WHL-016 Rev. 4.14.16
50
D. Programming Boiler Settings
Boiler Setting Program Access
Note: Programming the boiler control is not possible when the
boiler is firing. Make sure any input which can create a demand
on the boiler, such as the tank thermostat, is turned off, so the
boiler will remain idle to allow programming.
Boiler Setting Program Navigation
Once the code is confirmed, the user can start to set the
Boiler
Settings
. Use the arrow keys on the display to navigate through
the
Boiler Settings
. A blinking setting indicates the setting can
be changed. To change a setting, press
ENTER
. Boiler settings
can be increased by pressing
^
and decreased by pressing
v
on
the display. When done, press
ENTER
. The setting will stop
blinking and the user can move on to next setting. Press
RESET
to exit programming and store settings. Listed below are the
boiler settings that can be programmed into the control.
Screen
Description
ENTER MENU CODE
000
To access the boiler setting program,
press and hold
ENTER
for 4 seconds
until the display shows the screen at
left.
ENTER MENU CODE
600
Use the arrow keys to log in the
Boiler
Menu Access Code - 600
. Press
ENTER
to confirm the code and access the
Boiler Setting Program
navigation
menu.
Table 14 - Boiler Setting Access
Screen
Description
CENTRAL HEAT
180
o
F
Allows the user to adjust the boiler
set point from 50F to 190
o
F (Factory
Default 180
o
F).
CENTRAL DIFF SET
30
o
F
Adjusts the boiler differential set point
from 5
o
F to 30
o
F (Factory Default
30
o
F).
DHW SETPOINT
119
o
F
Adjusts the indirect tank set point from
70
o
F to 185
o
F (Factory Default 119
o
F).
DHW DIFF SETPOINT
7
o
F
Adjusts the DHW differential set point
from 1
o
F to 30
o
F (Factory Default 7
o
F).
TEMP DISPLAY C OR F
o
F
Adjusts
the
temperature
measurement in F = Fahrenheit to
C = Celsius (Default is Fahrenheit).
Table 15 - Boiler Setting Program Navigation
Clock Settings
(
NOTE:
The clock will reset if the boiler is powered off for more
than a week.)
Screen
Description
CLOCK MODE (12/24)
08/28/2009 Fr 9:42A
Changes the clock from 12 hour
mode (8:45 PM) to 24 hour mode
(20:45). To change to 24 hour mode,
press
ENTER
. The letter (A or P)
after the time will blink. Press the
up or down arrow key once and the
letter will disappear. Press
ENTER
to
save the new setting.
CLOCK HOUR
08/28/2009 Fr 10:01A
Allows the user to adjust the hour
setting.
CLOCK MINUTE
08/28/2009 Fr 10:01A
Adjusts the minute setting.
CLOCK DAY OF WEEK
08/28/2009 Fr 10:01A
Adjusts the day of the week.
CLOCK DATE MODE
08/28/2009 Fr 10:01A
Allows the user to switch to
European date format (2009/08/28)
from US format (08/28/2009).
CLOCK YEAR
08/28/2009 Fr 10:01A
Adjusts the year setting.
CLOCK MONTH
08/28/2009 Fr 10:01A
Adjusts the month setting.
CLOCK DATE
08/28/2009 Fr 10:01A
The clock is set.
Table 16 - Clock Setting Screens
NOTE:
The internal clock does not adjust for daylight savings
time and requires manual adjustment.
E. Programming the System Setting
System Setting Program Access
Note: Programming the boiler control is not possible when
the boiler is firing. Make sure any input which can create a
demand on the boiler, such as the tank thermostat, is turned
off, so the boiler will remain idle to allow programming.
Screen
Description
ENTER MENU CODE
000
To access the boiler setting program,
press and hold
ENTER
for 4 seconds
until the display shows the screen at
left.
ENTER MENU CODE
925
Use the arrow keys to log in the
Boiler Menu Access Code - 925
.
Press
ENTER
to confirm the code
and access the
System Setting
Program
navigation menu.
Table 17 - System Setting Access
F. System Setting Program Navigation
Once the
System Menu Access Code
is confirmed, the user can
begin to set the system setting menu. Use the
< >
keys on the
display to navigate through the System Settings. To change
a setting, press
ENTER
. System settings can be
increased
by
pressing
^
and
decreased
by pressing
v
on the display. When
done, press
ENTER
. The setting will stop blinking and you can
move on to next setting. Press
RESET
to exit programming
and store settings. Listed below are the boiler settings that
can be programmed into the control.
Screen
Description
Function 1
Factory Program Mode
MODE
INDIRECT 1
This indicates that the control is
configured correctly. Do not change
this setting.
Function 3
DHW Tank Max Temp
DHW TANK MAX TEMP
180
o
F 3
This is the maximum temperature
that can be selected in boiler
settings for the DHW indirect tank.
Factory Default is 180
o
F. (Range:
95
o
F to 180
o
F)
Содержание WBC 399
Страница 14: ...WHL 016 Rev 4 14 16 14 Figure 6 Boiler Dimensions NOTE All Dimensions Are Approximate 055 080 ...
Страница 21: ...WHL 016 Rev 4 14 16 21 Figure 9 Piping Symbol Legend ...
Страница 42: ...WHL 016 Rev 4 14 16 42 Figure 33 Internal Connection Diagram ...
Страница 65: ...WHL 016 Rev 4 14 16 65 Figure 37 Combustion System Replacement Parts 55 110kBTU Models ...
Страница 67: ...WHL 016 Rev 4 14 16 67 Figure 39 Combustion System Replacement Parts 155 399kBTU Models ...
Страница 75: ...WHL 016 Rev 4 14 16 75 Maintenance Notes ...