
WHL-016 Rev. 4.14.16
62
Part 12 - Maintenance
A. Procedures
Periodic maintenance should be performed once a year by a
qualified service technician to assure that all the equipment
is operating safely and efficiently. The owner should make
necessary arrangements with a qualified heating contractor
for periodic maintenance of the boiler. The installer must also
inform the owner that a lack of proper care and maintenance of
the boiler may result in a hazardous condition.
BEFORE EACH HEATING SEASON a trained and qualified
service technician should perform the inspections as per the
boiler inspection and maintenance schedule in this manual.
Failure to do so could result in death or serious injury.
The combustion chamber insulation in this product contains
ceramic fiber material. Ceramic fibers can be converted
to cristobalite in very high temperature applications. The
International Agency for Research on Cancer (IARC) has
concluded, “Crystalline silica inhaled in the form of quartz
or cristobalite from occupational sources is carcinogenic to
humans (Group 1).”
•
Avoid breathing dust and contact with skin and eyes.
•
Use a NIOSH certified dust respirator (N95). This type
of respirator is based on the OSHA requirements for
cristobalite at the time this document was written. Other
types of respirators may be needed depending on job
site conditions. Current NIOSH recommendations can
be found on the NIOSH website: http://www.cdc.gov/
niosh/homepage.html. NIOSH approved respirators,
manufacturers, and phone numbers are also listed on this
website.
•
Wear long-sleeved, loose fitting clothing, gloves, and eye
protection.
•
Apply enough water to the combustion chamber lining to
prevent dust.
•
Wash potentially contaminated clothes separately from
other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
•
Eye: Irrigate immediately.
•
Breathing: Fresh air.
B. Combustion Chamber Coil Cleaning Instructions
*Before beginning this procedure, have on hand the following
items:
•
a nylon, stainless steel, or brass brush (not steel)
•
an FDA approved liquid lime scale remover in a spray bottle
•
gloves and eye protection
1. Shut down the boiler by using the following steps:
a. Turn off power to the boiler. Turn thermostats down to
ensure there is no call for heat, or disconnect thermostat
connections from terminals. Close the gas valve inside the
boiler cabinet. Wait for the boiler to be cool to the touch.
b. Disconnect the wires plugged into the fan, spark electrode,
flame rod, and gas valve.
c. Disconnect the flexible gas lines from the venture attached
to the fan.
d. Loosen the nuts that hold the burner plate to the heat
exchanger.
e. Remove the combustion assembly.
2. Spray water or solution into the combustion assembly and
monitor the flow through the combustion system. Liquid
should flow freely through each tube. If there is an obstruction,
increase the flow on the tube to force blockage out.
3. Once complete, reinstall the combustion assembly with
gaskets and secure nuts. Tighten properly.
a. Reconnect all wire and piping connections. Once
connected, apply power and disconnect the wire harness
with the white-blue-red-black wires to run fan and dry
combustion assembly. Let fan run for five minutes. When
finished, reconnect harness to the fan.
b. Connect the thermostat wires to the field connection
board, or turn up thermostat to fire the combustion
system. Check for leaks in the combustion system. Observe
operation for 5 to 10 minutes.
If boiler is operating properly, condensate is flowing normally,
and no gas leaks are detected, combustion coil cleaning is
complete.
Do not use solvents to clean any of the burner components.
The components could be damaged, resulting in unreliable or
unsafe boiler operation, substantial property damage, severe
personal injury, or death.
Outdoor Sensor
(7250P-319)
Supply Temperature Sensor
(7250P-324)
Boiler Sensor
(7250P-667)
Indirect Sensor
(7350P-325)
Outside
Temperature
(
o
F)
Resistance
(ohms)
High / Low
Temp Sensor
Temp. (
o
F)
Resistance (Ohms)
-22
171800
32
32550
-13
129800
41
25340
-4
98930
50
19870
5
76020
59
15700
14
58880
68
12490
23
45950
77
10000
32
36130
86
8059
41
28600
95
6535
50
22800
104
5330
59
18300
113
4372
68
14770
122
3605
77
12000
131
2989
86
9804
140
2490
95
8054
149
2084
104
6652
158
1753
113
5522
167
1481
176
1256
185
1070
194
915
202
786
212
667
Table 27 - Sensor Temperature Resistance
Содержание WBC 399
Страница 14: ...WHL 016 Rev 4 14 16 14 Figure 6 Boiler Dimensions NOTE All Dimensions Are Approximate 055 080 ...
Страница 21: ...WHL 016 Rev 4 14 16 21 Figure 9 Piping Symbol Legend ...
Страница 42: ...WHL 016 Rev 4 14 16 42 Figure 33 Internal Connection Diagram ...
Страница 65: ...WHL 016 Rev 4 14 16 65 Figure 37 Combustion System Replacement Parts 55 110kBTU Models ...
Страница 67: ...WHL 016 Rev 4 14 16 67 Figure 39 Combustion System Replacement Parts 155 399kBTU Models ...
Страница 75: ...WHL 016 Rev 4 14 16 75 Maintenance Notes ...