling.
NOTE: Watt and pressure readings will vary
and
are influenced by existing
condition of
the appliance, such as
iced-up evap-
orator, condition of
the condenser, de-
frost cycle, pull-
down time and customer
use.
TECUMSEH
TP1380Y
12049703
--
--
10097202
10377015
C8931604
C8946703
10530702
10428409
10442407
10654206
10884501
10624901
GENERAL COMPONENT INFORMATION
BE SURE AND USE CORRECT REPLACEMENT PARTS
120VAC
COMPONENT
COMPRESSOR
RUN WINDING
START WINDING
PTC RELAY
OVERLOAD
RUN CAPACITOR
THERMOSTAT
DEFROST TIMER MOTOR
DEFROST HEATER
BI-METAL
EVAPORATOR FAN
CONDENSER FAN
RETURN HEATER
WATTAGE
@120VAC
--
--
--
--
--
--
--
--
450
--
10.9
10
1
OHMS
RESISTANCE
--
2.6
4.35
--
--
--
--
1320
30
--
--
--
13300
SERVICE INFORMATION
1. Do not interchange the compressor suction and process stubs.
2. Refrigerant charge must be applied to high side only.
3. Ice Maker and Water Valve not original equipment on all models.
4. CAUTION:Ice Maker cycle MUST be initiated electrically. Do not try to manually start cycle.
5. Service defrost bi-metal (55°F) open.
6. Defrost timer may contain a capacitor in series with motor. Do not continuity test when checking
for failed timer motor. Instead, energize timer and listen for gear movement.
7. Part number can be found on component.