MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
________________________________________________________________
TECO – Westinghouse Motor Company
10
PRGM
DRIVE
DSPL
EDIT
ENTER
Sn – 01 -
key twice
Inverter Capacity
Flashing
To set the parameter Sn-24 = 0
Keypad Steps
Resulting Display
1 - Press the
2 - Press the
3 - Press the
key until display shows
4 - Press the
key
(VIN, 0 – 10 VDC)
key
An – 01 -
Freq. Cmd. 1
Sn – 24
Sn – 24 =
1
CMD. AIN
EDIT
ENTER
key to
save
.
5 - Press the
key
6 - Press the
Entry Accepted
2 Seconds
PRGM
DRIVE
7 - Press the
key to return to the main display.
Flashing
Sn – 24 =
0
CMD. VIN
Flashing
Sn – 24 =
0
External Input
CMD. VIN
Step 9
– Select Feedback Engineering Units (P1-01) and Scaling (P1-02)
•
Initially the display will read
output frequency
in
(Hz)
as the
factory default
and is set by
parameter
(Cn-28=0).
If
(Cn-28)
is changed to (
=1),
then the display will read out in
(%).
The
setting of
(Cn-28)
is only
valid
if
(P1-01=0),
which is the
factory default
. Other engineering units
may be selected by parameter setting
(P1-01)
as
described on the following page.
•
In this step, the feedback engineering units that the system is controlling such as
CPM
in fan
applications or
PSI
in the case of pumps can be selected by parameter
(P1-01)
.
(See Appendix
A for additional selections)
. The
maximum
value that the engineering units will be in any given
application is set by parameter
(P1-02)
. These selections will now be displayed on the digital
operator.
Example: A pump application that has a feeedback transducer with a maximum value of
200 PSI i.e 200 PSI = 20mA or 10 Vdc, can be set as shown next.