Table 5: Sound Output Level Selection
Switch Settings (SW1)
Sound Output
Level
Relative Level
(dB)
POS 4
POS 3
POS 2
A
1
+6
(typical) OFF
ON
OFF
B
1
+3
(typical) OFF
ON
ON
6
2
0
(Reference) OFF
OFF
OFF
5 -3
3
(typical) OFF
OFF
ON
4 -6
3
(typical) ON
ON
OFF
3 -9
3
(typical) ON
ON
ON
2 -12
3
(typical) ON
OFF
OFF
1 -15
3
(typical) ON
OFF
ON
NOTES
1.
These settings are not to be used in UL Listed applications
and should be used in non-UL Listed applications only when
the audio input level is not at the rated value – 0.5 V RMS for the 0.5-V mode and 25 V RMS for the 25-V mode – to
provide 3- or 6-dB compensation for line losses and/or low drive levels.
Using these settings while applying the rated audio
input to the appliance will cause excessive distortion and increased current consumption, and it is not a recommended
operating condition.
2.
This is the setting used as a reference level for the other settings in this table.
3.
These are
typical
values with respect to the reference level (Sound Output Level 6: 0 dB), and are included only to assist the
user in choosing a setting during installation.
However, use the values in Table 1, not these values, for the actual sound
output levels.
WARNING: DOUBLE CHECK SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT. IMPROPER
SETTINGS CAN DAMAGE THE UNIT OR RESULT IN A DISTORTED OUTPUT OR A dBA SOUND OUTPUT LEVEL
THAT IS BELOW CODE REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WIRING DIAGRAMS:
Figure 3:
STROBE
TO NEXT SIGNAL
OR END 0F LINE
RESISTOR
+
-
-
+
-
+
-
+
+
-
+
-
AUDIO
POWER
FROM PRECEDING
AMPLIFIER OR
SAFEPATH PANEL
A
D
-
A
D
+
G
N
D
+
2
4
S
T
-
S
T
+
Figure 4: Sync Modules/Sync Strobes Connection Diagram
+
-
END OF LINE
RESISTOR
+
-
+
-
+
-
+
-
STROBE AND
AUDIBLE #N
COMBINATION
STROBE OR
STROBE OR
COMBINATION
STROBE AND
AUDIBLE #2
STROBE OR
COMBINATION
STROBE AND
AUDIBLE #1
SYNC *
MODULES
FIRE
ALARM
CONTROL
PANEL
(FACP)
OUTPUT
INPUT
NOTE:
All wiring must be all power-limited or all non-power-limited.
*Refer to Sync Module instruction sheets SM (P83123),