Dimensions

285

1120

2150

165

OUT 1-1/4ÓF

1630

IN 1-1/4ÓF

3. Operating Instructions - Shower

1. Standards and regulations 

The FAR safety showers comply with all aspects of DIN 12899-3:2009, DIN EN 15154-1:2006, 

ANSI Z358.1-2009, TRGS 526 and the BG Chemie BGI/GUV-I 850-0 guidelines. This operating 

manual serves as a supplement to the valid rules and regulations. Please take note of the DIN 

12899-3:2009, DIN EN 15154-1:2006, ANSI Z358.1-2009, TRGS 526 and the BG Chemie BGI/

GUV-I 850-0 guidelines. 

2. Operating pressure 

The FAR safety showers are designed for an operating pressure of a maximum of 10 bar  

(PN 10). The flow rate is dependent on the available water pressure as well as the cross 

section of the connecting pipes. FAR safety showers with high-performance shower head 

without integrated flow regulation have an average volume flow of at least 60 liters/minute  

at 1 bar dynamic water pressure. 

3

PRODUCT MANUAL

1800 358 101

[email protected]

www.westlab.com.au

09 972 7682

[email protected]

www.westlab.co.nz

646 568 5391

[email protected]

www.westlab.com

1 877 822 1455

[email protected]

www.westlab.com

Australia

New Zealand

United States

Canada

Содержание 664-812

Страница 1: ...1 PRODUCT MANUAL Product Manual Floor Mounted Emergency Shower Head Eye Wash Code 664 812...

Страница 2: ...Coated Surface Protection Hand Foot Operated 100 Italian Made 2 Technical Specifications Application Floor Fixed Test Pressure 9 bars air Working Pressure Max 5 bars Flow Rate 30L min at 1 bar Surfac...

Страница 3: ...uidelines 2 Operating pressure The FAR safety showers are designed for an operating pressure of a maximum of 10 bar PN 10 The flow rate is dependent on the available water pressure as well as the cros...

Страница 4: ...o be safely drained away using barriers and drain trays if necessary 3 1 Water connection The connections for the various safety showers have a to 1 thread We recommend attaching the safety shower to...

Страница 5: ...4 5 1 Models with safety eye showers combine the eye shower and body safety shower using the provided adapter 4 5 2 Models with hand held eye showers mount the bracket of the hand held eye shower at a...

Страница 6: ...must be deinstalled during this process It must be reinstalled after the rinsing process The high performance shower head can be fastened and tightened using a pin type face wrench item no BR 010 100...

Страница 7: ...the shower 9 3 Models with safety eye showers In order to start the eye shower press the big PUSH lever This locks the PUSH lever in the open position The eyewash should not make direct contact with t...

Страница 8: ...is too low Water pressure is too low supply line cross section is too small or the jet regulator is contaminated The valve does not close properly The valve seal is damaged This is NOT a fault This is...

Страница 9: ...eye shower irrespective of the existing operating pressure 2 2 Eye showers with two high performance spray heads To guarantee correct operation the flow pressure must be at least 2 bar The flow rate i...

Страница 10: ...able fixing system 3 2 5 25 table mounted hand held eye shower Install using the 25 table mounting accessories M28x80mm A hole of 30 mm diameter should be made in the table top at a suitable point The...

Страница 11: ...t possible to hold open the lids of the contaminated eyes with both hands at the same time The shower can also be removed from the bracket This allows other body parts or an injured person on the floo...

Страница 12: ...have started to leak This is generally due to dirt from the water supply which collects in front of the valve If this has happened disconnect the handheld eye shower from the supply Operate the shower...

Отзывы: