![Wheelock SA-S90-24MCC-FR Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/wheelock/sa-s90-24mcc-fr/sa-s90-24mcc-fr_installation-instructions-manual_968815003.webp)
P84503 C
Sheet 3 of 8
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 2: UL Current Ratings (AMPS)
Maximum RMS Current
UL Voltage
15cd
30cd
75cd
95cd
DC 16-33.VDC 0.065
0.105
0.189
0.249
FWR 16-33.VRMS 0.110 0.170 0.280
0.375
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE
CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM
SYNC MODULES OR WHEELOCKS POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED
CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES
ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF
POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 2 to determine the highest value of “RMS Current” for an individual strobe (across the
expected operating voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents
for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the
listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For
example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup
across the output) may exhibit this characteristic.
CAUTION:
The
Speaker
Strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.
LIGHT DISTRIBUTION:
Table 3A: Horizontal Plane
Horizontal 15cd
30cd
75cd
95cd
Angle (in deg.)
UL Min.
Typ. 15cd
UL Min.
Typ. 30cd
UL Min.
Typ. 75cd
UL Min.
Typ. 95cd
0
15.0
20.5
30.0
43.3 75.0 102.6 95.0 146.0
5
13.5
20.5
27.0
43.3 67.5 102.6 85.5 146.0
10 13.5
20.1
27.0
43.0
67.5 102.0 85.5 145.0
15 13.5
20.2
27.0
42.7
67.5 102.0 85.5 145.0
20 13.5
18.8
27.0
40.0
67.5 97.1 85.5 134.1
25 13.5
16.9
27.0
35.0
67.5 85.5 85.5 121.3
30 11.3
15.3
22.5
32.7
56.3 80.0 71.3 111.6
35 11.3
14.8
22.5
31.1
56.3 74.0 71.3 106.3
40 11.3
14.1
22.5
29.0
56.3 70.6 71.3 100.7
45 11.3
12.8
22.5
25.9
56.3 62.3 71.3 90.7
50 8.3
11.3
16.5
23.3
41.3 57.1 52.3 81.2
55 6.8
11.9
13.5
23.8
33.8 57.7 42.8 84.5
60 6.0
11.3
12.0
22.3
30.0 52.2 38.0 78.1
65 5.3
10.1
10.5
20.9
26.3 48.9 33.3 69.1
70 5.3
9.7
10.5
19.8
26.3 44.7 33.3 64.7
75 4.5
12.3
9.0
25.0
22.5 57.8 28.5 81.7
80 4.5
10.6
9.0
21.9
22.5 51.3 28.5 69.4
85 3.8
5.4
7.5
12.1
18.8 28.7 23.8 37.2
90 3.8
7.6
7.5
16.6
18.8 39.8 23.8 49.7