background image

CIRCUIT  BREAKER 

STATIONARY  CORE 

MOVING  CORE 

CALIBRATION  SCREW 

FIG. 

13. 

Instantaneous  Overload  Trip 

Drop tank and examine the contacts. Remove any 

slight  burns  with  a  file.  Replace  contacts  when 
burns  penetrate  more  than 

inch.  On  the  Type 

F-11 breaker, burning will be on the top of the moving 

contact and on the flared portion of the finger.  Con­
tacts  need  be replaced  only when burned  so  badly 
as  to  cause  possible  stubbing  before  the  next  in­
spection. 

Give  the  moving  contacts  a  light  rubbing  with 

fine  sand  paper  (not  emery  cloth).  Place  the  sand 
paper  over  moving  contact  with  the  sand  side  out 
and  close  the  breaker three or  four  times. 

Check  the  insulating  quality  of  the  oil.  If  it  tests 

below  17  kv  in  a  standard  test  cup  replace  it. 

When  replacing  oil  be  sure  to  clean  out  the  tank 
before  refilling.  When  a  portable  test  set  is  not 
available  it  is  common  practice  to  replace  the  oil 
with  new  oil  and  then  take  the  original  oil  to  the 
test  set,  filtering  if  necessary  before  re-using.  Note 
oil need not be replaced just because it is darkened 
by suspended  carbon.  Depend  on  the  test  cup  test. 

Check  the  tank  liners  to  see  that  they  are  not 

burned  so  deeply  that  there  is  danger  of  burning 
through  before  the next  inspection. 

When  replacing  the  tank  be  sure  it  is  centered 

and draw  up all bolts evenly and tightly. 

ATTACHMENTS 

The instantaneous overload  trip shown in Fig. 

13 

consists  of  trip  coil  and  trip  details  to  assemble  in 

the  coverplate.  The  distance  between  the  moving 
and  stationary  cores  can  be  varied  as  indicated  by 
the  calibration marking  for tripping  between  5  and 
9  amperes  in  the  trip  coil.  By  using  current  trans­

formers of suitable ratio tripping can be accomplish­
ed  at  any  desired  primary  current.  In  assemblying 
be  sure  that  the  wedges  are  put  in  below  the coils. 

Also  check  to  see  that  the trigger  is  released  when 
the  moving  tripping  core  is  raised  slowly  mechan­

ically to within 

inch of its total  travel.  Also check 

to  see  that  tripping  occurs  if  moving  core  is  raised 
mechanically  until  trip  rod  touches  trigger  and  5 
amperes  applied suddenly to  coil. 

The  shunt  trip  attachment  for  tripping  from  a 

separate  source  of  power  as  shown  in  Fig.  14  is 

essentially  a  non  adjustable  overload  trip.  Tripping 
should  occur  if  moving  core  is  raised  slowly  the 
same  as  on  the  overload  trip.  The  coil  should  pick 
up  and  trip  the  breaker  if  60%  voltage  is  applied. 

If moving  core  is raised to  bring  trip  rod in contact 

with  trigger,  tripping  should  occur 

if 

full  voltage 

is  applied  to coil.  If  tripping  is  actuated  by  a  relay 
an  auxiliary  switch  is  to  be  used  to  interrupt  coil 

circuit  to  save  relay  contacts. 

Time  delay  overload  trip  as  shown  in  Fig.  15  is 

similar  to  the  instantaneous  trip  with  a  dash  pot 
added  to  the  moving  core  to  hold  it  back.  The time 

delay  can  be  changed  by  rotating  the  partial  disk 
on the lower end of the trip rod so as  to change the 
number of the holes uncovered. A loose washer pro­

vides for  quick resetting.  Current  calibration  is  ob­

tained  by  screwing  pot  into  or  out  of  the  dashpot 
cover. 

STATIONARY 

CORE 

TUBE 

MOVING  CORE 

RIVET 

FIG. 

14. 

Shunt Trip 

13 

www 

. ElectricalPartManuals 

. com 

Содержание F-11

Страница 1: ...CTIONS OIL CIRCUIT BREAKER Types F 11 and F 22 WESTINGHOUSE ELECTRIC CORPORATION EAST PITTSBURGH PLANT SUPERSEDES 1 8 5229 L SWITCHGEAR DIVISION EAST PITTSBURGH PA DECEMBER 1954 Rep 11 57 Printed In U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...ing Assembly Panel Frame Mounting Assembly Remote Control Assembly Pipe Frame Mounting Assembly Bell Crank Assembly Single Handle Coverplate Double Handle Coverplate Instantaneous Overload Trip Shunt Trip Inverse Time Delay Trip Inverse Time Delay Tripping Curves Hand Retrieve Undervoltage Trip Automatic Retrieve Undervoltage Trip Auxiliary Switch Bell Alarm Switch Double Throw Interlock Sequence ...

Страница 3: ...ts are as listed Keep the papers MAIN I at least until installation is complete Correspond ence will be expedited if the Westinghouse order number the style number or other identification marked on the part or assembly under question and a description are included in the first letter If possible refer to the part or parts by the names given in this book together with the figure number where it app...

Страница 4: ... hand then proceed in approximately the following se quence 1 Place the bell alarm Fig 19 or auxiliary switch Fig 18 if they are supplied in the slot in the coverplate Z Place trip coils in coverplate and assemble trip attachments by inserting in holes in bottom of FIG 2 F 11 Double Throw Breaker Unit 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 5: ... in back of switchboard assemble with coverplate See Fig 6 CROSSBAR MAIN CHECKNUT CONTACT CLAMP Note several of the bolts fasten both assemblies Make sure breaker unit is level with studs vertical 6 If breaker unit and coverplate are to be mount ed on a pipe mounting bracket as in Fig 9 proceed as per 3 4 5 above the pipe bracket is just a cast iron switchboard to be supported on pipes 7 If breake...

