IQ DATA PLUS I I
T D 17271 A
Table 6.C
IQ DATA PLUS II INSTALLATION RECORD SHEET: SW2
Setting
Description
DIP
Slide
ON/OFF
Switch
Switch
Combinations
1
-
Action on overvoltage
=
__
2
-
(Do nothing/trip/alarm/trip and alarm) Refer to Table 6. D
3
-
Action on undervoltage
=
__
4
-
(Do nothing/trip/alarm/trip and alarm) Refer to Table 6. E
SW2
5
-
Action on phase loss/reversal
=
__
6
-
(Do nothing/trip/alarm/trip and alarm) Refer to Table 6. F
7
-
Action on phase unbalance
=
__
8
-
(Do
6.1 .6 Overvoltage Detection Response
-
Should an over
voltage condition be detected, the IQ Data Plus
II
can control
the internal Trip and Alarm Relays in 4 ways:
•
Activate trip relay
•
Activate alarm relay
•
Activate both trip and alarm relays
•
Activate neither trip and alarm relays
Switch
SW2, Nos. 1 and 2
determine the response of the unit,
as listed in Table 6.D.
Table 6.D
OVERVOLTAGE DETECTION RESPONSE
Response
SW2
Switch Settings
of Relay(s)
1
2
Alarm only
ON
OFF
Trip only
OFF
ON
Alarm and trip(1>
OFF
OFF
No alarm or trip
ON
ON
(1) Relays energize or de-energize simultaneously
Note also that the Switch
SW1 , No. 7
determines whether the
response is instantaneous or a selectable time interval, as
described in Paragraph 6.1.4. Switch
SW6, Nos. 5, 6, 7
deter
mine the time interval, in seconds, as described in Paragraph
6.1.23. Switch
SW3, No. 8
disables or enables all of the over
voltage and undervoltage protective capabilities, as described
in Paragraph 6.1 .12.
nothing/trip/alarm/trip and alarm) Refer to Table 6.G
32
6.1 .7 Undervoltage Detection Response
-
Should an
undervoltage condition be detected, the IQ Data Plus II can
control the internal Trip and Alarm Relays in 4 ways:
•
Activate trip relay
•
Activate alarm relay
•
Activate both trip and alarm relays
•
Activate neither trip and alarm relays
Switch
SW2, Nos. 3 and 4
determine the response of the unit,
as listed in Table 6.E.
Table 6.E
UNDERVOLTAGE DETECTION RESPONSE
Response
SW2
Switch Settings
of Relay(s)
3
4
Alarm only
ON
OFF
Trip only
OFF
ON
Alarm and trip(1l
OFF
OFF
No alarm or trip
ON
ON
(1) Relays energize or de-energize simultaneously
Note also that Switch
SW1 , No. 7
determines whether or not
there is a time interval, as described in Paragraph 6.1.4. Switch
SW6, Nos. 5, 6, 7
determine the time interval, in seconds,
as described in Paragraph 6.1 .23. Switch
SW3, No. 8
disa
bles or enables all of the overvoltage and undervoltage pro
tective capabilities, as described in Paragraph 6.1 .12.