WIRING INFORMATION: 

 

Figure 6. 

  Figure 7.     

 
 

OR END OF LINE

FROM PRECEDING
APPLIANCE, FACP

TO NEXT SIGNAL

+

-

RESISTOR (EOLR)

OR SYNC MODULE

 

 

When the sync module is used, the audible tone will be the 

code 3 sound only

.  Refer to Sync Module installation 

instruction sheets SM (P83123), DSM (P83177) or PS-12/24-8 
(P83862) for additional information. 

 

 

 

 

 

1) NS Appliances have in-out wiring terminals 

that accepts two #12 to 18 American Wire 
Gauge (AWG) wires at each screw terminal.  
Strip leads 3/8” inches for connection to screw 
terminals. 

2)  Break all in-out wire runs on supervised circuit 

supervision as shown in Figure 7.  The polarity 
shown in the wiring diagrams is for the 
operation of the appliances.  The polarity is 
reversed by the FACP during supervision. 

 
 
MOUNTING OPTIONS: 

 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used with 

each mounting option.  If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires 
and stresses from the wires could damage the product. 

 

Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of 
the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room 
for easy installation and minimum stress on the product from wiring. 

 

  C

  A

  B

  D

FLUSH MOUNTING

 STD. SINGLE-GANG

 BACKBOX

 #6-32 X 7/8"

 SCREWS

NS MOUNTING PLATE 

(NSMP) 

NS BEAUTY PLATE (SUPPLIED) 

MAXIMUM NUMBER OF CONDUCTORS

AWG #18 AWG#16 AWG#14 AWG#12

      4               4             4              4        

NS MOUNTING PLATE 

(NSMP) 

NS MOUNTING PLATE 

(NSMP) 

NS MOUNTING PLATE 

(NSMP) 

NS BEAUTY PLATE (SUPPLIED) 

NS BEAUTY PLATE (SUPPLIED) 

NS BEAUTY PLATE (SUPPLIED) 

 #6-32 X 7/8"

 SCREWS

 #8-32 X 7/8"

 SCREWS

 #8-32 X 7/8"

 SCREWS

  4" SQ. X 1-1/2" DEEP BACKBOX

  OR 100mm X 37.5mm

  EUROPEAN BACKBOX

FLUSH OR SURFACE MOUNT

SURFACE MOUNT

FLUSH OR SURFACE MOUNTING

MAXIMUM NUMBER OF CONDUCTORS

AWG #18 AWG#16 AWG#14 AWG#12

       4               4              4              4        

MAXIMUM NUMBER OF CONDUCTORS

AWG #18 AWG#16 AWG#14 AWG#12

       4               4             4              4        

 DOUBLE-GANG X 2-1/4"

DEEP BACKBOX

  5" SQ. X 1-9/16" DEEP

  SHBB BACKBOX

MAXIMUM NUMBER OF CONDUCTORS

AWG #18 AWG#16 AWG#14 AWG#12

       4               4              4              4        

 

 

Содержание NS-1215W

Страница 1: ... lens to provide maximum visibility and reliability for effective visible signaling Series NS Appliances can be field set for High HI or Low LO dBA sound output These strobe models are designed for use with either filtered DC VDC or unfiltered Full Wave Rectified FWR input voltage All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP NOTE...

Страница 2: ...8 83 86 87 89 91 Low 67 72 74 82 84 86 Code 3 Horn High 75 79 82 87 89 91 WARNING OPERATING THE 24 VOLT NS AUDIBLE APPLIANCES SET ON CODE 3 HORN WITH LOW dBA AT MINIMUM VOLTAGE DOES NOT MEET THE 75dBA MINIMUM UL REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION SERVICE NOTED BY IN TABLE 2 OPERATING THE 12 VOLT NS AUDIBLE APPLIANCES SET ON CODE 3 HORN WITH LOW dBA OR CONTINOUS HORN W...

Страница 3: ...10W 16 0VDC 0 181 0 265 0 482 0 675 24 0VDC 0 183 0 270 0 485 0 680 33 0VDC 0 188 0 275 0 489 0 685 16 0VRMS 0 183 0 270 0 485 0 680 24 0VRMS 0 188 0 275 0 489 0 685 33 0VRMS 0 430 0 480 0 520 0 690 Voltage NS 1215W 8 0VDC 0 460 12 0VDC 0 465 17 5VDC 0 470 8 0VRMS 0 465 12 0VRMS 0 470 17 5VRMS 0 475 Rated Inrush Current Voltage NS 2415W NS 2430W NS 2475W NS 24110W 16 0VDC 0 110 0 110 0 110 0 110 2...

Страница 4: ...LERT OCCUPANTS DURING AN EMERGENCY WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS When calculating the total average peak or inrush currents Use Table 3 and 3A to determine the highest value of Rated Average Current for an individual strobe across the expected operating voltage range of the strobe and use Table 3 to determine the highest value of Rated Inrus...

Страница 5: ...n Typ 110cd 0 15 0 24 30 0 46 75 0 103 110 0 149 5 13 5 24 27 0 46 67 5 103 99 0 149 10 13 5 24 27 0 46 67 5 103 99 0 137 15 13 5 24 27 0 45 67 5 102 99 0 120 20 13 5 24 27 0 41 67 5 104 99 0 110 25 13 5 21 27 0 48 67 5 89 99 0 129 30 13 5 23 27 0 40 67 5 96 99 0 114 35 9 8 22 19 5 45 48 8 91 71 5 119 40 6 9 13 13 8 39 34 3 57 50 6 109 45 5 1 9 10 2 24 25 5 36 37 4 66 50 4 0 9 8 1 16 20 0 33 29 7 ...

Страница 6: ...ug JUMPER PLUGS TOP PLUG NO PLUG HI LOW CODE 3 HORN Factory setting is on High dB and Code 3 Figure 2 Jumper plug settings for High dB and Code 3 Figure 3 Jumper plug settings for Low dB and Continuous Horn SHOWN SET ON HI dB CENTER PIN IS NOT USED SHOWN SET ON CODE 3 CENTER PIN IS NOT USED SHOWN SET ON CONT HORN SHOWN SET ON LOW dB Figure 4 Jumper plug settings for Low dB and Code 3 Figure 5 Jump...

Страница 7: ... backbox to accommodate the field wires and stresses from the wires could damage the product Although the limits shown for each mounting option comply with the National Electrical Code NEC Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires whenever possible to provide additional wiring room for easy installation and minimum stress on the produc...

Страница 8: ...S Beauty Plate Second gently pull away from the wall with the inserted screwdriver to disengage the snap Third repeat the first and second steps for the second slot Finally gently lift the Beauty Plate away from the NSMP 6 Mounting hardware for each mounting option is supplied 7 Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product 8 W...

Страница 9: ...system communication circuits and or audio circuits for example may require special precautions to assure immunity from electrical noise e g audio crosstalk NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential...

Страница 10: ... SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...

Отзывы: