Overload protection
When you have a power overload on the output load, for poker between 3000-3450W, the inverter can deliver
power continuously for 3 minutes; then, if the overload condition persists, the overload protection is activated and
the AC output is disabled. If the power exceeds 4500W protection is activated almost immediately, in about 10sec.
To restore the normal state of operation, the inverter must be switched off and then on again. Before restoring, you
can read the cause of failure from the visual indication of the load:
Table of error codes
Intervention of
overload
protection for an output
power between
3000W ÷3450W
for at least 3min.
Remove the cause of the overload on output and
make a new start of the inverter through the
ON/OFF button.
Intervention of anomaly protection for
battery
voltage
in input.
Check the wiring of the battery
and make a new
start of the inverter through the ON/OFF button.
Intervention of
overload
protection for an output
power between 3450W ÷4500W for at least 10sec.
Remove the cause of the overload on output and
make a new start of the inverter through the
ON/OFF button.
Intervention of the working
over temperature
protection.
Check the aeration capacity of the installation site
and make a new start of the inverter through the
ON/OFF button.
Intervention of
overload
protection for an output
power >
4500W
instantaneous.
Remove the cause of the overload on output and
make a new start of the inverter through the
ON/OFF button.
Intervention of protection of battery aging.
Control battery conditions and, possibly, make a
new start of the inverter through the ON/OFF
button.
Intervention
of
instantaneous
short
circuit
protection.
Remove the cause of short circuit on output and
make a new start of the inverter through the
ON/OFF button.
STAND-BY status. After turning off the equipment
through the ON/OFF button, it is displayed the
status of stand-by waiting for a new start.
Fig. 12 Inverter error codes
Power limitation curves
Fig. 13 Power derating curves