Страница 6: ... end to lock adjustment when complete 9 Connect power circuit Be sure conductors of adequate cross section are used to carry the 6 expected load in the circuit without overheating Be sure all surfaces are clean before bolting to gether A light coat of linseed oil particularly on threaded studs will help make up a tight low resistance joint and will make breaking the joint easier Be careful when bo...

Страница 7: ... are at the proper closed position with the toggle stop in the linkage in con tact A wood screw prevents rotation In replacing rods be sure there are no burrs in the threaded holes and drill a hole in the wood rod to start the locking screw Check operation when the breaker is closed suddenly and when trigger is released with breaker in the closed position Check to see that moving contacts enter ap...

Страница 8: ...MENT 8 FOR 2 POLE BREAKER OMIT MIDDLE P OLE FOR 4 POLE BREAKER UNDER VOLTAGE RELEASE t ____ _ BREAKER UNIT FIG 6 Switchboard Mounting Assembly COVER PLATE w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 9: ... that main copper connections are tight and taped according to standard practice Check to see that tank is filled to proper level with oil that has been checked to be up to standard New oil should check 22 kv or better in standard test cup Be sure dash pot of time delay trip is filled with the special oil provided 9 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 10: ...r I I I I 1 I I I I FOR 2 POLE BREAKER OMIT MIDDLE POLE FOR 4 POLE BREAKER BRACKET UNIT clean that all cotter pins are in place and no bolts loose See that no levers or links are worn so much at fulcrums as to interfere with operation of breaker UNDER VOLTAGE RELEASE AUXILIARY SWITCH COVER PLATE BELL ALARM SWITCH FIG B Remote Control Assembly 10 w w w E l e c t r i c a l P a r t M a n u a l s c o ...

Страница 11: ...MIT MIDDLE POLE l Oi C JO ro r __ FOR A POLE BREAKER UNDER VOLTAGE RELEASE PLATE AUXILIARY SWITCH BREAKER UNIT FIG 9 Pipe Frame Mounting Assembly STOP ROD ROD END BELL CRANK FIG 10 Bell Crank Assembly r G a 1 0 0 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 12: ...MAINTENANCE 12 SIGNAL SWITCH FIG 11 Single Handle Coverplate RUNNING HANDLE FIG 12 Double Handle Coverplate AUTOMATIC UNDERVOLTAGE _ f I w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 13: ...e between the moving and stationary cores can be varied as indicated by the calibration marking for tripping between 5 and 9 amperes in the trip coil By using current trans formers of suitable ratio tripping can be accomplish ed at any desired primary current In assemblying be sure that the wedges are put in below the coils Also check to see that the trigger is released when the moving tripping co...

Страница 14: ...CL LOW TEMP OIL 1 MINIMUM TIME DELAY 2 50 TIME DELAY 3 MAX I MUM TIME DELAY TEMP 30 C 40 70 100 CURRENT AMPERES 800 1400 2000 CURRENT PER CENT FIG 16 Inverse Time Delay Tripping Curves MAGNET CIRCUIT TRIPPING SPRING ARMATURE SHAFT RETRIEVING HANDLE FIG 17 Hand Retrieve Undervoltage Trip w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 15: ...ise direction as far as it will go the application of 80 control voltage will hold armature Check to see that with handle released HINGE JAW FIG 18 Auxiliary Switch MOUNT I NG SCREW BLADE slowly after removal of voltage the trigger of cover plate is released Check to see that armature will drop and trip breaker when voltage is reduced to approximately 50 of normal Adjustment is pro vided to vary p...

Страница 16: ...witch from one position to the other Check from time to time to see INTERLOCK PIN BRACKET SPRING TRIP LEVER I that the contacts are clean and that the connections are tight The mechanical interlock shown in Fig 20 con sists of a bar and centralizing springs so arranged that it is possible to close but one of two levers at a time This may be used on two single handle coverplates on various center l...

Страница 17: ... OIL CIRCUIT BREAKER RUNNING HANDLE OPEN RUNNING HANDLE OPEN RUNN I NG HANDLE CLOSED r _ STARTING HANDLE OPEN STARTING STAR TING HANDLE OPEN FIG 21 Sequence Interlock 17 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ... swings towards the panel As the starting lever re turns to the open position the pin strikes the unlock 18 ing surface of the interlocking lever swinging it back away from the panel This unlocks the running handle which can be moved to the closed position if done promptly before the interlocking lever swings back into the locking position If the running handle is moved to the closed position the ...

Страница 19: ... HEX STL BOLT 3 8 16 X 3 IN HEX STL BOLT 3 8 16 x 3 1 4 HEX STL BOLT 3 8 16 x 3 1 2 HEX STL BOLT 3 8 16 HEX STL NUT 3 8 STO STL WASHER 3 8 X WIDE STL WASHER 3 8 STL LOCKWASHER f G l J T VI e co 0 n 0 o r to 0 0 0 0 X i 0 j J w c o 0 w 2f rt c v v r _ Ul wo _l ll l r J _l t tQrlrh _ JP l J L______ _ GROUP NUMBER 11213141516171819 1 o I 1 11211311411 5116117118 I f I I I I I I 5 I I I I I I I I 4 I ...

Страница 20: ... I I w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: