CAUTION:  

Audible Horn appliances are not designed to be used on coded systems in which the applied voltage is cycled 

on and off. 

 

WARNING:  THE AUDIBLE HORN APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA 

SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED.  THIS IS DONE BY PROPERLY INSERTING A 
JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT SETTINGS WILL RESULT IN 
IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR 
DEATH TO YOU AND/OR OTHERS. 

 

SOUND OUTPUT (SPL) SETTINGS: 

 

Figure 1:  Showing Location of Jumper Plug J1 and J1. 

 

AUD

+

-

P83511

J2 J1

H

M

L

C

O

D

E

3

J2

J1

H

M

L

D

3

E

O

C

 

Factory setting is on Medium dB and Code 3. 

 

Figure 2:  Jumper Plug Settings for High, Medium, Low dB, Code 3 Horn and Continuous Horn Setting 

 

J1

HIGH

LOW

H

C
O
D
E
3

3

E

D

O

C

SETTING

HORN

SETTING

HORN

J1

J2

J2

J2

M

L

H

M

L

H

M

L

MEDIUM

SETTING

HORN

CODE 3

SETTING

HORN

CONTINUOUS

SETTING

* HORN

 

 

(Use needle nose pliers to pull and properly insert the jumper plug.) 

 

No jumper plug is needed for continuous horn setting.  However, it is recommended that the jumper plug be retained in the unit 
for future use (if needed) as shown in Figure 2. 

 

NOTE

:  The Audible Horn must be set for code 3 when used with the sync module. 

* Continuous horn operation without sync module. 

 

WIRING INFORMATION: 

 

          Figure 3: 

 Figure 4: 

 

+

-

(+)

(-)

-

+

TO NEXT APPLIANCE OR

RESISTOR (EOLR)

FROM PRECEDING APPLIANCE,
FIRE ALARM CONTROL PANEL (FACP)
OR SYNC MODULE

END OF LINE

 

 

Refer to Sync Module instruction sheets SM (P83123) DSM (P83177) and Wheelock’s Power Supplies 
for additional information. 

 

      

 

 

1.

 

AH-WP Appliances have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge (AWG) wires at each 
screw terminal.  Strip leads 3/8” inches for connection to screw terminals. 

 

2.

 

Break all in-out wire runs on supervised circuit supervision as shown in Figure 4.  The polarity shown in the wiring 
diagrams is for the operation of the appliances.  The polarity is reversed by the FACP during supervision. 

 