![Wheelock SAFEPATH SAPE-1AB Скачать руководство пользователя страница 77](http://html1.mh-extra.com/html/wheelock/safepath-sape-1ab/safepath-sape-1ab_operation-and-installation-manual_968644077.webp)
SAFEPATH Manual
Sheet 78 of 78
Rev. C April 1999
Message File Activation
Dry Contact
8 Dry contact inputs are provided on each digital voice module. A
Inputs
300 millisecond minimum short across input is required to activate
files. Input device must sink up to 10mA current with maximum
24VDC
drop.
Expansion Terminal
Each DV-EM module has 32 dry contact inputs (same activation as
above).
Digital Command
Through serial port, RS-232 or optional RS-485.
Outputs
Visual Notification
1 to 4 output channels optionally provided; each output is rated for
Appliance Output
2.0 Amps at 24V. Total of all output channels may not exceed 6.0 Amps.
Central Amplified
1 to 4 output channels optionally provided; each programmable for Audio
Output
either 25V, 70.7V or 100V output.
Amplified Speaker
1 to 4 output channels optionally provided; each through 15 Ohm
Audio
Output isolation
transformer. Output level is -5 dBm maximum
Amplified Speaker
1 to 4 output channels optionally provided; each output is rated for
Power Output
2.0 Amps at 24V.
Trouble
Audible
Output
is
rated for 0.100 Amps at 24VDC
Output
Status Contact
Form C contact normally energized. Contacts transfer during trouble.
Rated 0.5 Amps at 24VDC max, resistive load.
WARNING:
DO NOT EXCEED THE RATINGS OF THE STATUS CONTACT. EXCEEDING THE RATINGS MAY CAUSE
THE RELAY TO FAIL AND PREVENT A TROUBLE CONDITION FROM BEING INDICATED.
Alarm Contact
Form C contact normally de-energized. Contact transfers during alarm.
Rated 0.5 Amps at 24VDC max, resistive load.
WARNING:
DO NOT EXCEED THE RATINGS OF THE ALARM CONTACT. EXCEEDING THE RATINGS MAY CAUSE
THE RELAY TO FAIL AND PREVENT MESSAGES FROM BEING PLAYED.
Wiring Connections
Screw
Terminals
Each
terminal
accepts one conductor from #22 to #12 AWG.
Series DV-EM Port
25 pin D connector (DB25S) on bottom right of digital voice module.
RS-232 Port
25 pin D connector (DB25S) on bottom left of digital voice module.
End-of-Line Resistor
Dry Contact Inputs
10K, 1/8W Minimum, 5%
Visual Notification
Appliance Outputs
10K, 1/8W Minimum, 5%
Audio Notification
Appliance Outputs
10K, 1W Minimum, 5%
Amplified Speaker
Appliance Power Outputs 10K, 1/8W Minimum, 5%
Содержание SAFEPATH SAPE-1AB
Страница 10: ...SAFEPATH Manual Sheet 11 of 78 Rev C April 1999 Figure 1 Basic Capabilities of the SAFEPATH Panel...
Страница 19: ...SAFEPATH Manual Sheet 20 of 78 Rev C April 1999 Figure 3 Operator s Console...
Страница 24: ...SAFEPATH Manual Sheet 25 of 78 Rev C April 1999 Figure 5 DX 100 Module Illustration...
Страница 25: ...SAFEPATH Manual Sheet 26 of 78 Rev C April 1999 Figure 6 DX 200 Module Illustration...
Страница 28: ...SAFEPATH Manual Sheet 29 of 78 Rev C April 1999 Figure 7 SAFEPATH Panel Mounting...
Страница 32: ...SAFEPATH Manual Sheet 33 of 78 Rev C April 1999 Figure 8 Typical System Block Diagram...
Страница 62: ...SAFEPATH Manual Sheet 63 of 78 Rev C April 1999 Figure 30 Module Layout of the SAFEPATH Panel...
Страница 63: ...SAFEPATH Manual Sheet 64 of 78 Rev C April 1999 Figure 31 SAFEPATH Panel Block Diagram...
Страница 66: ...SAFEPATH Manual Sheet 67 of 78 Rev C April 1999 Figure 33 Supervised Audio System Common Control Module...
Страница 70: ...SAFEPATH Manual Sheet 71 of 78 Rev C April 1999 Figure 35 Self Amplified Speaker Control Signal Circuit Module...