background image

P82774 C 

Sheet 1 of 5 

 

273 Branchport Ave. 
Long Branch, N.J.  07740 
(800) 

 

631-2148             

 

Thank you for using our products.

 

www.wheelockinc.com 

INSTALLATION INSTRUCTIONS 

STROBE APPLIANCES 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

The Strobe Appliances are UL Listed under Standard 1638 for outdoor Fire Protective Service.  They are listed for outdoor use, wall 
mount, with the backboxes specified in these instructions (See Mounting Option).  The Strobe Appliances use a Xenon flashtube with 
solid state circuitry enclosed in a rugged Lexan

 lens to provide maximum visibility and reliability for effective visible signaling.  All 

inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel 
(FACP). 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

 

WARNING:  READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE 

FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, 
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD 
RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

WARNING:  THE STROBE APPLIANCES ARE NOT TO BE USED AS AN INDOOR VISUAL EVACUATION 

SIGNAL OR FOR THE HEARING IMPAIRED. 

 

SPECIFICATIONS: 

 

Table 1:  UL Listed Models and Ratings 

Outdoor 

Plate

2

 

Rated Input 

Voltage Range 

Nominal Input 

Voltage 

Rated Average 

Current 

Rated 

  Candela

1

 

Mounting 

Options 

WHT-12 

---- 

12VDC 

.150A 

  15cd 

WHT-24 

18.0-31.0VDC 

24VDC 

.075A 

  15cd 

WH1T-12 

---- 

12VDC 

.150A 

  15cd 

WH1T-24 

18.0-31.0VDC 

24VDC 

.075A 

  15cd 

WH1T-115 

---- 

115VAC 

.060A 

  15cd 

WH3T-12 

---- 

12VDC 

.150A 

  15cd 

WH3T-24 

18.0-31.0VDC 

24VDC 

.075A 

  15cd 

WH3T-115 

---- 

115VAC 

.060A 

  15cd 

WM3T-24 18.0-31.0VDC  24VDC 

.088A 

117cd 

 

1

  At -35

°

 C the following candela ratings apply:  117cd models = 78cd;  15cd models = 7.5cd 

2

  W in models number indicates white or clear lens.  Substitute R for optional red lens (does not apply to WM models).  Derate 

intensity by 60% for red lens. 

 

WARNING:  ALTHOUGH UL TESTING HAS VERIFIED THAT THESE STROBES FUNCTION EVEN AT 80% OF 

THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS 
THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE.  
THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO 
THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO 
YOU AND/OR OTHERS. 

 

The UL Listed "Rated Input Voltage Range" is 18.0-31.0VDC for WHT-24, WH1T-24, WH3T-24, WM3T-24 and 12VDC for WHT-
12, WHIT-12, WH3T-12 using either filtered (DC) or unfiltered full-wave-rectified (FWR) voltage.  Check the minimum and 
maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to determine 
the applied voltage to the strobes. 

 

Copyright 1994, 1999 Wheelock, Inc.  All rights reserved. 