4-32
Set the minimum frequency reference. Maximum output frequency depends on motor selection. Motor 1:
Maximum frequency is set by parameter 01-02.
Notes:
- When 00-13 and the command frequency are both set to 0.00, and RUN is pressed
”
Stp
o” is displayed.
- When Frequency command is higher than value in 00-13 inverter output will ramp up from 0.00 to the
command frequency.
- When 00-
13> 0, and the frequency command value ≤ 00-13, inverter output will ramp up from preset to the
lower limit frequency.
Frequency
Reference
Output
Frequency
650 Hz
00-12
00-13
650 Hz
Figure 4.3.5 Frequency reference upper and lower limits
00-14
Acceleration Time 1
Range
【
0.1~3600.0
】
Sec
00-15
Deceleration Time 1
Range
【
0.1~3600.0
】
Sec
00-16
Acceleration Time 2
Range
【
0.1~3600.0
】
Sec
00-17
Deceleration Time 2
Range
【
0.1~3600.0
】
Sec
Notes:
- Acceleration time is the time required to accelerate from 0 to 100% of maximum output frequency.
- Deceleration time is the time required to decelerate from 100 to 0% of maximum output frequency.
- Maximum frequency is set by parameter 01-02.
- If parameter 01-00=18, Maximum output frequency is set by parameter 01-02.
- If parameter 01-
00≠18, Maximum output frequency = 50.00 or 60.00 depending on initialization mode.
Actual acceleration and deceleration time is calculated as follows:
(00-15)x(set frequency - the minimum starting frequency)
Actual acceleration time=
(00-14)x(set frequency - the minimum starting frequency)
Maximum output frequency
Actual deceleration time=
Maximum output frequency