3. Example: SKOV4-28
d
4
c
3
b
a
Table 10 Indoor Unit
Table 11 Liquid Refrigerant Pipe
2
1
Fig.11
Serial No.
a
b
c
d
Diameter
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Length
20
15
15
15
The total length of each liquid refrigerant pipe is: a+b+c=20+15+15+15=65m
Thus, the minimum additional refrigerant charge=(65-40)×0.022=0.55kg
(Note: no additional refrigerant is needed for the liquid pipe within 40m)