DE•ION AIR CIRCUIT BREAKER
C ONTROL RELAY
The control relay (Figure
1 1 )
mounts di
rectly under the auxiliary switch.
It is a
single-coil, mechanical tripping device with
the coil suitable for continuous duty.
The
operation sequence is outlined in Figure
2,
Page 9.
The contacts should normally last
the lift of the breaker, but are replaceable
if necessary.
The relay trip pin and relay toggle release
are designed so that the relay trips at approx
imately the same ,time as the breaker latches.
The relay is not adjustable.
SHUNT TRIP ATTACHMENT
The shunt trip (Figure
12)
mounts on top
of the p latform immediately to the right of
I
I
I
I
I
I
0
I
I
the operating mechanism. It is non-adjustable
and is intended for intermittent duty only.
The shunt trip circuit must always be open by
an auxiliary switch contact.
Inspecti on
With the breaker in the open position,
m anually p ull t he shunt trip moving core
against the stationary core and manually at
tempt to close the breaker. The breaker should
be trip free.
The trip rod of the shunt trip should have
approximately
7/32
inch clearance to the trip
rod clip.
Maintenance
Check for loose bolts and faulty coil.
I
0
I
I
I
I
I
I
I
COIL
MOVING
CORE
NON-
MA.GNETlC
WASHER
APPROX.
FIG. 12- SHUNT TRIP ATTACHMENT -CONSTRUCTION DETAILS