Westfire WF15 Скачать руководство пользователя страница 5

WESTFIRE · WF

15

 · WF

16

 · WF

20

8

WESTFIRE · WF

15

 · WF

16

 · WF

20

9

A single wall metal fl uepipe is suitable for connecting the stove to the chimney but is not suitable for using for 
the complete chimney. The chimney and connecting fl uepipe must have a minimum diameter of 150 mm and its 
dimension should be not less than the size of the outlet socket of the stove.

Any bend in the chimney or connecting fl uepipe should not exceed 45°. 90° bends should not be used. 

If it is found that there is excessive draught in the chimney then either an adjustable fl ue damper or alternatively 
a draught stabiliser should be fi tted. The adjustable fl ue damper should not close off the fl ue entirely but should 
in its closed position leave a minimum continuous opening free area of at least 20 % of the total cross sectional 
area of the fl ue or fl uepipe.

Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and 
connecting fl ue pipe

Distance to Combustible materials
Combustible materials should not be located where the heat dissipating through the walls of fi replaces or fl ues 
could ignite it. Therefore when installing the stove in the presence of combustible materials due account must be 
taken of the guidance on the separation of combustible material given in Building Regulations Approved Docu-
ment J and also in these stove instructions.

Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not inde-
pendently supported. 

The Westfi re UNIQ 15, 16, 20 wood stove has been tested and is suitable to be installed on a 12mm non combus-
tible plate such as Westfi re 12mm glass plates or 20mm slate plates. Installation of all hearths should comply in 
size and construction so that it is in accordance with the provisions of the current Building Regulations Approved 
Document J.

The clearance distances to combustible material beneath, surrounding or upon the hearth and walls adjacent to 
the hearth should comply with the guidance on the separation of combustible material given in Building Regula-
tions Approved Document J and also in these stove instructions.

If the stove is to be installed on a wooden fl oor, it must be covered with a non-combustible material at least 
12mm thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the 
stove and 15 cm to each side measuring from the door of the combustion chamber.

Combustion air supply
In order for the stove to perform effi ciently and safely there should be an adequate air supply into the room in 
which the stove is installed to provide combustion air. This is particularly necessary if the room is double-glazed 
or a fl ue draught stabiliser is operating in the same room as the appliance. The provision of air supply to the 
stove must be in accordance with current Building Regulations Approved Document J. An opening window is not 
appropriate for this purpose. Air inlets must be positioned in such a way that they cannot be blocked. An air inlet 
may be a vent (the vent must be open and the capacity of the vent suffi cient when the stove is lit) or a fresh air 
system linked to the stove.

The UNIQ 15, 16 & 20 are available with a closed air supply collar (additional item) this enables the stove to take 
combustion directly from outside with 100mm pipe from the stove. 

UK

UNIQ 15,16,20 

Distance to combustible materials rear

150 mm

Distance to combustible materials side

350 mm

Distances to fl ammable materials/furnitures

750 mm

There are no European rules regarding the minimum distance to non-fl ammable walls, Westfi re recommend leav-
ing a gap of at least 10 cm behind and to sides of stove.

Soapstone base and top Plates for the UNIQ 16
When installing a UNIQ 16 or 20 with Soapstone top plates remove standard louvre grill top plate from stove.
Place soapstone panels directly on top of stove and fi t new rear grill to rear. If top fl ue exit is not used a cover 
plate is supplied on the stove to cover fl ue area.

When installing a Uniq 16 or 20 with a base soapstone a 12mm fl oor plate or construction hearth is still be 
installed in accordance with document J regulations.

UNIQ 15,16,& 20
 

Westfi re Insulated chambers
The Westfi re UNIQ 15, 16, 20 wood burning stove is lined with heat defl ection panels and baffl es, these panels 
are designed to ensure the maximum effi ciency and are an integral part of the clean burn process of the stove. 
These baffl es should not be removed apart from for cleaning the stove. Any defective panels should be replaced.

Connection to chimney
Westfi re UNIQ 15,16,20 wood stove has both rear and top fl ue gas connector that allows connection to either a 
masonry chimney or a prefabricated factory made insulated metal chimney in accordance with the instructions for 
“Connection to chimney” given in the instruction booklet.

Commissioning and handover
Ensure loose parts are fi tted in accordance with the instructions for “Fitting the loose parts” given in the instruc-
tion booklet.

UNIQ 16 & 20 soapstone plates

UNIQ 16

UNIQ 20

Height with 10cm plate

1160 mm

1400 mm

Height with 20cm plate

1260 mm

1500 mm

Height with 30cm plate

1360 mm

1600 mm

Base soapstone

60 mm

60 mm

UK

Top fl ue exit 150 mm
Distance from rear to centre of fl ue
UNIQ 15:   

155 mm

UNIQ 16 & 20: 

180 mm

Rear fl ue exit 150 mm
Height  to centre of rear fl ue 
UNIQ 15, 16 & 20: 

960 mm

Closed combustion air intake 100 mm
Height to centre of air intake
UNIQ 15, 16 & 20: 

110 mm

Содержание WF15

Страница 1: ... WF16 WF20 1 DANSK INGENIØRKUNST DK INSTALLATIONS OG BRUGSVEJLEDNING WF15 WF16 WF20 UK INSTALLATION MANUAL AND OPERATING INSTRUCTIONS D INSTALLATIONS UND GEBRAUCHSANWEISUNG FR NOTICE D INSTALLATION ET D UTILISATION ...

