NOTE:
Range is shipped from factory with 1-3/8" dia. hole as
shown. To use either 7/8" dia. hole or 1-1/8" dia. knockouts refer
to Fig. 9.
3 & 4 - Wire electrical wall Receptacle types &
recommended mounting orientation on wall
Fig. 8
Fig. 9
Rear
Access
Cover
2b. MODELS REQUIRING POWER SUPPLY CORD KIT.
RISK OF FIRE OR ELECTRICAL SHOCK MAY OCCUR IF AN
INCORRECT SIZE RANGE CORD KIT IS USED, THE
INSTALLATION INSTRUCTIONS ARE NOT FOLLOWED OR
STRAIN RELIEF BRACKET IS DISCARDED.
This appliance may be connected by means of a power supply
cord. Only a power supply cord kit rated at 125/250 volts
minimum, and marked for use with ranges shall be used. See Fig.
10 for cord kit ampere rating information. Cord must have either
three (3) or four (4) conductors (See Fig. 8). Terminals on end of
wires must be either closed loop or open-end spade lugs with
upturned ends. Cord must have strain relief properly installed. See
Steps
4a.
for 4-Wire or
4b.
for 3-Wire connections.
3. ELECTRICAL CONNECTION TO RANGE.
The Rear Access Cover must be removed (Fig 9). To remove,
loosen center screw (one screw) and remove cover. The terminal
block will then be accessible.
Fig. 10
4A. POWER CORD CONNECTIONS
Fig. 11
Fig. 12
(
4-Wire Connection Instructions - Refer to Fig.12)
Before wiring the range review the suggested power source
location drawing in Fig. 3. If connecting to a 4-Wire electrical
system (new branch-circuit or mobile home requires 4-Wire
connection):
1.
Follow the manufacturer’s installation instructions supplied
with the strain relief and install (Also see Figs. 9, 10 & 11).
2.
Insert the end connectors for Line 1, Line 2 and Neutral and
tighten securely to the terminal block.
IMPORTANT NOTE:
DO NOT LOOSEN the factory
installed nut connections which secure the range wiring to the
terminal block. Electrical failure or loss of electrical
connection may occur if these 3 nuts are loosened or
removed.
3.
You must disconnect the ground strap.
Remove the
factory installed ground screw & plate to release the copper
ground strap from the frame of the appliance. Cut and
discard the copper ground strap & plate. KEEP the ground
screw.
4.
Connect the ground wire (Green) lead with the eyelet to the
frame of the appliance with the ground screw using the same
hole in the frame where the ground screw was originally
installed (See Fig. 12).
5.
Make sure all screws are tightened securely and replace the
rear access cover (See Fig. 9).
3
INSTALLATION INSTRUCTIONS FOR FREESTANDING ELECTRIC RANGE
Required for new and
remodeled installations
4-Wire Wall
receptacle (14-50R)
Allowed for
existing installations
3 Wire Wall
receptacle (10-50R)