background image

P84506 C 

Sheet 3 of 4 

WARNING:  THE SPEAKER STROBE APPLIANCE MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL BEFORE IT IS 

INSTALLED.  THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT 
SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR 
DEATH TO YOU AND/OR OTHERS. 

 

Table 3:  Speaker Voltage and Wattage Connection Chart 

Position 25V  70V 

A 8 

------ 

B 4 

------ 

C 2 

------ 

D 1 8 

E 1/2 4 
F 1/4 2 

G 1/8 1 
H ------ 

1/2 

I ------ 

1/4 

J ------ 

1/8 

           

Figure 5: 

0

1

15

75

1

30

 CANDELA

 POINTER

INSERT 

SCREWDRIVER 

 

NOTE:  

The ET80-24MCW comes pre-set at 15cd. 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.  

WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE.  AFTER CHANGING 
THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.  IMPROPER SETTING OF THE CANDELA 
SELECT SWITCH, MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

MOUNTING PROCEDURES: 

 

1.

 

The ET80-24MCW can be flush mounted to a 4” square by 2-1/8” deep backbox with a 4” square 1-1/2” extension ring (Figure A) or surface mounted to a 
surface backbox (Figure B).  Mounting hardware for each mounting option is supplied. 

2.

 

Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  Do not pass additional wires (used for other 
than the signaling appliance) through the backbox.  Such additional wires could result in insufficient wiring space for the signaling appliance.  

3.

 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the signaling appliance. 

4.

 

Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is 
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

5.

 

ET80-24MCW model has an integrated speaker mounting plate which must be oriented correctly when it is mounted to the backbox.  Turn the speaker mounting 
plate so that the arrow above the words “Horizontal Strobe” points to the top side of the speaker mounting plate. 

6.

 

To move selector switch, insert screwdriver into slot shown on the bottom side of the strobe.  The setting is indicated by a pointer and can be seen on the bottom 
side of the lens.  See Figure 5. 

7.

 

Mount the speaker mounting plate to the backbox.  Next slide the grille over the speaker mounting plate strobe and attach with (2) screws.  Tamper-resistant Pan 
Torx screws have been provided. 

 

WARNING:  THE SPEAKER STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT." 

 

WARNING:  WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING 

OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT 
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE 
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION.  FAILURE TO 
DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

The 110 candela strobe setting is Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority 
Having Jurisdiction. 

 

WARNING:  INSTALLATION OF WHEELOCK 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS SHOULD BE WALL MOUNTED AT 

LEAST 24" BELOW THE CEILING AS FOLLOWS:  (1) THE ON-AXIS (DIRECTLY IN FRONT OF LENS) LIGHT OUTPUT SHOULD BE DIRECTED 
AT THE EYE-LIDS OF THE SLEEPING PERSON, E.G. PILLOW END OF BED, BED HEAD; (2) NO PART OF THE BED SHALL BE MORE THAN 
SIXTEEN (16) FEET FROM THE STROBE NOTIFICATION APPLIANCE.  INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF 
BUILDINGS WITH SLEEPING OCCUPANTS, E.G. HOTELS AND MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE 
THE BED LOCATION TO A POSITION VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR 
DURING A FIRE EMERGENCY. 

 