Key points for a variable flow primary system:
In order for the components of the system to operate optimally, it is important to take some key points
into account:
1) minimum water flow and bypass valve supplied:
The inverter Driven pump also includes the two-way bypass valve supplied with it and adequately
designed in relation to the size of the unit.
If on the system side the heat load is very low, this means that many utilities are closed, which results
in an increase in pressure drops. The inverter counters the Dp1 variation detected by the sensor by
reducing the speed of the pump and the flow rate as a result. However, there is a limit lower than the
flow rate value below which the heat exchange towards the evaporator is not performed properly and
the temperature drop processed by the evaporator increases, which might activate the anti-freeze
alarm. The two-way control valve adequately selected based on the machine model prevents this
alarm from being triggered, thereby ensuring the minimum water flow rate towards the evaporator.
2)”Minimum thermal flywheel”:
In the event of a heat load close to zero, with the unit in maximum power partialisation conditions, the
pump set at the minimum flow rate and closed system valves, the machine might stop due to the anti-
freeze alarm.
To prevent this problem, there must be a “minimum thermal flywheel” in the evaporator / bypass valve
section.
Below is the formula to determine it:
The water content of the evaporator, of the hydraulic module’s inertial tank (if there is one) and of the
pipes between the bypass and the evaporator itself may contribute to determine the “minimum thermal
flywheel”.
However, it is advisable to use three-way valves on a certain number of utilities on the system to
ensure a minimum flow of water towards the system in any condition.
Please note: if this accessory is installed, the minimum cold water temperature at the outlet cannot
drop below 7°C. Moreover, the temperature variation considered under the conditions specified in the
project must be 5°C. Please contact our sale department for the minimum water temperature at the
outlet (production of cold water) and for different temperature drop values.
You should also contact the sales department in the event of production of hot water for temperatures
at the outlet below 40°C.
Attention: the “minimum thermal flywheel” must be between the bypass valve and the evaporator. This
is a pa
rt of the “minimum water content of the system” described in the relative chapter; the difference
between the “minimum water content of the system” and the “minimum thermal flywheel” can instead
be positioned in any area of the system.
Содержание Zeta Echo/LN
Страница 11: ...Western Airconditioning B V reserves the right to alter specifications 11...
Страница 16: ...Western Airconditioning B V reserves the right to alter specifications 16...
Страница 17: ...Western Airconditioning B V reserves the right to alter specifications 17...
Страница 18: ...Western Airconditioning B V reserves the right to alter specifications 18...
Страница 19: ...Western Airconditioning B V reserves the right to alter specifications 19...
Страница 20: ...Western Airconditioning B V reserves the right to alter specifications 20...
Страница 21: ...Western Airconditioning B V reserves the right to alter specifications 21...
Страница 22: ...Western Airconditioning B V reserves the right to alter specifications 22...
Страница 23: ...Western Airconditioning B V reserves the right to alter specifications 23...
Страница 24: ...Western Airconditioning B V reserves the right to alter specifications 24...
Страница 25: ...Western Airconditioning B V reserves the right to alter specifications 25...
Страница 26: ...Western Airconditioning B V reserves the right to alter specifications 26...
Страница 27: ...Western Airconditioning B V reserves the right to alter specifications 27...
Страница 28: ...Western Airconditioning B V reserves the right to alter specifications 28...
Страница 29: ...Western Airconditioning B V reserves the right to alter specifications 29...
Страница 30: ...Western Airconditioning B V reserves the right to alter specifications 30...
Страница 31: ...Western Airconditioning B V reserves the right to alter specifications 31...
Страница 32: ...Western Airconditioning B V reserves the right to alter specifications 32...
Страница 33: ...Western Airconditioning B V reserves the right to alter specifications 33...
Страница 34: ...Western Airconditioning B V reserves the right to alter specifications 34...
Страница 35: ...Western Airconditioning B V reserves the right to alter specifications 35...
Страница 36: ...Western Airconditioning B V reserves the right to alter specifications 36...
Страница 37: ...Western Airconditioning B V reserves the right to alter specifications 37...
Страница 38: ...Western Airconditioning B V reserves the right to alter specifications 38...
Страница 39: ...Western Airconditioning B V reserves the right to alter specifications 39...
Страница 40: ...Western Airconditioning B V reserves the right to alter specifications 40...
Страница 41: ...Western Airconditioning B V reserves the right to alter specifications 41...
Страница 42: ...Western Airconditioning B V reserves the right to alter specifications 42...
Страница 43: ...Western Airconditioning B V reserves the right to alter specifications 43...
Страница 44: ...Western Airconditioning B V reserves the right to alter specifications 44...
Страница 45: ...Western Airconditioning B V reserves the right to alter specifications 45...
Страница 46: ...Western Airconditioning B V reserves the right to alter specifications 46...
Страница 47: ...Western Airconditioning B V reserves the right to alter specifications 47...
Страница 48: ...Western Airconditioning B V reserves the right to alter specifications 48...
Страница 49: ...Western Airconditioning B V reserves the right to alter specifications 49...
Страница 50: ...Western Airconditioning B V reserves the right to alter specifications 50...
Страница 51: ...Western Airconditioning B V reserves the right to alter specifications 51...
Страница 52: ...Western Airconditioning B V reserves the right to alter specifications 52...
Страница 53: ...Western Airconditioning B V reserves the right to alter specifications 53...
Страница 54: ...Western Airconditioning B V reserves the right to alter specifications 54...
Страница 55: ...Western Airconditioning B V reserves the right to alter specifications 55...
Страница 56: ...Western Airconditioning B V reserves the right to alter specifications 56...
Страница 57: ...Western Airconditioning B V reserves the right to alter specifications 57...
Страница 58: ...Western Airconditioning B V reserves the right to alter specifications 58...
Страница 59: ...Western Airconditioning B V reserves the right to alter specifications 59...
Страница 60: ...Western Airconditioning B V reserves the right to alter specifications 60...
Страница 61: ...Western Airconditioning B V reserves the right to alter specifications 61...
Страница 62: ...Western Airconditioning B V reserves the right to alter specifications 62...
Страница 63: ...Western Airconditioning B V reserves the right to alter specifications 63...
Страница 64: ...Western Airconditioning B V reserves the right to alter specifications 64...
Страница 65: ...Western Airconditioning B V reserves the right to alter specifications 65...
Страница 66: ...Western Airconditioning B V reserves the right to alter specifications 66...
Страница 67: ...Western Airconditioning B V reserves the right to alter specifications 67...
Страница 68: ...Western Airconditioning B V reserves the right to alter specifications 68...
Страница 69: ...Western Airconditioning B V reserves the right to alter specifications 69...