background image

P83601 F 

Sheet 8 of 11

 

MOUNTING OPTIONS: 
 
 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used with 

each mounting option.  If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires 
and stresses from the wires could damage the product. 
 
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of 
the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room 
for easy installation and minimum stress on the product from wiring. 

 
 

  C

  A

  B

  D

FLUSH MOUNTING

 STD. SINGLE-GANG

 BACKBOX

 #6-32 X 7/8"

 SCREWS

NS MOUNTING PLATE 

(NSMP) 

NS BEAUTY PLATE (SUPPLIED) 

MAXIMUM NUMBER OF CONDUCTORS

BACKBOX 

 

                      

  DEPTH  AWG #18 AWG#16 AWG#14 AWG#12

  2-1/2"           8               4              4              4        

  3-1/8"           8               8              8              8        

NS MOUNTING PLATE 

(NSMP) 

NS MOUNTING PLATE 

(NSMP) 

NS MOUNTING PLATE 

(NSMP) 

NS BEAUTY PLATE (SUPPLIED) 

NS BEAUTY PLATE (SUPPLIED) 

NS BEAUTY PLATE (SUPPLIED) 

 #6-32 X 7/8"

 SCREWS

 #8-32 X 7/8"

 SCREWS

 #8-32 X 7/8"

 SCREWS

  4" SQ. X 1-1/2" DEEP BACKBOX

  OR 100mm X 37.5mm

  EUROPEAN BACKBOX

FLUSH OR SURFACE MOUNT

SURFACE MOUNT

FLUSH OR SURFACE MOUNTING

 DOUBLE-GANG X 2-1/4"

DEEP BACKBOX

  5" SQ. X 1-9/16" DEEP

  SHBB BACKBOX

MAXIMUM NUMBER OF CONDUCTORS

AWG #18    AWG #16    AWG #14    AWG # 12

8                  8                  8                   8

MAXIMUM NUMBER OF CONDUCTORS

AWG #18    AWG #16    AWG #14    AWG # 12

8                  8                  8                   8

MAXIMUM NUMBER OF CONDUCTORS

AWG #18    AWG #16    AWG #14    AWG # 12

8                  8                  8                   8

 

 
 

Содержание NS4-121575W*

Страница 1: ...ity for effective visible signaling The horn portion of the NS4 Appliances can be field set to provide either Continuous Horn or Code 3 Horn The sound output can be field set for High HI or Low LO dBA The NS4 Horn Strobe can also be used with a Sync Module SM or Dual Sync Module DSM to provide synchronized strobe and synchronized Code 3 signal These strobe models are designed for use with either f...

Страница 2: ... the listed voltage range 2 Anechoic dBA is measured on axis in a non reflective free field test room using fast meter response For peak dBA measured with peak meter response add 5dBA to anechoic values as shown in Table 2 Reverberant dBA is a minimum UL rating based on sound pressure measurements in a reverberant test room 3 All models are UL Listed for indoor use with a temperature range of 32oF...

Страница 3: ...DC 0 178 0 215 0 255 0 425 0 525 20 0VRMS 0 173 0 210 0 250 0 410 0 510 24 0VRMS 0 178 0 215 0 255 0 410 0 525 31 0VRMS 0 182 0 220 0 265 0 435 0 535 Voltage NS4 1215W NS4 121575W 10 5VDC 0 405 0 510 12 0VDC 0 410 0 520 15 6VDC 0 415 0 530 10 5VRMS 0 410 0 520 12 0 VRMS 0 415 0 530 15 6 VRMS 0 420 0 540 Rated Inrush Current Voltage NS4 2415W NS4 241575W NS4 2430W NS4 2475W NS4 24110W 20 0VDC 0 135...

Страница 4: ...GS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS When calculating the total average peak and inrush currents Use Table 3 and 3A to determine the highest value of...

Страница 5: ...0cd 0 15 0 24 94 30 0 46 75 0 103 110 0 149 5 13 5 24 83 27 0 46 67 5 103 99 0 149 10 13 5 24 30 27 0 46 67 5 103 99 0 137 15 13 5 24 19 27 0 45 67 5 102 99 0 120 20 13 5 24 17 27 0 41 67 5 104 99 0 110 25 13 5 21 16 27 0 48 67 5 89 99 0 129 30 13 5 23 15 27 0 40 67 5 96 99 0 114 35 9 8 22 12 19 5 45 48 8 91 71 5 119 40 6 9 13 11 13 8 39 34 3 57 50 6 109 45 5 1 9 10 10 2 24 25 5 36 37 4 66 50 4 0 ...

Страница 6: ... Showing Location of Jumper Plug JUMPER PLUGS CANDELA SELECTOR Factory setting is on High dB and Code 3 Figure 2 Jumper plug settings for High dB and Code 3 Figure 3 Jumper plug settings for Low dB and Continuous Horn SHOWN SET ON HI dB CENTER PIN IS NOT USED SHOWN SET ON CODE3 SHOWN SET ON LOW dB SHOWN SET ON CONT HORN CENTER PI N IS NOT USED Figure 4 Jumper plug settings for Low dB and Code 3 Fi...

Страница 7: ...OBE AUDIBLE When the sync module is used the audible tone will be Code 3 sound only Refer to Sync Module Installation Instruction sheets SM P83123 and DSM P83177 for additional information Audible will operate only with power applied to both strobe and audible Figure 7 1 NS4 Appliances have in out wiring terminals that accepts two 12 to 18 American Wire Gauge AWG wires at each screw terminal Strip...

Страница 8: ...nimum stress on the product from wiring C A B D FLUSH MOUNTING STD SINGLE GANG BACKBOX 6 32 X 7 8 SCREWS NS MOUNTING PLATE NSMP NS BEAUTYPLATE SUPPLIED MAXIMUMNUMBER OF CONDUCTORS BACKBOX DEPTH AWG 18 AWG 16 AWG 14 AWG 12 2 1 2 8 4 4 4 3 1 8 8 8 8 8 NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS BEAUTYPLATE SUPPLIED NS BEAUTYPLATE SUPPLIED NS BEAUTYPLATE SUPPLIED 6 32 X 7 ...

Страница 9: ...from the strobe assembly once engaged First gently insert a screwdriver into one of the slots located on the side edges of the NS Beauty Plate Second gently pull away from the wall with the inserted screwdriver to disengage the snap Third repeat the first and second steps for the second slot Finally gently lift the Beauty Plate away from the NSMP 6 Mounting hardware for each mounting option is sup...

Страница 10: ... Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precautions to assure electrical noise immunity e g audio crosstalk NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection a...

Страница 11: ...R SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUI...

Отзывы: