P82774 C
Sheet 1 of 5
273 Branchport Ave.
Long Branch, N.J. 07740
(800)
631-2148
Thank you for using our products.
www.wheelockinc.com
INSTALLATION INSTRUCTIONS
STROBE APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
The Strobe Appliances are UL Listed under Standard 1638 for outdoor Fire Protective Service. They are listed for outdoor use, wall
mount, with the backboxes specified in these instructions (See Mounting Option). The Strobe Appliances use a Xenon flashtube with
solid state circuitry enclosed in a rugged Lexan
lens to provide maximum visibility and reliability for effective visible signaling. All
inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel
(FACP).
NOTE:
All
CAUTIONS
and
WARNINGS
are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD
RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE STROBE APPLIANCES ARE NOT TO BE USED AS AN INDOOR VISUAL EVACUATION
SIGNAL OR FOR THE HEARING IMPAIRED.
SPECIFICATIONS:
Table 1: UL Listed Models and Ratings
Outdoor
Plate
2
Rated Input
Voltage Range
Nominal Input
Voltage
Rated Average
Current
Rated
Candela
1
Mounting
Options
WHT-12
----
12VDC
.150A
15cd
B
WHT-24
18.0-31.0VDC
24VDC
.075A
15cd
B
WH1T-12
----
12VDC
.150A
15cd
C
WH1T-24
18.0-31.0VDC
24VDC
.075A
15cd
C
WH1T-115
----
115VAC
.060A
15cd
C
WH3T-12
----
12VDC
.150A
15cd
A
WH3T-24
18.0-31.0VDC
24VDC
.075A
15cd
A
WH3T-115
----
115VAC
.060A
15cd
A
WM3T-24 18.0-31.0VDC 24VDC
.088A
117cd
A
1
At -35
°
C the following candela ratings apply: 117cd models = 78cd; 15cd models = 7.5cd
2
W in models number indicates white or clear lens. Substitute R for optional red lens (does not apply to WM models). Derate
intensity by 60% for red lens.
WARNING: ALTHOUGH UL TESTING HAS VERIFIED THAT THESE STROBES FUNCTION EVEN AT 80% OF
THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS
THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE.
THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO
THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO
YOU AND/OR OTHERS.
The UL Listed "Rated Input Voltage Range" is 18.0-31.0VDC for WHT-24, WH1T-24, WH3T-24, WM3T-24 and 12VDC for WHT-
12, WHIT-12, WH3T-12 using either filtered (DC) or unfiltered full-wave-rectified (FWR) voltage. Check the minimum and
maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to determine
the applied voltage to the strobes.
Copyright 1994, 1999 Wheelock, Inc. All rights reserved.