Страница 2: ...ing af Deres brændeovn er der en række love og bestemmelser i Bygningsreglementet der skal overholdes Disse bestemmelser kan man læse i Bygningsreglementet Bygningsreglementet siger at ved lukkede ildsteder skal brændbare gulve dækkes mindst 30 cm foran fyringsåbningen og mindst 15 cm til hver side Underlaget skal være af ikke brændbar materiale f eks stålplade glasplader klinker eller kunstskifer...

Страница 3: ...rbrændingen sker på den rigtige måde Hvis Deres ovn indvendig får en belægning af hård blank sod er der tegn på en ufuldstændig forbrænding i så fald skal der tilføres mere sekundærluft Det er vigtig at man inden fyring kontroller trækforholdene det kan fx gøres ved at krølle et stykke avispapir sammen ligge det i brændkammeret og antænde det hvis røgen trækker fint ud gennem skorsten er trækforho...

Страница 4: ...burning wood in a smoke control area PREPARATORY WORK AND SAFETY CHECKS IMPORTANT WARNING This stove must not be installed into a chimney that serves any other heating appliance There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room CHIMNEY Chimney Connection Flue Diameter 150mm 175cm2 IMPORTANT When installing the UNIQ 15 16...

Страница 5: ... combustion air This is particularly necessary if the room is double glazed or a flue draught stabiliser is operating in the same room as the appliance The provision of air supply to the stove must be in accordance with current Building Regulations Approved Document J An opening window is not appropriate for this purpose Air inlets must be positioned in such a way that they cannot be blocked An ai...

Страница 6: ... pieces of wood measuring approx 20cm with a combined weight of approx 1 4kg and close the door Leave the air values open for 10 minutes to allow the fire to reach a good temperature Then close primary air valve on ash pan and slide secondary air value to 50 open 75 open on smoke control models Once the fire is hot the primary air slider can be closed fully In the event of a chimney fire Close the...

Страница 7: ...aft b check for blockages in the flue pipe chimney c check the height of the chimney in relation to the surroundings 6 Soot in the chimney a The firewood may be too wet b intake of secondary air may be insufficient Chimney Fires If the chimney is thoroughly and regularly swept chimney fires should not occur However if a chimney fire does occur turn the air control setting to the minimum and tightl...

Страница 8: ...rick 6 fitted UK means such as a soot door After sweeping the chimney the stove flue outlet and the flue pipe connecting the stove to the chimney must be cleaned with a flue brush HETAS Ltd Approval This appliance has obtained HETAS Ltd approval on a safe and fit for purpose level single tick approval for burning wood logs only as detailed in list of recommended fuels above Approval does not cover...

Страница 9: ...le Kaminöfen von Westfire sind mit einer Rauchumlenkplatte ausgestattet sodass der Weg den der Rauch nimmt möglichst lang ist ANSCHLUSS AN SCHORNSTEIN Der Schornstein muss einen Durchmesser von mindestens 15 cm aufweisen was einer Öffnung von 175 cm entspricht Er muss zudem eine Höhe haben die ausreichend Zug gewährleistet und dafür sorgt dass es zu keiner Rauchbelästigung in unmittelbarer Nähe ko...

Страница 10: ...unbefugten technischen Änderungen am Ofen Bei Reparaturen sind ausschließlich von der Fa Westfire ApS empfohlene Ersatzteile zu verwenden Das Rauchrohr ist mit einer Regulierklappe erhältlich die es ermöglicht den Schornsteinzug an Tagen mit starkem Wind zu regulieren Sie darf sich nicht vollständig schließen lassen d h der freie Durchgang muss mind 20 cm betragen Eine Verringerung des Schornstein...

Страница 11: ...jours de grand vent La trappe ne doit pas se fermer complètement mais doit avoir une surface libre d au moins 20 cm2 sur la surface d ouverture totale du conduit Il est également possible d avoir d autres types de limitateurs de tirage par exemple en laissant entrer l air dans la cheminée sans passer par le poêle Les modèles WF15 WF16 et WF20 peuvent être raccordés au conduit de cheminée même lors...

Страница 12: ...rseur de fumées Il peut arriver que l une des plaques Skamol se fende après avoir été heurtée trop violemment par un morceau de bois Cela n a pas d incidence sur la combustion ce qui n est pas le cas de l inverseur de fumées Lorsque les plaques Skamol sont si usées qu elles ne sont plus entières il est temps de les remplacer C est également le cas lorsque les plaques sont fendues à plusieurs endro...

Страница 13: ...24 TØMRERVEJ 3 DK 6800 VARDE TELEFON 45 7522 5352 FAX 45 7522 1352 WWW WESTFIRE DK E MAIL INFO WESTFIRE DK WESTFIRE 2009 Der tages forbehold for trykfejl 14136 Mediegruppen Reklamebureau ...

Отзывы: