10

6043-2202

Test 

Test commands can be sent from a standard terminal with an RS-232 connection. The
terminal is connected to the master MA-43  (address 00), which is the only MA-43 that
can act on the test commands. To be able to give test commands the MA-43 has to be
in the test mode. Test mode can only be entered directly after power up or reset of the
master MA-43. To enter the test mode, send an ASCII 0 as the first character to the
master MA-43 after power up or reset. The MA-43 then answers with a character string
(***** MA-43 TEST MODE ******). During the test phase normal data traffic will be
disturbed. The MA-43 will leave testmode with a reset as soon as a start character is
sent to the master MA-43.

The following test is available:TEST1.

Test 1

The test is designed to be used to control an installation. TEST1 first resets all slaves,
then all slave addresses are polled. The slaves which recognises their own address ans-
wer with a configuration message. 10 slaves will be displayed in ascending order, the user
is asked to press a key to continue to see 10 new slaves, only the answering slaves will
be displayed. The units will answer with the information seen below. To test the RS-232
hardware the slaves have to be looped back between TD and RD (position 2 and 3 in
the 25-pole D-sub). The test can run without TD and RD looped on the slaves, but the
RS-232 interface will not be tested.

Example

Address

Baudrate

Flow control

Buffered

Looped

01

9600,e,8,1

RTS/CTS

Buffered

OK

03

4800,n,7,1

XON/XOFF

No

OK

0A

4800,n,7,1

XON/XOFF

No

No loop

Addresses and commands

All commands and addresses are only accepted through the master MA-43.

Decimal

Hex

Address/Command

0

00

Master unit.

1–239

01 – EF

Slave units.

240

F0

Broadcast.

241–253

F1 – FD

Reserved.

254

FE

Reset, resets the whole MA-43 system.

255

FF

Reserved.

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles

Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

Содержание MA-43

Страница 1: ...MA 43 H Westermo Teleindustri AB 2001 REV A Galvanic Isolation Transient Protection Balanced Transmission CE Approved AUDIN 8 avenue de la malle 51370 Saint Brice Courcelles Tel 03 26 04 20 21 Fax 03...

Страница 2: ...AUDIN 8 avenue de la malle 51370 Saint Brice Courcelles Tel 03 26 04 20 21 Fax 03 26 04 28 20 Web http www audin fr Email info audin fr...

Страница 3: ...age transmitter and receiver 7V Surge capacity 0 6 kW for 1 ms Transient protection Power Line Yes Yes Isolation Galvanic isolation with opto coupler data transmission and transformer supply Isolation...

Страница 4: ...1 2 3 4 S4 04 EOT ON 1 2 3 4 S4 1B ESC Master Number of start charter ON 1 2 3 4 S4 4 ON 1 2 3 4 S4 1 Master Timed address frame ON 1 2 3 4 S4 Yes ON 1 2 3 4 S4 No Master Reserved ON 1 2 3 4 S4 Not in...

Страница 5: ...3 4 5 6 7 8 S5 No ON 1 2 3 4 5 6 7 8 S5 Even ON 1 2 3 4 5 6 7 8 S5 No ON 1 2 3 4 5 6 7 8 S5 600 ON 1 2 3 4 5 6 7 8 S5 1200 ON 1 2 3 4 5 6 7 8 S5 2400 ON 1 2 3 4 5 6 7 8 S5 4800 ON 1 2 3 4 5 6 7 8 S5...

Страница 6: ...ta for the addressed unit There is no limit for the number of data bytes that can be sent to and from an addressed slave after the address frame The address frame is made of two parts a start sequence...

Страница 7: ...character If another character is received instead of a start character this character and any previously accepted start characters for this address frame search is transmitted and the MA 43 looks fo...

Страница 8: ...s character and any previously accepted start characters for this address frame search are transmitted and 10 new byte times have to pass before the MA 43 looks for a new start character If the time e...

Страница 9: ...e user When the user equipment is ready to receive characters RTS has to be high LED Indicators MA 43 has 7 LED indicators The LEDs has the following function POWER Fixed light indicates normal functi...

Страница 10: ...The slaves which recognises their own address ans wer with a configuration message 10 slaves will be displayed in ascending order the user is asked to press a key to continue to see 10 new slaves onl...

Страница 11: ...position A and S2 in position 1 the unit will become the address A1 Adress 00 will become master Only one master is allowed per system Direction Connection CCITT V 11 no Description Receiver 1 A R Re...

Страница 12: ...rd it can help to shift A and B if the unit does not work Transmission range interface 2 Use twisted pair cable Max transmission range 1200 metres cable specifications 0 3 mm2 and capacitance 42pF m T...

Страница 13: ...S4 No codes ON 1 2 3 4 S4 Result codes Slave Buffered ON 1 2 3 4 S4 Yes ON 1 2 3 4 S4 No Slave Mode ON 1 2 3 4 S4 Hayes ON 1 2 3 4 S4 Normal Factory settings ON 1 2 3 4 S4 Master ON 1 2 3 4 S4 Slave S...

Страница 14: ...period of 10 byte times before the 10 byte times with 9 600 baud is approximately 10 ms The time is at least 100 baud rate The time between the signs has to be less than 300 ms If any other command w...

Страница 15: ...AUDIN 8 avenue de la malle 51370 Saint Brice Courcelles Tel 03 26 04 20 21 Fax 03 26 04 28 20 Web http www audin fr Email info audin fr...

Страница 16: ...0 7254 95400 0 Fax 49 0 7254 95400 9 E Mail info westermo de Web www westermo de Westermo Data Communications Ltd Unit 14 Talisman Business Centre Duncan Road Park Gate Southampton SO31 7GA Phone 44 0...

Отзывы: