![Wheelock SAFEPATH SAPE-1AB Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/wheelock/safepath-sape-1ab/safepath-sape-1ab_operation-and-installation-manual_968644053.webp)
SAFEPATH Manual
Sheet 54 of 78
Rev. C April 1999
Procedure E
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the BAT OPEN indicator on the SABC module is on,
a battery trouble condition has occurred. A battery trouble condition may be caused by:
1.
A fuse on the SABC module is blown.
2.
Faulty field wiring to batteries.
3.
A faulty SABC module.
Perform the following:
1.
Verify that all fuses on the SABC module are intact.
2.
Verify that the field wiring to the batteries is intact.
3.
Replace the SABC module.
Procedure F
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the AMP indicator on the SAA module is on, an
amplifier trouble condition has occurred. An amplifier trouble condition may be caused by:
1.
Faulty internal wiring between the backplane module and the digital voice module.
2.
A faulty SAA module.
3.
A faulty SADC module.
4.
A faulty backplane module.
Perform the following:
1.
Verify that the wiring between the backplane module and the digital voice module is intact.
2.
Replace the SAA.
3.
Replace the SADC module.
4.
Replace the backplane module.
Procedure G
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the SPK indicator on the SAA module is on, an audio
output wiring trouble condition has occurred. An audio output wiring trouble condition may be caused by:
1.
Missing end-of-line resistor on the audio output.
2.
The audio output field wiring is open or shorted.
3.
A fuse on the SAA module is blown.
4.
A faulty SAA module.
5.
A faulty backplane module.
Perform the following:
1.
Verify that the end-of-line resistor is properly in place.
2.
Verify that the audio output field wiring is intact.
3.
Verify that all fuses on the SAA module are intact.
4.
Replace the SAA module.
5.
Replace the backplane module.
Procedure H
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the STR indicator on the SAA module is on, a visual
notification output wiring trouble condition has occurred. A visual notification output wiring trouble condition may be caused by:
1.
Missing end-of-line resistor on the visual notification output.
2.
The visual notification output field wiring is open or shorted.
3.
A fuse on the SAA module is blown.
4.
A faulty SAA module.
5.
A faulty backplane module.
Perform the following:
1.
Verify that the end-of-line resistor is properly in place.
2.
Verify that the visual notification output field wiring is intact.
3.
Verify that all fuses on the SAA module are intact.
4.
Replace the SAA module.
5.
Replace the backplane module.
Содержание SAFEPATH SAPE-1AB
Страница 10: ...SAFEPATH Manual Sheet 11 of 78 Rev C April 1999 Figure 1 Basic Capabilities of the SAFEPATH Panel...
Страница 19: ...SAFEPATH Manual Sheet 20 of 78 Rev C April 1999 Figure 3 Operator s Console...
Страница 24: ...SAFEPATH Manual Sheet 25 of 78 Rev C April 1999 Figure 5 DX 100 Module Illustration...
Страница 25: ...SAFEPATH Manual Sheet 26 of 78 Rev C April 1999 Figure 6 DX 200 Module Illustration...
Страница 28: ...SAFEPATH Manual Sheet 29 of 78 Rev C April 1999 Figure 7 SAFEPATH Panel Mounting...
Страница 32: ...SAFEPATH Manual Sheet 33 of 78 Rev C April 1999 Figure 8 Typical System Block Diagram...
Страница 62: ...SAFEPATH Manual Sheet 63 of 78 Rev C April 1999 Figure 30 Module Layout of the SAFEPATH Panel...
Страница 63: ...SAFEPATH Manual Sheet 64 of 78 Rev C April 1999 Figure 31 SAFEPATH Panel Block Diagram...
Страница 66: ...SAFEPATH Manual Sheet 67 of 78 Rev C April 1999 Figure 33 Supervised Audio System Common Control Module...
Страница 70: ...SAFEPATH Manual Sheet 71 of 78 Rev C April 1999 Figure 35 Self Amplified Speaker Control Signal Circuit Module...