P83601 F
Sheet 5 of 11
LIGHT DISTRIBUTION PER UL 1971:
Table 4: Horizontal Plane
Horizontal 15cd 1575cd*
30cd
75cd
110cd
Angle (in deg.)
UL Min.
Typ. 15cd
Typ. 1575cd UL Min.
Typ. 30cd
UL Min.
Typ. 75cd
UL Min.
Typ. 110cd
0
15.0
24
94
30.0
46
75.0
103
110.0
149
5
13.5
24
93
27.0
46
67.5
103
99.0
152
10
13.5
24
88
27.0
45
67.5
104
99.0
151
15
13.5
24
87
27.0
46
67.5
100
99.0
151
20
13.5
23
85
27.0
43
67.5
101
99.0
148
25
13.5 23
80 27.0 43 67.5 98
99.0 140
30
11.3 21
75 22.5 41 56.3 94
82.5 135
35
11.3 20
71 22.5 40 56.3 89
82.5 129
40
11.3 14
62 22.5 39 56.3 83
82.5 124
45
11.3 18
52 22.5 41 56.3 81
82.5 133
50
8.3
18
35
16.5
36
41.3
77
60.5
121
55
6.8
12
32
13.5
27
33.8
60
49.5
85
60
6.0
11
34
12.0
30
30.0
59
44.0
95
65
5.3
13
27
10.5
35
26.3
71
38.5
113
70
5.3
17
19
10.5
29
26.3
73
38.5
81
75
4.5
13
11
9.0
22
22.5
53
33.0
72
80
4.5
8
9
9.0
17
22.5
35
33.0
50
85
3.8
7
10
7.5
15
18.8
30
27.5
38
90
3.8
6
10
7.5
15
18.8
30
27.5
43
Table 4A: Vertical Plane
Vertical 15cd
1575cd*
30cd
75cd
110cd
Angle (in deg.)
UL Min.
Typ. 15cd
Typ. 1575cd UL Min.
Typ. 30cd
UL Min.
Typ. 75cd
UL Min.
Typ. 110cd
0
15.0
24
94
30.0
46
75.0
103
110.0
149
5
13.5
24
83
27.0
46
67.5
103
99.0
149
10
13.5
24
30
27.0
46
67.5
103
99.0
137
15
13.5
24
19
27.0
45
67.5
102
99.0
120
20
13.5
24
17
27.0
41
67.5
104
99.0
110
25
13.5 21
16 27.0 48 67.5 89
99.0 129
30
13.5 23
15 27.0 40 67.5 96
99.0 114
35
9.8
22
12
19.5
45
48.8
91
71.5
119
40
6.9
13
11
13.8
39
34.3
57
50.6
109
45
5.1
9
10
10.2
24
25.5
36
37.4
66
50
4.0
9
9
8.1
16
20.0
33
29.7
45
55
3.3
8
9
6.6
15
16.3
31
24.2
43
60
2.7
8
9
5.4
15
13.5
31
19.8
40
65
2.4
8
9
4.8
14
12.0
31
17.6
40
70
2.3
8
10
4.5
15
11.3
31
16.5
39
75
2.0
8
10
4.0
14
10.0
31
14.3
39
80
1.8
8
9
3.6
13
9.0
27
13.2
36
85
1.8
7
9
3.6
13
9.0
27
13.2
37
90
1.8
3
9
3.6
9
9.0
12
13.2
28
* 1575W models are UL Listed for 15cd and meet 75cd on axis.
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING
PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE
LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED
VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S
ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.